Cypress Suprex EXP-2000 Скачать руководство пользователя страница 19

Before using EXP-2000 Expansion modules with the SPX-7200 system, it will be necessary to perform a short 
configuration process.  This process determines if the 7200 will utilize expansion modules, and if so, how many will be 
used with the system.  Each SPX-7200 link can support up to 8 expansion modules.  

SPX-7200 units are shipped in the factory default condition.  Factory default units will be setup to function as SPX-7200 
units without expansion modules.  Only communications between the 2 gateway units will be active.  

Setup Process

:

1. With power off, set the DIP switch on the Central unit according to the table below.

2. Apply power.
    The Diagnostic LED should display a steady Green indication.

3. Remove power
    Set DIP switch #1 OFF.  Any other DIP switches can now be set  as required (Reader family/ Pullup resistors).
    The Central unit is now configured.  No expansion module configuration is required for the Remote unit.

4. The expansion modules will need to be setup and correctly addressed. See EXP-2000 manual for details of     
    Expansion module setup and configuration.  The Expansion units are addressed, and added to the system as pairs.

5.  Connect the Expansion modules into the system as indicated in this wiring diagram.

Operation with Expansion Modules:

The SPX-7200 system Remote and Central gateway units will operate as a standard pair Suprex® units,  all of the I/O 
and data terminals are available for use with readers and access control systems.  There are some minor differences in 
operation when using the expansion modules.  Each pair of 

1. The Diagnostic LED on the Gateway units will indicate the status of the main (gateway) communication link only.

2. The Alarm relay on the Central Gateway unit will deactivate (indicate alarm condition) when the communication fails 
between the Gateway units or ANY of the the Remote or Central Expansion units.

3.  Paired Expansion units will be functionally similar to the standard SPX-1300 Suprex® system.

"

"

"

         Switch

"

"

"

1  2  3  4  5  6  7  8

Gateway only - No EXP

"

1  0  0  1  0  0  0  0

1 EXP Pair used 

""

1  0  0  1  0  0  0  1

2 EXP Pair used

" "

1  0  0  1  0  0  1  0

3 EXP Pair used

" "

1  0  0  1  0  0  1  1

4 EXP Pair used

" "

1  0  0  1  0  1  0  0

5 EXP Pair used

" "

1  0  0  1  0  1  0  1

6 EXP Pair used

" "

1  0  0  1  0  1  1  0

7 EXP Pair used

" "

1  0  0  1  0  1  1  1

Central Unit Configuration Mode Settings

1 2 3 4 5 6 7 8

1 = ON

0 = OFF

SPX-7200  Setup - Using Expansion Modules 

See  EXP-2000 Manual for further setup instructions

Содержание Suprex EXP-2000

Страница 1: ...SPX 7200_MAN_082112 SPX 7200 Series Suprex Reader Extender Ethernet Operations Manual EXP 2000 SPX 7200...

Страница 2: ...for additional door gate on a single Ethernet link Economical expansion capabilities using Suprex Lynk technology Physical SPX 7200 Aluminum Enclosure 4 45 x 3 08 x 2 0 Each Unit SPX 7200 Aluminum En...

Страница 3: ...x x x Wiegand Wiegand No Filter Strobed Rising Edge MR 5 Strobed Rising Edge Dorad0 644 Strobed Rising Mag Tek Strobed Falling Edge Reserved F2F x ON 1 2 3 4 5 6 7 8 Dip switch 4 is ON Disable Pullup...

Страница 4: ...o 16 VDC Ground Diagnostic LED R1 Input Controls Strike on Remote R1 IN LED In D1 Data Out D0 Clock Out Card Reader DC Power Supply R1 N O R1 Com R1 N C Door Strike Output 8 to 16 VDC Ground Diagnosti...

Страница 5: ...Cypress Suprex SPX 7200 Enclosure Dimensions 1 70 2 00 3 08 0 80 0 80 3 15 4 45 0 20 X 4...

Страница 6: ...not receiving communication from the Central REMOTE AND CENTRAL UNITS FLASHING BETWEEN RED GREEN The Central is not Receiving communication from the Remote Operating modes By setting DIP switch 1 to...

Страница 7: ...switch to the required reader and panel format 6 If a reader and panel is accessible connect the reader to the Remote unit and the Central unit to the panel and verify that card reads are being accept...

Страница 8: ...e Net mask comes set from the factory at 255 255 255 0 The Net mask setting can be changed using the Xport Device Installer if necessary Changing the Net mask It will be necessary for the Host Compute...

Страница 9: ...PX 7200 1 Start the Lantronix XPort Installer software The startup screen is shown above 2 Click the Search button after a brief delay the connected device s should appear in the device list as shown...

Страница 10: ...ialog box shown above will open Enter an IP address for the unit The IP address should be unique and on the same subnet as the host computer Click on the OK button after the IP address has been entere...

Страница 11: ...esses have been assigned to both units select the CENTRAL unit in the device list 6 Select the Telnet option and click OK Once both units have had their IP addresses set it will be necessary to tell t...

Страница 12: ...Setting IP Address SPX 7200 7 You should now have an open window like this Press the ENTER key to enter setup mode 8 A list of options will be presented select Option 1 Channel 1...

Страница 13: ...settings have been entered Keep in mind that this is the CENTRAL unit and we are entering the address of the REMOTE unit 10 When the address has been entered click through any remaining parameters wit...

Страница 14: ...are two relays available for accessory outputs at the Remote end Either relay can be used to provide the Door Strike or Gate activation function This example uses Relay 1 Wiring Example Door Strike Fo...

Страница 15: ...rom the Remote and Central units without the need to run additional wiring The accessory control I O use active low inputs When the inputs are floating nothing connected the associated output will be...

Страница 16: ...rrow denotes direction of command signal Relay 1 IN Input Signal Relay 1 N O Relay 1 Com Relay 1 N C Contact Outputs Suprex Central Suprex Remote Relay 2 N O Relay 2 Com Relay 2 N C Contact Outputs Re...

Страница 17: ...ion when either the Relay 3 input on the remote is active OR the Remote unit is unable to communicate with the Central unit See APP NOTE FOR DETAILS Suprex Remote Relay 3 IN Input Signal 5Volts DC Max...

Страница 18: ...values locally at the panel so that the correct supervised status is maintained At the same time the Remote unit must maintain supervision of the wires connected to the relays and switches that are co...

Страница 19: ...ssed and added to the system as pairs 5 Connect the Expansion modules into the system as indicated in this wiring diagram Operation with Expansion Modules The SPX 7200 system Remote and Central gatewa...

Страница 20: ...485 Link Multi drop Card Reader Control and I O ACS SPX 7200C 1 EXP 2000C 3 EXP 2000C 2 EXP 2000R 2 EXP 2000R 3 SPX 7200R 1 Cypress Suprex Ethernet Solution with Wiegand expansion modules Door Parkin...

Страница 21: ...485 485 5 VDC Out Prog Res 4 Prog Res 3 LED Input D1 Data Out D0 Clock Out RLY4 N O RLY4 Com RLY4 N C RLY3 N O RLY3 Com RLY3 N C RS232 Out RS232 In Ground Aux Out Relay2 Input Relay1 Input Access Cont...

Страница 22: ...m RLY2 N C RLY1 N O RLY1 Com RLY1 N C RS232 Out RS232 In Ground Aux In N C N C 485 485 5 VDC Out RLY4 Input 5V RLY3 Input 5V LED Output D1 Data Input D0 CLK Input DC Power Supply Card Reader EXP EXP L...

Отзывы: