4

HARDWARE INSTALLATION

RACKMOUNT INSTALLATION FOR 4-POST RACK

To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting 
brackets.

Step 1: Rackmount ear & hanging bracket installation 

Attach two rack mount ears to the step-down transformer using eight black M5X7L flat head screws. 
Install hanging brackets using six silver M5X6L pan head screws

Step 2: Rackmount rail Installation 

The rails adjust to mount in 19 in (48 cm) racks from 20.5 in to 36 in (52 cm to 91.5 cm) deep. Select 
the proper holes in the rack for positioning the step-down transformer in the rack. The step-down 
transformer takes up 2 rack units: rack hole positions 1 through 6.

Position the guide screws on the back of the rackmount rails into the rear rack square holes to 
temporarily support the rails in place.

Step 3: Adjust rackmount rails to fit your rack 

Adjust the rail depth to match your rack depth. Attach the rackmount rail to your rack with two black 
M5X6L pan head screws and two plastic washers at the front of the rack (square holes 1 and 4 as shown 
below). Secure the rail to the rear of the rack with two black M5X12L screws and two plastic washers.

Caution: Important Instructions

1

2

position 1

position 4

3

1

2

3

4

5

6

1U

2U

3U

Rackmount ear

Rackmount rail

Содержание OL5KSTF

Страница 1: ...TRANSFORMER OL5KSTF INSTALLATION AND OPERATION MANUAL 2021 Cyber Power Systems Inc All rights reserved K01 0000913 01 SAVE THESE INSTRUCTIONS Please read this manual and follow the instructions for i...

Страница 2: ...ation contact your local recycling or hazardous waste facility Information advice help See applicable user manual SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instruction...

Страница 3: ...re conducting any maintenance repairs or shipment Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants Do not install this step down...

Страница 4: ...shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires Connect the Protection Earth PE safety c...

Страница 5: ...ected equipment and only qualified maintenance personnel may carry out installations Wiring must be done by qualified personnel DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT Under no circumstances...

Страница 6: ...Rackmount Installation For 4 Post Rack 4 ELECTRICAL INSTALLATION 6 Hardwiring the Input Terminals 6 Connecting a Step Down Transformer to a UPS Power Module 8 TECHNICAL SPECIFICATIONS 9 PRODUCT REGIST...

Страница 7: ...all handling operations including unpacking lifting and installation in a rack system Do not use the lifting straps to carry the unit around they are provided to manually unpack the unit only USE LIF...

Страница 8: ...L5KSTF step down and isolation transformer 1 2 Left right hanging brackets 1 3 Left right rackmount rail 1 4 Input terminal block bottom cover 1 5 2U Rack mount ears Tower stands 2 ITEM CONTENT QTY 6...

Страница 9: ...egment 1 Provides output overload and fault protection 5 Output Circuit Breaker 15A Max segment 2 Provides output overload and fault protection 6 4 x NEMA 5 20R Outlets 120Vac segment 2 Output recepta...

Страница 10: ...n to 36 in 52 cm to 91 5 cm deep Select the proper holes in the rack for positioning the step down transformer in the rack The step down transformer takes up 2 rack units rack hole positions 1 through...

Страница 11: ...DWARE INSTALLATION CONT RACKMOUNT INSTALLATION FOR 4 POST RACK CONT RACKMOUNT EARS INSTALLATION CONT RACKMOUNT INSTALLATION FOR 2 POST RACK This unit can be installed in a 2 post rack with an optional...

Страница 12: ...30P POWER CORD CONNECTION Connect the NEMA L6 30P input power cord directly to an outlet on the UPS Refer to the CONNECTING A STEP DOWN TRANSFORMER TO A UPS POWER MODULE section in this user manual fo...

Страница 13: ...STALLATION CONT 5 4 3 THE INPUT CONFIGURATION CONT 3 Secure the bottom section of the input terminal cover using the included screws 4 Insert the input cable through the appropriate cable gland not in...

Страница 14: ...N CONT CONNECTING A STEP DOWN TRANSFORMER TO A UPS POWER MODULE The following illustrations provide the recommended connections between a step down transformer and a CyberPower Smart App Online UPS Sy...

Страница 15: ...Vac Input connection type Power cord L6 30P Terminal Input Frequency 50 60 Hz Input Current Rating Power Cord 24A Terminal 27A OUTPUT Nominal Output Voltage 120 Vac UPS Outlets 12 NEMA 5 20R PHYSICAL...

Страница 16: ...cyberpowersystems com registration to establish that you are the Initial Customer of the Product and therefore entitled coverage under the Limited Warranty and the Connected Equipment Guarantee Regis...

Страница 17: ...ir respective owners 11 Cyber Power Systems Inc www CyberPowerSystems com For USA and Canada 4241 12th Ave East Suite 400 Shakopee MN 55379 Toll free 877 297 6937 For all other regions Please visit ou...

Отзывы: