Allow to bypass even if utility power is out of range.
Options: Enabled / Disabled
Default: Disabled
Battery Backup supplies power at the specified voltage.
Options: 110 / 120 / 127
Default: 120
Output Frequency Determination
- Following utility frequency when it is within the specified tolerance. (default)
[When checked, the value can be modified from the drop-down box.]
Options: 1~10%
Default: 5%
- Fixed on the specified frequency.
[When checked, the value can be modified from the drop-down box.]
Options: 50/60 Hz
Default: 60 Hz
Outlet #1 / Outlet #2
Turn off if battery capacity is below the specified percentage.
Options: Enabled / Disabled
Default: Disabled
Percentage: 0~100%
Turn off when utility power has failed for the specified time.
Options: Enabled / Disabled
Default: Disabled
Time: 0~120 minutes
Turn on when utility power has been restored for the specified time.
Options: Enabled / Disabled
Default: Disabled
Time: 0~120 minutes
Operation 17