background image

20

The following applies to these products: SPX-7500.

This application note describes the connections necessary to convey supervised contact status over a Suprex®. The 

configurations described in this application note should apply to most panels which utilize supervised contacts. When 
connected as described, the Suprex® provides a supervised signal to the panel interface by reading the supervised status 

of the contacts connected to the Suprex® Remote unit.  

Theory of operation: 

The access control panel is looking for a certain value of resistance connected to the supervised 

contact terminals. The Suprex® Central unit will provide these resistance values locally at the panel so that the correct 

supervised status is maintained. At the same time, the Remote unit must maintain supervision of the wires connected to 
the relays and switches connected to the remote access point. The contact supervision is provided by the Remote unit.  

The Suprex® system does this by comparing the value of programming resistor at the Central unit with the resistance seen 
at the Remote interface terminals. When there is a difference in the two values, the Relay on the Central unit is activated.
There are two different 

examples. One example is 
monitoring a normally closed 

contact at the Remote unit, and 
the other example is monitoring 
a normally open contact at the 

Remote unit. In the examples 
given, a normally closed 
contact will require a 
programming resistor of 1K and 
a normally open contact will 

require a programming resistor 
of 2K. Other resistor values can 

be used, but 1K resistors are 
the most common. Other 
resistance values will require 

different value(s) for the 
programming resistor(s). 

+8 to +16 VDC

Ground

exp(+)
exp(-)
+5V Out
P R 4
P R 3
LED In 
D1/Data Out
D0/Clock Out

Relay 4 N.O.

Relay 4 Com

Relay 4 N.C.

Relay 3 N.O.

Relay 3 Com

Relay 3 N.C.

Ground

Aux Output

Relay 2 Input
Relay 1 Input

+8 to +16 VDC

Ground

exp(+)
exp(-)
+5V Out
Relay 4 Input
Relay 3 Input
LED In 
D1/Data In
D0/Clock In

Relay 2 N.O.

Relay 2 Com

Relay 2 N.C.

Relay 1 N.O.

Relay 1 Com

Relay 1 N.C.

Ground

Aux Input

Not Used
Not Used

+8 to +16 VDC

Ground

exp(+)
exp(-)
+5V Out
P R 4
P R 3
LED In 
D1/Data Out
D0/Clock Out

Relay 4 N.O.

Relay 4 Com

Relay 4 N.C.

Relay 3 N.O.

Relay 3 Com

Relay 3 N.C.

Ground

Aux Output

Relay 2 Input
Relay 1 Input

Central 

Remote

Remote

Central 

Normally Closed Contact

Normally Open Contact

1K

1K

Input +

Input -

+8 to +16 VDC

Ground

exp(+)
exp(-)
+5V Out
Relay 4 Input
Relay 3 Input
LED In 
D1/Data In
D0/Clock In

Relay 2 N.O.

Relay 2 Com

Relay 2 N.C.

Relay 1 N.O.

Relay 1 Com

Relay 1 N.C.

Ground

Aux Input

Not Used
Not Used

1K

1K

2K

1K

1K

1K

Input -

Input +

Application Note on using Supervised contacts with the Suprex® RS-485 Series

Содержание 816684001659

Страница 1: ...x RS 485 SPX 7500 Wired Reader Extender Product Manual Cypress Integration Solutions 35 Years of Access Control Ingenuity CypressIntegration com 2019 Cypress Computer Systems 1778 Imlay City Road Lape...

Страница 2: ...O Interface Wiegand maximum 248 bits pass through Strobed Clock Data F 2F Unsupervised LED 0 30V Range and Cable Requirements Typical range of 4000 ft 22 AWG Shielded Twisted Pair Additional Features...

Страница 3: ...n Mode Settings 8 DIP Switch Map 9 Quick Reference for Typical Connections 10 Troubleshooting 11 Accessory I O I O Overview 12 Central Relay Inputs 13 Relay 1 2 I O 14 Remote Relay Inputs 15 Relay 3 4...

Страница 4: ...Series Physical Dimensions and Mounting Hole Locations All dimensions are listed in inches EXP Enclosure 0 120 X 4 4 125 2 890 3 155 2 121 2 364 EXP 2000 SPX 7500 Enclosure 0 120 X 4 3 065 2 770 4 06...

Страница 5: ...y 4 N O Relay 4 COM Relay 4 N C Relay 3 N O Relay 3 COM Relay 3 N C Ground Aux Output Relay 2 Input Relay 1 Input 8 16VDC Input Ground EXP EXP 5VDC Output Relay 4 Input Relay 3 Input LED Output D1 Dat...

Страница 6: ...e powered by a suitable power supply For testing purposes the units can share the same power supply Basic Bench Test During initial setup refer to the Run Configuration mode settings pgs 7 9 1 Connect...

Страница 7: ...ng properly Check that all connected EXPs are powered and properly connected For details on setting Configuration Mode see pgs 7 9 OPERATING MODES Wired Suprex products have 3 operating modes Run Mode...

Страница 8: ...select Run Mode settings When switching to Run Mode always reselect Run Mode settings Central Remote Select Turn DIP switch 3 on for Central Mode turn off for Remote Mode Remote Digital Analog Relay...

Страница 9: ...tion Mode setting the unit will need to be powered off turn DIP 1 on and other Configuration DIP Switches as needed power the unit on and the Status LED will be solid green The solid green LED means t...

Страница 10: ...Ground exp exp 5V Out P R 4 P R 3 LED In D1 Data Out D0 Clock Out Relay 4 N O Relay 4 Com Relay 4 N C Relay 3 N O Relay 3 Com Relay 3 N C Ground Aux Output Relay 2 Input Relay 1 Input Door Strike Out...

Страница 11: ...he access control panel data port are functional by directly connecting the reader to the data port and passing card data Check Suprex circuit boards for any signs of visual damage such as burnt trace...

Страница 12: ...vated and will hold this state for as long as the Relay Input is set to 0Volts The Relay Inputs can be tested by making a jumper connection to ground and monitoring the change in continuity of the Rel...

Страница 13: ...emote unit will be activated When the relay is activated the Relay Output pins will change continuity from N C and COM to N O and COM not shown in diagram Cypress Suprex RS 485 Series Accessory I O Ce...

Страница 14: ...xp 5V Out Relay 4 Input Relay 3 Input LED Out D1 Data In D0 Clock In Relay 2 N O Relay 2 Com Relay 2 N C Relay 1 N O Relay 1 Com Relay 1 N C Ground Aux Input Not Used Not Used Remote 8 to 16 VDC Groun...

Страница 15: ...ay output pins will change continuity from N C and COM to N O and COM not shown in diagram Relay 3 can used to send signals to the access panel while Supervision mode is active but it is important to...

Страница 16: ...Ground exp exp 5V Out P R 4 P R 3 LED In D1 Data Out D0 Clock Out Relay 4 N O Relay 4 Com Relay 4 N C Relay 3 N O Relay 3 Com Relay 3 N C Ground Aux Output Relay 2 Input Relay 1 Input Central 8 to 16...

Страница 17: ...ot Used pin is the new Relay 4 input pin Use the diagram below as a reference For most applications the analog relay inputs are sufficient But for instances where a significant delay is noticed in the...

Страница 18: ...O Signal Diagram below shows how this signal is passed through he SPX 7500 Ground LED Out Data1 Data 0 N O COM Access Control Panel Card Reader Power Ground LED IN Data 1 Data 0 LED I O Signal Diagram...

Страница 19: ...In pin The AUX I O Signal Diagram below shows how this signal is passed through the SPX 7500 AUX I O Signal Diagram Ground Input Data1 Data 0 N O COM Access Control Panel Card Reader Power Ground Out...

Страница 20: ...ormally closed contact at the Remote unit and the other example is monitoring a normally open contact at the Remote unit In the examples given a normally closed contact will require a programming resi...

Страница 21: ...x Central and Remote units must be configured with the total number of EXP pairs being used This is configured in the Run Mode settings and is controlled by DIP switches 6 7 and 8 Change settings on b...

Страница 22: ...N C Ground Aux Output Relay 2 Input Relay 1 Input 8 to 16 VDC Ground exp exp 5V Out P R 2 P R 1 LED In D1 Data Out D0 Clock Out Relay 4 N O Relay 4 Com Relay 4 N C Relay 3 N O Relay 3 Com Relay 3 N C...

Страница 23: ...k In Relay 2 N O Relay 2 Com Relay 2 N C Relay 1 N O Relay 1 Com Relay 1 N C Ground Aux Input Not Used Not Used 8 to 16 VDC Ground exp exp 5V Out Relay 4 Input Relay 3 Input LED Out D1 Data In D0 Cloc...

Отзывы: