Chapter 4 Operations
25
RT33020/25/30KE User Manual
Fig.4-3 Interface of inverter starting
7. After about 30S, when the inverter is running normally, the UPS switches from the bypass
to the inverter, the bypass indicator bar is off, and the load indicator bar flashes. As shown
in Fig.4-4.
Fig.4-4 Interface of inverter mode
8. Close the external battery switch, the battery indicator flashes, and then the UPS charges
the battery. The UPS works in normal mode. As shown in Fig.4-5
Fig.4-5 Interface of normal mode
Note
When the system starts, the stored setting will be loaded.
Users can browse all incidents during the process of the starting up by checking the menu
Log.
4.1.2 Start from Battery
The start for battery model is referring to battery cold start. The steps for the start-up are as