23
Operation
Step 3. Notification
Notifying the computers of potential outlet shutdown can be
accomplished using the following methods:
•
Outlets Control Menu: Performing the task of turning off or
rebooting outlets.
•
Scheduling Menu: Setting the application to perform the task
of turning off or rebooting outlets. The notification will occur
prior to the scheduled date/time.
•
Outlet Overload: In the event of PDU overload, notification will
be sent prior to the PDU shutting down.
Firmware Upgrade
By upgrading the Firmware, you can obtain new features and
updates/improvements to existing functionality. There are three
methods for upgrading the PDU firmware. Please follow the
instructions below for the method that is appropriate for your
application.
Note:
Please do not turn the PDU off when processing the
Firmware upgrade.
Option 1: Single Device Upgrade
There are two files to update in order to upgrade the firmware
version:
* cpsmpdumafw_XXX.bin
* cpsmpdumadata_XXX.bin
Note that the XXX is not part of the file name but is where the
version number in the filename is given.
Use the following steps to upgrade the firmware.
1. Download the latest firmware from www.cyberpower.com
2. Extract the file to “C:\”
3. Open a command prompt window and navigate to “C:\”.
4. Login to the PDU with FTP command, type
- C:\>ftp
- ftp> open 192.168.22.126 21 (for example: 192.168.22.126
is the current IP of the PDU and 21 is the default ftp
port for the PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
5. Upload the cpsmpdumafw_XXX.bin, type
- ftp > bin
- ftp > put cpsmpdumafw_XXX.bin
6. Upgrade complete, type
- ftp > quit
7. The system will reboot after you type "quit". This reboot will take
approx. 30 seconds.
8. Login to the FTP again
- C:\>ftp
- ftp> open 192.168.22.126 21 (for example: 192.168.22.126
is the current IP of the PDU and 21 is the default ftp
port for the PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
9. Upload cpsmpdumadata_XXX.bin
- ftp > bin
- ftp > put cpsmpdumadata_XXX.bin
10. Upgrade complete , type
- ftp > quit
11. The system will reboot after you type “quit”.
You can check to see if the firmware upgrade is successful by
checking the “Firmware version” on the [System->About] webpage.