![CyberPower Paragon OL1000RMXL2U Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/cyberpower/paragon-ol1000rmxl2u/paragon-ol1000rmxl2u_user-manual_2702795012.webp)
1.3 Control panel
13 14 15 16 17 18 19 20 21 22
23 24
NO Description
13 ON / OFF.
14 BATT: Operation on battery power.
15 INV: Operation in ON-LINE mode (backup power available).
16 BYPASS: Operation on bypass (no backup power available).
17 OUTLET 2: Status of programmable outlet 2.
18 OUTLET 1: Status of programmable outlet 1.
: LED on indicates the outlet is supplied with power.
: LED flashing indicates the outlet status change in progress.
19 BZ STOP (TEST):
➣
Lamp test or buzzer OFF.
➣
Forced transfer to bypass and back by pressing the button
three times within five seconds.
20 LOAD:
Hold down to display percentage of load by LEDs
21
to
24
.
Press 19 & 20 simultaneously at least three seconds to reset the “End of
battery life” alarm.
21 WIRING FAULT / Load 20% Alarms are indicated by LED flashing
22 BATT ALARM* / Load 50%
23 ALARM / Load 80%
24 OVER LOAD / Load 100%
( ); percentage of load and battery
remaining are indicated by LED
illuminated ( ).
* Flashing LED + buzzer: battery fault (battery must be replaced).
Flashing LED + long buzzer (once per hour): theoretical end of battery life
(replacement recommended).
Device Overview 5