LCD SETUP FUNCTIONS

 

 

 

7

 

 

MULTI-FUNCTION LCD MAIN MENU 

Press “

Enter

” button to activate “

MAIN MENU

”. 

MAIN MENU submenu 

Function Description 

Information 

Displays the UPS information. 

Configure 

Displays the UPS settings that can be configured by the user. 

Event Log 

Displays  the  3  most  recent  events,  by  event  count,  time 
(day/hour/minute), and event description. 

 

LCD INFORMATION READOUT

 

There are 19 types of UPS information available for display. 

1. 

Press the “

ENTER

” button to activate the “

MAIN MENU

”. 

2. 

Press the 

” and “

” buttons to scroll to the “

Information

” option. 

3. 

Press the “

ENTER

” button to select the “

Information

” submenu. 

4. 

Press 

the “

” and “

” buttons to scroll through the “

Information

” submenu in the following table. 

5. 

Press 

the “

ESC

” button to return to UPS Status. 

Information Submenu 

Description 

O/P Volt 

= XXX.XV 

Displays the Output Voltage 

O/P Freq  = XX.XHz 

Displays the Output Frequency 

I/P Volt 

= XXX.XV 

Displays the Input Voltage 

I/P Freq 

= XX.XHz 

Displays the Input Frequency 

O/P Load  =    XXX% 

Displays the Output Load as a Percentage of Maximum load 

O/P Amp     =      X.XA 

Displays the Output Current 

O/P Watt  =XXXXXW 

Displays the Output Wattage 

O/P VA   

=XXXXXVA 

Displays the Output VA 

BAT Volt  = XXX.XV 

Displays the Battery Voltage 

BAT Cap    =    XXX% 

Displays the Estimated Percentage of Battery Capacity 

BAT Runtime =XXXM 

Displays the Estimated Battery Runtime in Minutes 

EBM Number =      X 

Displays the External Battery Module Number 

TEMP  =XX°C / XXX°F 

Displays  the  Approximate  inside  Temperature  in  both 

(Celsius)  and 

(Fahrenheit) for the UPS 

SBM 

= XXXXX XH(M) 

Displays the stage of Smart Battery Management with Operation Time

 

Rating      = XXK VA 

Displays the UPS Rating 

MCU Ver  =      XXXX 

Displays the MCU Firmware Version 

Model Name 

Displays the UPS Model Name 

Date & Time 
- - - - / - - / - -    - -:- - 

Displays the present Date & Time 

Next BAT Change   
                    XXX / XXXX 

Displays the next Battery Change Date & Time 

Содержание OL1000EXL

Страница 1: ...User s Manual OL1000EXL OL1500EXL OL2000EXL OL3000EXL CyberPower Systems Inc www cpsww com K01 0000358 00 ...

Страница 2: ... carry out installations CAUTION Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage t...

Страница 3: ...lled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity range CAUTION Never install a UPS or associated wiring or equipment during a lightning storm CAUTION Do not work alone under hazardous conditions CAUTION In case of the risk of electric shock do not remove the top cov...

Страница 4: ...ephone fax machine or network device 5 Press the ON OFF switch to turn the UPS on The Power On indicator light will display when activated If an overload is detected an audible alarm will sound and the UPS will continuously emit two beeps per second For resetting the unit unplug some equipment from the outlets Make sure your equipment carries a load current within the unit s safe range refer to th...

Страница 5: ...he power supply to equipment connected to NONCRITICAL outlets after a designated period of time 7 Serial Port Serial port provides communication between the UPS and the computer The UPS can control the computer s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters 8 USB port This is a connectivity port which all...

Страница 6: ...Copyright 2014 CyberPower Systems Inc BASIC OPERATION 5 OL1000EXL OL1500EXL OL2000EXL OL3000EXL ...

Страница 7: ...Y Red Battery will soon need to be replaced due to insufficient runtime LCD SCREEN UPS STATUS LCD Screen UPS Status Description Line Mode UPS is operating in Line Mode Battery Mode UPS is operating in Battery Mode Bypass Mode UPS is operating in Bypass Mode Manual Bypass UPS is operating in Manual Bypass ECO Mode UPS is operating in ECO Economy Mode BUTTON OPERATION Button Operation Description ON...

Страница 8: ... XXX XV Displays the Output Voltage O P Freq XX XHz Displays the Output Frequency I P Volt XXX XV Displays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load as a Percentage of Maximum load O P Amp X XA Displays the Output Current O P Watt XXXXXW Displays the Output Wattage O P VA XXXXXVA Displays the Output VA BAT Volt XXX XV Displays the Battery ...

Страница 9: ... to select the Language submenu 6 Press the and buttons to scroll to the language that you want to select You may be prompted to save the selection if so press the ENTER button to save the setting 7 Press the ESC button to cancel or return to previous LCD menu LCD SETTINGS CONFIGURATION There are 22 UPS settings that can be configured by the user 1 Press the ENTER button to activate the MAIN MENU ...

Страница 10: ... Français French Deutsch German English Generator Mode Disable Enable Disable Communication Disable Enable Enable Dry Relay Set I P Power Fail Battery Low Summary Alarm UPS On Bypass UPS Fail I P Power Fail Converter Mode Converter Off O P Freq 50Hz O P Freq 60Hz Converter OFF Screen Saver Disable 1 Minutes 5 Minutes 5 minutes Clear Event Log Activate None Button OFF LOCK Disable Enable Disable Ch...

Страница 11: ...st portion of the LCD screen and the unit will perform a manual battery test GRAPHICAL LOAD BATTERY CAPACITY DISPLAY 1 Press the ESC button to return to UPS Status 2 Press the and buttons to scroll to the LOAD and BAT Capacity 3 Press the and buttons to scroll to the Charging or Discharging Capacity Discharging Capacity The LCD screen displays the remaining battery capacity with a graphical icon w...

Страница 12: ...s and may be toxic CAUTION To avoid electric shock turn off and unplug the UPS from the wall receptacle before servicing the battery CAUTION Only use tools with insulated handles Do not lay tools or metal parts on top of the UPS or battery terminals Replacement Batteries Please refer to the front side of the UPS for the model number of the correct replacement batteries For battery procurement log ...

Страница 13: ...e Mode 105 125 Load for 1 min 126 150 Load for 10 sec Battery Mode 105 130 Load for 10 sec 131 150 Load for 2 sec Short Circuit Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 3 12V 9AH 6 12V 9AH Recharge Time Typically 5 hours Sealed Maintenance Free Yes Hot Swappable Yes Status Indicators LCD Screen Multi Function LCD Readout that Support...

Страница 14: ...he EPO connection Wiring Fault Line and neutral wires are reversed Exchange line and neutral wires Missing ground wire Connect ground wire No ground wire Disable Wiring Fault alarm on LCD panel Line Abnormal Wrong utility power backed up during UPS auto restart Check whether voltage or frequency of utility power is out of range Output Short Output short circuit Your attached equipment may have pro...

Отзывы: