Cypress Envirosystems WPT-800-DB Series Скачать руководство пользователя страница 10

 

 

WPT-DB Installation Manual  

Document No. 910-00014-01, Rev. 04 

 

 

Page 10 of 20 

 

1.  From  the  home  screen,  press  all  three  buttons  simultaneously  to  enter 

“Programming Mode” and enter the password (see section 2.2.1 ). 

2.  Press  the  OVR  button  5  times  to  navigate  past  the  Network  and  Node  ID 

programming screen and into the Celsius/Fahrenheit screen. 

3.  Press 

 or 

 to toggle between Celsius and Fahrenheit. 

4.  Press OVR to accept the C/F change. 

5.  Continue to press OVR to exit Programming Mode. 

6.  Verify that the ambient temperature is displayed in the selected units (C or F). 

2.2.4 

Standalone (RF Mode) On/Off  

The  WPT-DB  can  also  be  used  as  a  standalone  pneumatic  thermostat.    In  this  setup, 
the wireless radio is turned off to preserve battery life.  If the radio remains on without a 
wireless network, the WPT-DB  will continually search  for a network, which reduces the 
overall battery life.  To turn off the radio, perform the following: 

1.  From  the  home  screen,  press  all  three  buttons  simultaneously  to  enter 

“Programming Mode” and enter the password (see section 2.2.1 ). 

2.  Press the OVR button 6 times to navigate past the  Network, Node ID, and the C/F 

screen into the Standalone On/Off screen. 

3.  Press all three buttons simultaneously to toggle between Standalone (RF Mode) On 

and Off.   In this menu, when the battery icon is empty, RF is off and the device is in 
standalone mode.  When the battery icon is full, RF is on and the device requires a 
Wireless Network. 

4.  Press OVR to accept the Standalone changes. 

NOTE:  The  Occupancy  state  of  a  WPT-DB  in  Standalone  is  always  “Occupied”. 

Occupancy Override will not be available, see section 3.2.  

2.2.5 

Selecting the Deadband Range – Cool Above and Heat Below 

The deadband is a temperature range where the WPT-DB will maintain the control 
pressure. The upper end of the range is referred to as the “Cool Above” temperature, 
and the lower end of the range is referred to as the “Heat Below” temperature. To set 
the Deadband range, perform the following: 

1.  From the home screen, press all three buttons simultaneously to enter the 

“Programming Mode” and enter the password. 

2.  Press the OVR button 7 times to navigate past the Network, Node ID, C/F screen 

and Standalone On/Off screen. The first temperature to set is the “Cool Above” 
temperature, or the upper end of the deadband temperature range. Use the 

 or 

 

buttons to change this value. 

3.  Press the OVR button to accept the “Cool Above” temperature, and now set the 

“Heat Below” temperature using the 

 or 

 buttons.  

4.  Press the OVR to accept the “Heat Below” temperature and exit the programming 

mode. 

NOTE:  Cool Above must always be greater than Heat Below.  

 

Содержание WPT-800-DB Series

Страница 1: ...of the legacy pneumatic HVAC systems 1 1 Components The WPT DB 800 Series kit includes the following components WPT DB Universal Wall Bracket Mounting screws 6 x 1 self tapping x2 Wall Anchors CR123 b...

Страница 2: ...may not have a lot of slack be careful that the tubes do not retract into the wall In a 2 pipe system note the positions of branch and main tubes ESD Handling Precautions Warning The WPT DB contains E...

Страница 3: ...ult if the end of the lever is allowed to move left or right by more than 1 16 Figure 2 WPT DB Lever 2 1 2 Installing the WPT DB The WPT DB is installed in the existing thermostat location using the U...

Страница 4: ...g is aligned with the air tube s The Universal Wall Bracket is shown in Figure 4 Figure 4 Universal Wall Bracket 4 Pull the air tubes through the central opening of the Universal Wall Bracket 5 Affix...

Страница 5: ...the batteries and close the top cover The battery polarities are as shown in Figure 7 Figure 7 WPT DB Batteries 2 1 3 Installing Replacing Batteries Replace battery with Type CR123A that meet UL 1642...

Страница 6: ...with clean water and consult a physician immediately Do not use new and used batteries together Do not use different types of batteries together Do not apply strong pressure to the batteries nor handl...

Страница 7: ...WPT DB Installation Manual Document No 910 00014 01 Rev 04 Page 7 of 20 Figure 8 WPT DB Menu Structure...

Страница 8: ...g this period the WPT DB is attempting to discover its nearest RWALs and HUSB This process should not be disturbed Wait for the dy to disappear from the LCD before performing any additional operations...

Страница 9: ...6 Repeat steps 4 and 5 to configure D2 D3 and D4 of the node ID NOTE While the node ID is being configured the corresponding bar of the battery indicator flashes Figure 11 Configuring Node ID 4321 7 A...

Страница 10: ...ultaneously to toggle between Standalone RF Mode On and Off In this menu when the battery icon is empty RF is off and the device is in standalone mode When the battery icon is full RF is on and the de...

Страница 11: ...nction 2 4 Calibrating the WPT DB 1 Remove the front cover of the WPT DB and make sure that the WPT DB is acclimatized to the ambient temperature NOTE This can take 5 to 10 minutes after attachment to...

Страница 12: ...the end of the lever is allowed to move left or right by more than 1 16 NOTE Ensure that there is at least one thread of calibration screw adjustment above the top surface of the Friction Clip or not...

Страница 13: ...onfirmation screen will appear and flash the stored control pressure for 3 seconds Repeat the calibration procedure if this value does not match the desired control pressure NOTE The WPT DB will autom...

Страница 14: ...using the or buttons To change the deadband range Press the or button once to view the current cool above and heat below temperature they will each flash once Press the or button to move the range up...

Страница 15: ...motion when trying to access branch pressure Press OVR to exit and try again Press the button The LCD will flash the stored control pressure for 3 seconds and return to the home screen The battery se...

Страница 16: ...e 16 of 20 Press the OVR button again to see the wireless signal strength from the WPT DB to the secondary path NOTE The Set Point Icon will identify the path currently in use by WPT DB as shown in Fi...

Страница 17: ...ter a few seconds LC Indicates that the buttons are locked This indication disappears automatically after a few seconds E0 Discovery error Not able to connect to nearest repeater or HUSB Retry discove...

Страница 18: ...T 10 If the pressure in the WPT is not the same as the main pressure try swapping the WPT with another unit For 1 pipe WPTs 1 Remove the WPT from the Universal Wall Bracket 2 Verify that the branch li...

Страница 19: ...DB does not have any field replaceable or repairable parts Contact the original distributor of the unit for repair or warranty service NOTE Care should be taken to keep the unit dust free during insta...

Страница 20: ...kPa Airflow Usage 0 011 scfm 5 2 mL s Sensitivity Factory Adjusted to 2 0 2 5 PSI F Operating Frequency Band 2 4 GHz ISM Band Battery Life More than 2 years with four setpoint changes per day Operatin...

Отзывы: