SAFETY INSTRUCTIONS CONT.

 PERSONAL SAFETY CONT.

 RISK OF ELECTRIC SHOCK

To prevent the risk of fire or electric shock, only use the supplied hardware to 
attach the mounting brackets.

Remove watches, rings or other metal objects. Use tools with insulated handles.

 Use tools with insulated handles.

The step-down transformer must be connected to a grounded AC power source 
with fuse or circuit breaker protection. DO NOT plug the step-down transformer 
into an outlet that is not grounded. If you need to power-drain this equipment, 
turn off and unplug the unit.

(No User Serviceable Parts): Risk of electric shock, do not remove cover. No user 
serviceable parts inside. Refer servicing to qualified service personnel.

To prevent the risk of fire or electric shock, install in a temperature and humidity 
controlled indoor area, free of conductive contaminants. (Please see specifications 
for acceptable temperature and humidity range).

To avoid electric shock, turn off and unplug the unit before installing the input/
output power cord with a ground wire. Connect the ground wire prior to 
connecting the line wires!

Connect the Protection Earth (PE) safety conductor before any other cables are 
connected.

Internal circuit configuration or equivalent. Installation instructions shall carry 
sufficient information, including the basic internal circuit configuration of the UPS, 
to emphasize its compatibility with power distribution systems.

Signaling circuit connection - Information shall be provided in the installation 
instructions as to the purpose and connection of any signaling circuits.

For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the 
equipment and shall be easily accessible.

For Permanently Connected Equipment:

A) A readily accessible disconnect device shall be incorporated in the building 

installation wiring for AC Input.

B) 

CAUTION -

 To reduce the risk of fire, connect only to a circuit provided with 

30 A maximum branch circuit overcurrent protection in accordance with the 
National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code,  
Part I, C22.1.

C) Wiring Information: Use No. 10 AWG, minimum 90°C copper wire and  18 lb-in 

Torque force when connecting to AC wiring terminal.

Содержание OL5KSTF

Страница 1: ...TRANSFORMER OL5KSTF INSTALLATION AND OPERATION MANUAL 2021 Cyber Power Systems Inc All rights reserved K01 0000913 01 SAVE THESE INSTRUCTIONS Please read this manual and follow the instructions for i...

Страница 2: ...ation contact your local recycling or hazardous waste facility Information advice help See applicable user manual SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instruction...

Страница 3: ...re conducting any maintenance repairs or shipment Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants Do not install this step down...

Страница 4: ...shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires Connect the Protection Earth PE safety c...

Страница 5: ...ected equipment and only qualified maintenance personnel may carry out installations Wiring must be done by qualified personnel DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT Under no circumstances...

Страница 6: ...Rackmount Installation For 4 Post Rack 4 ELECTRICAL INSTALLATION 6 Hardwiring the Input Terminals 6 Connecting a Step Down Transformer to a UPS Power Module 8 TECHNICAL SPECIFICATIONS 9 PRODUCT REGIST...

Страница 7: ...all handling operations including unpacking lifting and installation in a rack system Do not use the lifting straps to carry the unit around they are provided to manually unpack the unit only USE LIF...

Страница 8: ...L5KSTF step down and isolation transformer 1 2 Left right hanging brackets 1 3 Left right rackmount rail 1 4 Input terminal block bottom cover 1 5 2U Rack mount ears Tower stands 2 ITEM CONTENT QTY 6...

Страница 9: ...egment 1 Provides output overload and fault protection 5 Output Circuit Breaker 15A Max segment 2 Provides output overload and fault protection 6 4 x NEMA 5 20R Outlets 120Vac segment 2 Output recepta...

Страница 10: ...n to 36 in 52 cm to 91 5 cm deep Select the proper holes in the rack for positioning the step down transformer in the rack The step down transformer takes up 2 rack units rack hole positions 1 through...

Страница 11: ...DWARE INSTALLATION CONT RACKMOUNT INSTALLATION FOR 4 POST RACK CONT RACKMOUNT EARS INSTALLATION CONT RACKMOUNT INSTALLATION FOR 2 POST RACK This unit can be installed in a 2 post rack with an optional...

Страница 12: ...30P POWER CORD CONNECTION Connect the NEMA L6 30P input power cord directly to an outlet on the UPS Refer to the CONNECTING A STEP DOWN TRANSFORMER TO A UPS POWER MODULE section in this user manual fo...

Страница 13: ...STALLATION CONT 5 4 3 THE INPUT CONFIGURATION CONT 3 Secure the bottom section of the input terminal cover using the included screws 4 Insert the input cable through the appropriate cable gland not in...

Страница 14: ...N CONT CONNECTING A STEP DOWN TRANSFORMER TO A UPS POWER MODULE The following illustrations provide the recommended connections between a step down transformer and a CyberPower Smart App Online UPS Sy...

Страница 15: ...Vac Input connection type Power cord L6 30P Terminal Input Frequency 50 60 Hz Input Current Rating Power Cord 24A Terminal 27A OUTPUT Nominal Output Voltage 120 Vac UPS Outlets 12 NEMA 5 20R PHYSICAL...

Страница 16: ...cyberpowersystems com registration to establish that you are the Initial Customer of the Product and therefore entitled coverage under the Limited Warranty and the Connected Equipment Guarantee Regis...

Страница 17: ...ir respective owners 11 Cyber Power Systems Inc www CyberPowerSystems com For USA and Canada 4241 12th Ave East Suite 400 Shakopee MN 55379 Toll free 877 297 6937 For all other regions Please visit ou...

Отзывы: