INSTALLING YOUR UPS SYSTEM

 

 

 

3

 

 

 

SYSTEM BLOCK DIAGRAM

 

Output

Input

Filter

PFC

AC/DC

BUS

Inverter

DC/AC

INV

RY

Charger

AC/DC

Bypass

Battery

Output

Filter

Input

Line Mode

Battery Mode

Bypass Mode

Control

&

Monitoring

LCD Module

USB & DB9

SNMP Slot

DC/DC

 

 
 

 

HARDWARE INSTALLATION GUIDE

 

1.

 

Battery  charge  loss  may  occur  during  shipping  and  storage.  Before 

using  the  UPS,  it’s  strongly  recommended  to  charge  batteries  for  four 
hours to ensure the batteries’ maximum charge capacity. To recharge the 
batteries, simply plug the UPS into an AC outlet.   

2.

 

When  using  the  included  software,  connect  either  the  serial  or  the 

USB cable between the computer and the corresponding port on the UPS. 
Note: If the USB port is used, the serial port will be disabled. They cannot 
be  used  simultaneously.  After  connecting  to  either  the  USB  port  or  the 
Serial  port  on  the  UPS,  a  computer  with  the  PowerPanel

®

  Business 

Edition  Agent  software  installed  can  control  the  operating  schedule, 
battery test, outlets, as well as obtain UPS status information. However, 
other computers with PowerPanel

®

 Business Edition Client software can 

only obtain UPS status information via LAN connection.   

3.

 

Connect  your  computer,  monitor,  and  any  externally-powered  data 

storage  device  (Hard  drive,  Tape  drive,  etc.)  into  the  outlets  only  when 
the UPS is off and unplugged. DO NOT plug a laser printer, copier, space 
heater, vacuum, paper shredder or other large electrical device into the 
UPS.  The  power  demands  of  these  devices  will  overload  and  possibly 
damage the unit.   

4.

 

To  protect  a  fax  machine,  telephone,  modem  line  or  network  cable, 

connect the telephone  or network cable from  the wall jack outlet to the 
jack marked “IN” on the UPS and connect a telephone cable or network 
cable from the jack marked “OUT” on the UPS to the modem, computer, 
telephone, fax machine, or network device. 

5.

 

Press the ON/OFF switch to turn the UPS on. The Power-On indicator 

light  will  display  when  activated.  If  an  overload  is  detected,  an  audible 
alarm  will  sound  and  the  UPS  will  continuously  emit  two  beeps  per 
second. For resetting the unit, unplug some equipment from the outlets. 
Make  sure  your  equipment  carries  a  load  current  within  the  unit’s  safe 
range, (refer to the technical specifications). 

6.

 

This UPS is equipped with an auto-charge feature. When the UPS is 

plugged  into  an  AC  outlet,  the  battery  will  automatically  charge,  even 
when the unit is switched off. 

7.

 

To maintain an optimal battery charge, leave the UPS plugged into an 

AC outlet at all times. 

8.

 

Before storing the UPS for an extended period of time, turn the unit 

OFF. Then cover it and store it with the batteries fully charged. Recharge 
the  batteries  every  three  months  to  ensure  good  battery  capacity  and 
long  battery  life.  Maintaining  a  good  battery  charge  will  help  prevent 
possible damage to the unit from battery leakage. 

9.

 The UPS has one USB port (default) and one Serial port that allows 

connection  and  communication  between  the  UPS  and  any  attached 
computer running the PowerPanel

®

 Business Edition Agent software. The 

UPS  can  control  the  computer’s  shutdown  during  a  power  outage 
through the connection while the computer can monitor the UPS and alter 
various  programmable  parameters. Note: Only  one  communication  port 
can  be  used  at  a  time.  The  port  not  in  use  will  automatically  become 
disabled or the serial port will be disabled if both ports are attached.

 

10.

 

EPO (Emergency Power Off) Port: 

EPO ports allow administrators the capability to connect the UPS unit to 
customer-supplied  EPO  switches.  These  installations  give  operators  a 
single access point to immediately power-off all equipment connected to 
the UPS during an emergency. 

11.

 

To avoid electric shock, turn the unit OFF and disconnect the  unit 

from  utility  power  before  hardwiring  the  UPS  (in/out  power  cord).  The 
in/out power cord MUST be grounded. 
 

 

Содержание OL1000EXL

Страница 1: ...User s Manual OL1000EXL OL1500EXL OL2000EXL OL3000EXL CyberPower Systems Inc www cpsww com K01 0000358 00 ...

Страница 2: ... carry out installations CAUTION Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage t...

Страница 3: ...lled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity range CAUTION Never install a UPS or associated wiring or equipment during a lightning storm CAUTION Do not work alone under hazardous conditions CAUTION In case of the risk of electric shock do not remove the top cov...

Страница 4: ...ephone fax machine or network device 5 Press the ON OFF switch to turn the UPS on The Power On indicator light will display when activated If an overload is detected an audible alarm will sound and the UPS will continuously emit two beeps per second For resetting the unit unplug some equipment from the outlets Make sure your equipment carries a load current within the unit s safe range refer to th...

Страница 5: ...he power supply to equipment connected to NONCRITICAL outlets after a designated period of time 7 Serial Port Serial port provides communication between the UPS and the computer The UPS can control the computer s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters 8 USB port This is a connectivity port which all...

Страница 6: ...Copyright 2014 CyberPower Systems Inc BASIC OPERATION 5 OL1000EXL OL1500EXL OL2000EXL OL3000EXL ...

Страница 7: ...Y Red Battery will soon need to be replaced due to insufficient runtime LCD SCREEN UPS STATUS LCD Screen UPS Status Description Line Mode UPS is operating in Line Mode Battery Mode UPS is operating in Battery Mode Bypass Mode UPS is operating in Bypass Mode Manual Bypass UPS is operating in Manual Bypass ECO Mode UPS is operating in ECO Economy Mode BUTTON OPERATION Button Operation Description ON...

Страница 8: ... XXX XV Displays the Output Voltage O P Freq XX XHz Displays the Output Frequency I P Volt XXX XV Displays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load as a Percentage of Maximum load O P Amp X XA Displays the Output Current O P Watt XXXXXW Displays the Output Wattage O P VA XXXXXVA Displays the Output VA BAT Volt XXX XV Displays the Battery ...

Страница 9: ... to select the Language submenu 6 Press the and buttons to scroll to the language that you want to select You may be prompted to save the selection if so press the ENTER button to save the setting 7 Press the ESC button to cancel or return to previous LCD menu LCD SETTINGS CONFIGURATION There are 22 UPS settings that can be configured by the user 1 Press the ENTER button to activate the MAIN MENU ...

Страница 10: ... Français French Deutsch German English Generator Mode Disable Enable Disable Communication Disable Enable Enable Dry Relay Set I P Power Fail Battery Low Summary Alarm UPS On Bypass UPS Fail I P Power Fail Converter Mode Converter Off O P Freq 50Hz O P Freq 60Hz Converter OFF Screen Saver Disable 1 Minutes 5 Minutes 5 minutes Clear Event Log Activate None Button OFF LOCK Disable Enable Disable Ch...

Страница 11: ...st portion of the LCD screen and the unit will perform a manual battery test GRAPHICAL LOAD BATTERY CAPACITY DISPLAY 1 Press the ESC button to return to UPS Status 2 Press the and buttons to scroll to the LOAD and BAT Capacity 3 Press the and buttons to scroll to the Charging or Discharging Capacity Discharging Capacity The LCD screen displays the remaining battery capacity with a graphical icon w...

Страница 12: ...s and may be toxic CAUTION To avoid electric shock turn off and unplug the UPS from the wall receptacle before servicing the battery CAUTION Only use tools with insulated handles Do not lay tools or metal parts on top of the UPS or battery terminals Replacement Batteries Please refer to the front side of the UPS for the model number of the correct replacement batteries For battery procurement log ...

Страница 13: ...e Mode 105 125 Load for 1 min 126 150 Load for 10 sec Battery Mode 105 130 Load for 10 sec 131 150 Load for 2 sec Short Circuit Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 3 12V 9AH 6 12V 9AH Recharge Time Typically 5 hours Sealed Maintenance Free Yes Hot Swappable Yes Status Indicators LCD Screen Multi Function LCD Readout that Support...

Страница 14: ...he EPO connection Wiring Fault Line and neutral wires are reversed Exchange line and neutral wires Missing ground wire Connect ground wire No ground wire Disable Wiring Fault alarm on LCD panel Line Abnormal Wrong utility power backed up during UPS auto restart Check whether voltage or frequency of utility power is out of range Output Short Output short circuit Your attached equipment may have pro...

Отзывы: