11
4.4. Electrical Installation
4.4.1. Notes for installation
z
The UPS must be installed in a location with good ventilation, far away from
water, inflammable gas and corrosive agents.
z
Ensure the air vents on the front and rear of the UPS are not blocked. Allow at
least 0.5m of space on each side.
z
Condensation to water drops may occur if the UPS is unpacked in a very low
temperature environment. In this case it is necessary to wait until the UPS is
fully dried inside out before proceeding installation and use. Otherwise there are
hazards of electric shock.
z
Once the installation is completed, the side mounting brackets (used in shipping)
shall be fixed back to ensure the stability of the UPS enclosure. If impossible,
additional stability can be added by anchoring the mounting brackets to the floor
with M8 bolts. See Fig.4-1.
Fig.4-1 Additional stability
4.4.2. Power Wires Installation
Installation and wiring must be performed in accordance with the local electric
code and the following instructions by professional personnel.
For safety, please cut off the mains power switch before installation
1) Open the terminal block cover located on the rear panel of the UPS. Please refer
to the appearance diagram.
2) It is recommended to select the UL1015 6AWG(25mm²) wire or other insulated
wire which complies with AWG Standard for the UPS input and output wirings.