![CyberPower OLS3S15KE Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/cyberpower/ols3s15ke/ols3s15ke_user-manual_2702755010.webp)
7
Electrical Performance
Input
Model
Phase
Frequency
Range
Power Factor
OLS3S15KE(XL)
/OLS3S20KE(XL)
Three-phase
(45~55)/(54~66)Hz
≥
0.99 @ full load
Output
Voltage Regulation
f
1%
Load Type
0.9 lag
Frequency
Synchronized 50/60Hz
f
10% @Line mode
f
0.1% of normal frequency @Battery mode
THDV
THD<2% Full load (Linear Load)
THD<5% for reference non-linear load
Overload*
Line model:
5 minutes 100%~110%;
1 minute 110%~130%;
10 seconds 130~150%;
2 seconds
≥
150%.
Battery model:
1 minutes 100%~110%;
10 seconds 110%~130%;
2 seconds
≥
130%.
*The overload capacity would be derated automatically while the circumstance
temperature is larger than 35 degree.