14
Function Setup Guide
Function
Options
Default
Description
Page 1 - Audible Alarm
On
Off
ESC
On
If Off is selected, the unit will
mute alarms and the Mute
icon will appear on the LCD
display.
Page 2
– Input Voltage Range
Hi (Wide):
(90-280Vac)
Lo (Narrow):
(170-280Vac)
ESC
Hi
For connected equipment
that are less sensitive to the
fluctuation of voltage range,
set the input voltage range
wider and the output voltage
will follow.
For connected equipment
that are sensitive to the
fluctuation of voltage range,
narrow the input voltage
range.
Note: The transfer time will
increase while the input voltage
gets lower. If the connected
equipment is sensitive to the
transfer time, power interruption
condition may occur.
Page 3 - Temperature
Detection
OFF
40~50
℃
ESC
OFF
If the temperature sensor is
connected to the
temperature detection port,
the sensor probe will detect
the ambient temperature and
display on LCD. Setup the
temperature here, when
ambient temperature
reaches the value, charging
rate will be regulated in order
to protect and extend battery
Содержание CPD1200EO12LCD