Wire Gauge
     (AWG)

Wire Type

Tightening Torque
            (lb-in)

Minimum temperature 

rating of conductors

Copper conductors

7

75°C

10-18 AWG 

Copper Conductors

Table 3: AC Line Cord 

Table 4: Conduit Wires 

4.7.2 Outdoor Power Cord Selection

 

      1. If an outdoor AC Line cord is selected to connect the unit to AC wall outlet, be sure that the    
          selection criterion in the following table are fully complied. 

2. The connection of the power cord should also be in accordance with Article 110.14 of 

ANSI/NEPA 70.

3. Using pin terminals (as shown in the Figure 14) for the power cord at the end connected to 

terminal strip is recommended. 

"Warning

 

- Risk of Electric Shock.

 Connect plug of outdoor power cord only to a covered Class A 

GFCI receptacle that has an enclosure that is weatherproof with the attachment plug cap inserted or 
removed.

"

4. If conduit is used, be sure to choose wires in accordance with the following criterion.

Cord Rating

Wire (AWG)

Outdoor Use

Attachment Plug

Flexible Cord Type

Three conductors, 

current rating 10A, 

VW-1, 105

125/250V

Check 

specifications of 

liquid tight cable 

gland to determine 

the outside 

diameter of the 

wire. 

(O.D. > 6.8mm; 

18AWG min. for

each inner wire) 

Use cord type with 

the suffix "W", "W-A" 

or the words "Water 

resistant" or 

"Outdoor" marked on 

the flexible cord

15A, 125V (NEMA 

5-15P) or 15A, 250V 

(NEMA 6-15P)

SP-2, SPE-2, SPT-2, 
NISP-2, NISPE-2, 
NISPT-2, SP-3, SPE-3, 
SPT-3

SV, SVE, SVO, SVOO, 
SVT, SVTO, SVTOO

SJ, SJE, SJO, SJOO, 
SJT, SJTO, SJTOO

S, SE, SO, SOO, ST, 
STO, STOO

"Warning - Risk of Electric Shock.

  Install wires going through conduit only on a circuit protected 

by a Class A GFCI.

"

"Warning:

 Power supply cord must not be attached to the building surface, nor run through walls, 

ceilings, floors and similar openings in the building structure.

"

"Warning:

 The socket outlet shall be installed near the equipment and shall be easily accessible.

"

 

"Warning: 

To reduce the risk of fire, connect the unit only to a circuit provided with Listed 20 

Amperes circuit breaker in accordance with the National Electrical Code, ANSI/NFPA.

"

Note:

 Wiring, liquid tight fittings, conduit and cable glands shall be selected in accordance with 

Article 300 of ANSI/NFPA 70.

Note:

 Before installing the unit, confirm that there is listed IEC 61643-12 or UL1449 low surge 

protective device with surge protection level less than 2.5KV being connected between the 
unit and the power source.   

Note:

 Surge Arrestors or Transient Voltage Surge Suppressor external to the equipment to reduce 

overvoltages or to bypass surge current shall be installed per Article 280 or 285 of ANSI/NFPA 70.

Note:

 Be certain to keep coolant or oil away from the unit. 

Содержание CS150U48V3

Страница 1: ...CS150U48V3 Installation Operation Manual K01 1504801 00...

Страница 2: ...cting to Power Source 11 4 7 1 Installing the Power Cord 11 4 7 2 Outdoor Power Cord Selection 12 4 8 ONT Alarm Connections 13 5 Operation 13 5 1 Start Up 13 5 2 Controls and Operational LEDs 14 5 3 A...

Страница 3: ...of 17 TABLE OF TABLES Table 1 Battery Heater Specifications 11 Table 2 Block Diagram Descriptions 11 Table 3 AC Line Cord 12 Table 4 Conduit Wires 12 Table 5 Controls and LED Indicators 14 Table 6 Ala...

Страница 4: ...rify the supplied AC line voltage prior to installation using an AC voltage meter Verify branch circuit breaker or fuse on the service feed is correct for the equipment being installed Batteries may p...

Страница 5: ...maintaining servicing or replacing batteries A battery showing signs of cracking leaking or swelling should be replaced immediately with a battery of identical type and rating The battery can energize...

Страница 6: ...chnician for help CAUTION Any changes or modifications not expressly approved by Cyber Power could void the authority granted by the FCC to operate this equipment DO NOT USE FOR MEDICAL OR LIFE SUPPOR...

Страница 7: ...r owners Page 6 of 17 Figure 1 Dimensions Front View Figure 2 Dimensions Side View 3 DIMENSIONS 17 14 inch 435 4 mm 7 09 inch 180 1 mm 5 79 inch 147 1 mm 15 75 inch 400 1 mm 16 inch 406 4 mm 15 30 inc...

Страница 8: ...3 LED Indicators AC DC MODE BATTERY MISSING 1 BATTERY MISSING 2 DC OUTPUT 4 DC Output and Telemetry receptacles 5 Battery wiring harness plug in 6 Door clasp 7 Door padlock hasp 8 Door ground and bond...

Страница 9: ...L Pole Mount Kit Pole Mount Bracket x 3 M8 Flange Nut x 6 M8 x 25L Hex Head Screws clamp center bracket to side brackets x 4 M8 Lock Washers x 4 M8 Flat Washers x 4 OPTIONAL Battery Heater Battery Hea...

Страница 10: ...parately 3 Using the nuts included in the kit attach the left and right pole mount brackets to the threaded posts on the back side of the UPS enclosures as shown 4 Thread the 4 M8 x 25L hex head screw...

Страница 11: ...tion is complete Wire Harness Vo Wire Strain Relief Wire Harness Vo Battery tray mounting hole Battery Harness Wire Plug in Battery Tray Mounting Screw 4 5 Installing the Battery Trays Battery Replace...

Страница 12: ...nal L N G correctly and securely Figure 14 AC Wiring i Figure 15 AC Wiring ii Remove terminal cover Remove knock out and add strain relief or conduit here 4 6 Battery Heater BTH 150 8X Optional Figure...

Страница 13: ...inner wire Use cord type with the suffix W W A or the words Water resistant or Outdoor marked on the flexible cord 15A 125V NEMA 5 15P or 15A 250V NEMA 6 15P SP 2 SPE 2 SPT 2 NISP 2 NISPE 2 NISPT 2 SP...

Страница 14: ...Be certain to utilize environmentally sealed strain reliefs cordgrips or conduit at the cable exit point Note Output wires should be installed in accordance with Article 800 of ANSI NFPA 70 5 OPERATI...

Страница 15: ...reset an output if it has been shut down due to an over current or short condition and the fault has been removed The cold start allows a start up of the system after a power outage and the batteries...

Страница 16: ...nal in low state ON Batt signal in open state Low Batt signal in open state Missing Batt signal in open state Replace Batt signal in open state Description Condition normal AC input failure Battery is...

Страница 17: ...factory orderable option Replaceable Yes Surge Protection and Filtering Lightning Surge Protection GR 1089 CORE Sect 4 Warning Diagnostics AC AC Battery Mode Indicator Output Output On Off Indicator...

Страница 18: ...010 CyberPower Systems USA Inc All Trademarks are property of their owners Page 17 of 17 APPENDIX I Wall Mount Chart Recommended Screw Dimensions M8 x 25L or 3 8 x 1 L 7 09 inch 180 mm 16 inch 406 4 m...

Отзывы: