Appendices
83
Circuit Breaker Trip Time
Depending on the model, the Cyclades PM IPDU uses either one 10 amp, one 20 amp, two 15 amp,
or two 16 amp circuit breakers. The following table shows the circuit breaker trip time for all PM
IPDU models.
Table C.1: Circuit Breaker Trip Time
Current Load
Trip Time
200%
5-30 seconds
300%
1.8-10 seconds
400%
0.9-5 seconds
500%
0.5-3.3 seconds
600%
0.38-2.3 seconds
800%
0.2-1.3 seconds
1000%
0.15-0.9 seconds