RF Quick Start Guide for Models SPX-5631, SPX-5641    

1.  Check that all units & parts are included, and antennas are properly 

connected:

Central unit  

 Remote unit  

 6 connectors (2 each: 2-pin, 8-pin, 10-pin)  

 Warranty

2.  Bench test. (Complete before field installation for easier troubleshooting).
a.  Set up near control panel. Use spare reader. Place Central & Remote at least 24" apart.
b.  Connect suitable power supply (8-16 Vdc @ 300 mA) to each unit.
c.   After short delay, Status LED will pulse green on each unit (power/communication). 
d.  Touch jumper wire from Central's ground pin to Relay 1 input. Remote's Relay 1 activates with audible click. 

Multimeter/continuity tester shows Remote's Relay 1 "normally open" contacts closing when Central's Relay 1 
input is activated.

e. Select DIP Switch Settings as needed (see below). 
f. Connect reader to Remote; connect Central to panel. Scan card to ensure proper read.

DIP Switch Settings 
Default settings:

Standard Wiegand is the default Interface Type.

By default, units are configured & labeled as one Remote and one Central unit.

By default, Supervision relay and pullup resistors are disabled.

Configuration Mode: 

To select alternate interface, temporarily switch to Configuration Mode.

a) Power off both Suprex units.
b) Turn on DIP switch 1 on both units.
c) Set DIP switches as described below for appropriate interface:
d) Power on both Suprex units. Status LED should be solid green. 
e)   Power off both Suprex units. Turn off all DIP switches on both units, then reselect Run Mode settings.

Run Mode: 

Select Run Mode settings as described below, then power on both Suprex units 

                    to begin operating in Run Mode.

Relay locations

Relay 1 & 2 Outputs: Located on the Remote Unit / Triggered from the Central Unit.
Relay 3 & 4 Outputs: Located on the Central Unit / Triggered from the Remote Unit.

Central / Remote Select

Turn DIP switch 3 on for Central Mode / turn off for Remote 

Mode

Remote Digital/Analog Relay 

Select  

Turn Remote Unit's DIP switch 2 on for digital input /  off for 

analog input

Supervision Relay                    

(Relay 3, Central Unit)

Turn Central Unit's DIP switch 4 on for supervision relay / off 

for normal relay

Supervision Relay                    

(Relay 1, Remote Unit)

Turn Remote Unit's DIP switch 4 on for supervision relay / 

off for normal relay

Pullup Resistor Select

Turn on DIP switch 5 to enable pullup resistors /                         

off to disable (applicable units)

EXP Select (for no EXP)

Turn off DIP switches, 6, 7, and 8 on both units

EXP Select (for 1 EXP)

Turn on DIP switch 8 on both units

EXP Select (for 2-7 EXPs)

See manual

Default: Standard Wiegand

Turn on DIP switch 8 on both units

Keypad (Wiegand/No Filter)

Turn on DIP switch 7 on both units

F/2F (Unsupervised)

Turn on DIP switches 6, 7, 8 on both units

Strobed Rising Edge (MR-5)

Turn on DIP switches 7 and 8 on both units

Strobe Rising Edge (Dorado 
644)

Turn on DIP switch 6 on both units

Strobed Rising (MagTek)

Turn on DIP switches 6 and 8 on both units

Strobed Falling Edge

Turn on DIP switches 6 and 7 on both units