15
Web Interface
3-Phase Intelligent PDU User Guide
Visible Power Consumption
With comprehensive energy measurement data, users can gain more visibility to the total power
usage of a PDU, as well as estimate the energy cost and CO2 emissions. The energy-trend report
also helps users analyze their power utilization and to review the history of power conditions. See
Log Tab > Status Records,
Log Tab > Graphing, Log Tab > Energy Records,
and
Log Tab >
Maintenance.
Log Tab > Status Records
Item
Definition
HOST/GUEST#
Select the role of PDU (HOST or GUEST#) if PDUs are daisy chained.
Up to 3 GUEST PDUs can connect to 1 HOST PDU.
Device Max (W)
The maximum load current of the connected device(s) or bank during
a specific time interval, measured in Watts. This interval can be set in
Device (W)
Load current of the connected device(s) or bank, measured in Watts.
Phase Max (A)
The maximum load current of the phase during a specific time interval,
measured in Amps. This interval can be set in
Phase (A)
Load current of the phase, measured in Amps.
Phase (V)
Voltage of the phase.
Temp. (°C)
Temperature reading when the ENVIROSENSOR is connected to the
PDU.
Содержание PDU33 Series
Страница 33: ...31 Web Interface 3 Phase Intelligent PDU User Guide Configure Trap Receiver Page Add New Trap Receiver Page ...
Страница 40: ...38 Web Interface 3 Phase Intelligent PDU User Guide Configure SMS Receiver Page Add New SMS Receiver Page ...
Страница 59: ...57 Web Interface 3 Phase Intelligent PDU User Guide Administrator Page Viewer Page ...