MAN0125 Rev 19
© Cylon Controls
11
Overvi
ew
LEFT EDGE
Note
:
When the Nexus 2 is shipped from the factory, both power
connectors are covered by a warning label. Make sure this
label is completely removed before using the Nexus 2.
1
Power module expansion port
Unused
2
24 V AC/DC power Phoenix
connector
Connect a 24 V AC/DC power connector to
provide power to your system.
3
19.5 V DC power adapter port
Connect a 19.5 V DC power adapter connector to
provide power to your system.
Note:
Nexus 2 requires a dedicated SELV 24 V 60VA AC / DC supply
(Class II supply) or a dedicated Dell SELV 19.5 V 65 W PSU.
Note
:
The recommended supply for warranty purposes is the
included Dell PSU.
When using a higher VA transformer, care must be taken to
ensure that the voltage stays within specification (see
Detailed
Engineering Specifications - Power
on page 22).
Warning
:
Earthing or Grounding of any of the terminals connected to
the SELV power supply will cause serious damage to the power
supply rectifier and will invalidate the product Warranty.
Never
Earth or Ground any of the terminals connected to this
power supply.
Never
use this power supply to power CB, NB, or SBC control
devices,
or any other
equipment, because it is possible that
the other equipment may be connected to Earth or Ground.
Note
: If the
Nexus 2
is acting as a Site’s central server, hosting the
primary UI and historical data, it is recommended that its
power supply is connected to an Uninterruptible Power Supply
(UPS).
RIGHT EDGE
1
IO expansion port
Unused
Содержание Aspect-Nexus 2
Страница 1: ...SMART ENERGY CONTROL NEXUS SERIES HARDWARE INSTALLATION GUIDE...
Страница 6: ...6 Cylon Controls MAN0125 Rev 19 NEXUS Series This page is intentionally blank...
Страница 7: ...SECTION 1 OVERVIEW...
Страница 12: ...12 Cylon Controls MAN0125 Rev 19 NEXUS Series This page is intentionally blank...
Страница 13: ...SECTION 2 INSTALLATION AND CONFIGURATION...
Страница 18: ...18 Cylon Controls MAN0125 Rev 19 NEXUS Series This page is intentionally blank...
Страница 19: ...SECTION 3 DETAILED ENGINEERING SPECIFICATIONS...
Страница 24: ...24 Cylon Controls MAN0125 Rev 19 NEXUS Series This page is intentionally blank...
Страница 25: ...SECTION 4 SOFTWARE CONFIGURATION...
Страница 45: ...MAN0125 Rev 19 Cylon Controls 45 Software Configuration This page is intentionally blank...