HARDWARE INSTALLATION

HARDWARE INSTALLATION

These Battery modules can be mounted in a rackmount or vertical tower orientation. This 

versatility is especially important to growing organizations with changing needs that value 

having the option to position a Battery module on a floor or in a rackmount system. Please 

follow the instructions below for the respective mounting methods.

CAUTION!

  To prevent the risk of fire or electric shock, only use the supplied hardware to 

attach the mounting brackets.

RACKMOUNT INSTALLATION

Step 1: Rackmount ears installation  

Attach the two rackmount ears to Battery module using the provided screws M4X8L*8pcs.

 

 

Step 2: Rackmount rails installation 

(1) The rails adjust to mount in 48-cm (19-inch) panel racks from 46.4 to 73.8cm (18.3 to 29 

inches) deep. Select the proper holes in the rack for positioning the Battery module in the 

rack. The rails take up position 1 through position 3.
(2) Attach the rackmount rail to your rack with two M5X12L screws, two plastic washers, and 

two M5 nuts at the front of the rack. (Located in position 1 & position 3; It can also be located 

in position 1 & position 2 or position 2 & position 3 alternatively). Do not tighten the screws. 

Adjust the rail length on the rail assembly of your rack. Secure the rail to the rear of the rack 

with two M5X12L screws, two plastic washers, and two M5 nuts. Tighten all screws at the 

front and rear of the rail. Once completed, perform the same steps for assembling the other 

rackmount rail.

3U

2U

1U

position 9
position 8
position 7
position 6
position 5
position 4
position 3
position 2
position 1

position 3

position 1

(1) 

(2) 

Содержание BPSE24V40ART2U

Страница 1: ...User s Manual BPSE24V40ART2U BPSE48V40ART2U BPSE72V40ART2U Cyber Power Systems Inc www cyberpower com K01 C000610 00 ...

Страница 2: ......

Страница 3: ...ANT SAFETY INSTRUCTIONS 4 UNPACKING 5 OVERVIEW 6 FRONT REAR PANEL DESCRIPTION 6 HARDWARE INSTALLATION 7 RACKMOUNT INSTALLATION 7 VERTICAL TOWER INSTALLATION 8 BATTERY INSTALLATION AND REPLACEMENT 9 TECHNICAL SPECIFICATIONS 10 ...

Страница 4: ... voltage may exist between battery terminals and ground Test before touching CAUTION Wiring must be done by qualified personnel CAUTION DO NOT USE WITH OR NEAR AQUARIUMS To reduce the risk of fire do not use with or near aquariums Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out CAUTION Do not dispose of batteries in fire as the b...

Страница 5: ...lable on our website Please visit www cyberpower com and go to the Software Section for free download Rackmount rails 2 Screw hole dust covers 8 Rackmount ears Stands 2 Plastic washers 8 User s manual Battery cable Flat head screws M4X8L 8 Pan head screws M5X12L 4 ...

Страница 6: ...ccess 4 Automatic Detection of Extended Battery Module Connector Connect to UPS for automatic detection of Battery modules CONNECTION 1 POWER MODULE WITH ONE BATTERY MODULE Use the battery cable of the Battery module to connect the Battery module to the Power module CONNECTION 2 POWER MODULE WITH MULTIPLE BATTERY MODULES Step 1 Connect the first Battery module to the Power module via battery cable...

Страница 7: ...mount in 48 cm 19 inch panel racks from 46 4 to 73 8cm 18 3 to 29 inches deep Select the proper holes in the rack for positioning the Battery module in the rack The rails take up position 1 through position 3 2 Attach the rackmount rail to your rack with two M5X12L screws two plastic washers and two M5 nuts at the front of the rack Located in position 1 position 3 It can also be located in positio...

Страница 8: ...ck with four M5X12L screws at the front of the rack Located in position 2 position 5 VERTICAL TOWER INSTALLATION Step 1 Attach the base stands Tighten the screws M5X12 4pcs of the base stands rackmount ears onto the bottom of the Battery module Step 2 Attach dust covers Insert dust covers into the rackmount ear screw holes that are not being used position 1 position 3 position 2 position 5 1 2 ...

Страница 9: ... from the Battery module Step 2 Unscrew the steel bars and separate the steel bars from the Battery module Step 3 Remove the battery pack from the Battery module Step 4 Open the battery pack and change the batteries Step 5 Put the battery pack into the Battery module Re install the steel bars and top cover 5 1 2 3 4 ...

Страница 10: ...sets 12V x 4pcs x 2 sets 12V x 6pcs x 2 sets Rated Battery Voltage 24V 48V 72V Overload Protection Fuse Physical Dimension WxHxD mm 438 x 88 x 430 438 x 88 x 430 438 x 88 x 610 Net Weight kg 16 24 26 74 38 75 Environment Operating Temperature 32 F to 104 F 0 C to 40 C Operating Relative Humidity 20 to 90 Non Condensing ...

Страница 11: ......

Страница 12: ... Rd Neihu Dist Taipei City 114 Taiwan Entire contents copyright 2019 Cyber Power Systems Inc All rights reserved Reproduction in whole or in part without permission is prohibited PowerPanel Business and PowerPanel Personal are trademarks of Cyber Power Systems Inc ...

Отзывы: