I.B. 29C892B

Page 22

Effective 8/99

button to choose a particular category, Phase
for example, and the next selections are dis-
played Trip or No Trip (Figure 3-28).

Step 4: Once again, use the Right-Arrow or Left-

Arrow pushbuttons, if required, to move to a
different test category. Use the Select push-
button to choose a particular category, Trip for
example, and two different notices are momen-
tarily displayed before the next selection
appears (Figures 3-29 and 3-30).

Step 5: After the two momentary displays, the test cur-

rent screen is displayed permitting the selec-
tion of the desired test current (Figure 3-31). 

Step 6: The blinking cursor indicates the selectable test

current field. The current initially displayed is
the minimum test current value. Use the U p o r
Down pushbuttons to alter the current value. 

Step 7: Once all the test parameters have been select-

ed, hold Save pushbutton depressed and
depress Select pushbutton to initiate the test.
When the test is completed, a cause of trip
message is displayed (Figure 3-32).

Step 8: Use the Up-Arrow pushbutton to return to the

main menu.

Testing will not be permitted to proceed if there is
greater than 0.4 per unit of current flowing on a phase
circuit or 0.2 per unit of current on a ground circuit. The
maximum permitted current value can be determined by
multiplying the appropriate per unit value (0.4 or 0.2)
times the ampere rating of the installed rating plug. 

Notice: For currents less than the trip unit setpoint, no

message is displayed after the “Accepted
Message.” The trip unit will not be placed in a
Test Mode and, therefore, no pickup LEDs will
flash. The trip unit, however, must be reset.
The OPTIMizer will eventually return to the
main menu.

3-10  COPY AND DOWNLOAD COMMANDS

The OPTIMizer can quickly download trip unit setpoints
from one breaker to other breakers in a system. The
per-unit values (not the current ampere values) are
copied from one breaker and downloaded to any other
breaker in the OPTIM family within a system. The set-
tings are permanently retained in the memory of the
OPTIMizer until another copy sequence replaces them.

3-10.1  USING THE COPY COMMAND (CP)

Plug the OPTIMizer into the trip unit that the settings are
to be copied from. Move the cursor to the main menu
item CP. Press the Select key and wait while the
OPTIMizer reads the trip unit’s setpoints. The message
Accepted will be displayed if the copy was successfully
completed. The settings are now stored within the
OPTIMizer's memory and will be retained even after the
OPTIMizer is turned off. 

3-10.2  USING THE DOWNLOAD COMMAND (DL) 

Plug the OPTIMizer into the trip unit that the stored 
settings are to be downloaded to. Enter the password
for the OPTIMizer within the password main menu item
PA. Move the cursor to the main menu item DL. Press
the Select key and wait while the OPTIMizer gets the
address of the trip unit and then downloads the
OPTIMizer's stored settings to the trip unit. If the
OPTIMizer’s password was not entered, the operator
will be required to first enter their password and then
reselect the Download menu item from the main menu.
The message Accepted will be displayed if the settings
were successfully downloaded. 

Notice:  The Copy /Download commands will not 

change  factory enabled functions such as 
ground fault trip or alarm. When copying from a
trip unit with ground fault trip to a trip unit with 
ground fault alarm, only the pick-up, slope, and
time adjustments are copied.

Some breakers such as the DS will have setting limita-
tions based on the rating plug value. If settings are
downloaded which are not within the allowable limits of
the trip unit and rating plug, an error message will be
displayed. See I.L. 29C891 Table 3.3 for allowable set-
tings. This may also be the case for ground fault set-
tings in breakers above 1200 amps. 

3-11  RESET TRIP UNIT (RE)

The trip unit status indicators are generally reset by
pressing the Reset pushbutton on the trip unit. In some
instances, such as when a motor operator is used with
on an OPTIM breaker, it may be desirable to use a
remote reset. The reset trip feature is used in this case.

Содержание OPTIMizer

Страница 1: ...996 Cutler Hammer Instructions for Operation of OPTIMizer Hand Held Programmer For Use with Digitrip OPTIM Trip Units P R O T E C T I O N A N D C O O R D I N A T I O N C O M M U N I C A T I O N S S Y...

Страница 2: ...LAR PURPOSE OF MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CON TAINED HEREIN In no event will Cut...

Страница 3: ...8 2 4 Specification Summary 10 SECTION 3 OPERATION AND USE 3 1 General 11 3 2 Getting Started 11 3 3 Power Application 11 3 4 Function Overview 14 3 4 1 Select Address 14 3 4 2 Find Baud Address 14 3...

Страница 4: ...lay 14 3 3 Momentary Connect Failure Message Display 14 3 4 Address Invalid Display 14 3 5 Typical Momentary Successful Connection Message Display 14 3 6 Cursor on Password in Main Menu 14 3 7 Passwor...

Страница 5: ...Metered Values in Main Menu 19 3 23 First Display in Metered Values 19 3 24 Cursor Indicating Phase B Current Active 19 3 25 PHASE B IB Current Selected and Displayed 19 3 26 Cursor on Test Mode in Ma...

Страница 6: ...advanced programmable trip unit system Digitrip OPTIM Refer to Appendix A for all instructional material references Please read and understand this manual and all other relevant manuals before proceed...

Страница 7: ...AND FUNCTIONS An OPTIMizer must be used to configure the trip unit for communications on the INCOM Network This requires an operator during initial start up to Assign Unique Device Addresses Select B...

Страница 8: ...QUIPMENT AS SUCH IT SHOULD BE HANDLED CAREFULLY AT ALL TIMES TO AVOID POSSIBLE DEVICE DAMAGE 2 2 PACKAGE AND EXTERNAL CONNECTIONS The OPTIMizer Hand Held Programmer is packaged in a high strength plas...

Страница 9: ...hours the 9 volt battery will support depends upon the type of battery used Refer to Table 2 2 for information about battery choices When an auxiliary power supply is not being used the programmer wi...

Страница 10: ...OPTIMizer Battery Compartment with Battery Installed Figure 2 5 Auxiliary Power Module Shown Connected to OPTIMizer Direct Breaker Connection The first method for connecting the hand held program mer...

Страница 11: ...on and off To achieve power up the pushbutton must be pushed and held for approximately one second The programmer cannot be turned off while Find Baud Addr is displayed When the programmer is on power...

Страница 12: ...linking cursor horizontally to the right in the display from category to category Continued use of this pushbutton will wrap around and eventually return to the starting category Left Arrow Pushbutton...

Страница 13: ...he programmer Figure 2 2 The first line of the display is normally used to show the main menu selection possibilities A blinking cursor indi cates which category on the first line is active The sec on...

Страница 14: ...g of setpoints for connected trip unit valid password required to setup or change setpoints LD Long Delay Setting LDTI Long Delay Time LDA Long Delay Action LDS Long Delay Slope SDPU Short Delay Setti...

Страница 15: ...2 OPTIMizer Accessory Specifications Power Supply Battery ULTRALIFE Batteries Inc Lithium Power Cell Part U9VL 9 volts dc Auxiliary Power Module Cutler Hammer Catalog PRTAAPM Input 120 Vac Output 32...

Страница 16: ...source and the OPTIMizer Hand Held Programmer Refer to paragraph 2 2 2 for details on an external power connection Notice Keep in mind that an Auxiliary Power Module is always required if a Trip Test...

Страница 17: ...round Trip or No Trip Test Current Ground Current Neutral Current Total Energy Forward Energy Reverse Energy Power Peak Demand Power Factor Harmonic Distortion A B C and N Harmonic Content A B C and N...

Страница 18: ...tions Use Edit Values Up or Down Pushbuttons to alter active item or value Use Select and Save Pushbuttons simultaneously to save to memory or initiate test Some entries in Metered Values and Setpoint...

Страница 19: ...The OPTIMizer executes this func tion automatically when the OPTIMizer is first turned on Several attempts will be made to retrieve the address and baud rate If no trip unit is connected to the OPTIMi...

Страница 20: ...A For system security a password is required to change settings or use certain features To change the baud rate or trip unit address setpoints run test mode or download copied setpoints a correct pass...

Страница 21: ...enter a valid password pro ceed with the following steps Notice If the programmer automatically turns off or is intentionally turned off the procedure must be repeated from the beginning Use of an Aux...

Страница 22: ...of the four displayed zeros is active and able to be altered Use the Up or Down pushbuttons to change the active number Use the Right Arrow or Left Arrow pushbuttons to move the cursor from one digit...

Страница 23: ...ress is password protected Step 5 may require the entry of a valid password before any changes are accepted If the pro grammer was already turned on and a valid password was initially entered as descr...

Страница 24: ...e Right Arrow or Left Arrow pushbuttons to move the cursor from one digit to another Step 4 Once the desired breaker address is displayed hold Save pushbutton depressed and depress Select pushbutton T...

Страница 25: ...nt such as I4 t Figure 3 21 Step 8 Hold Save pushbutton depressed and depress Select pushbutton This simultaneous use of the two pushbuttons will enter the new setpoint into memory Notice Keep in mind...

Страница 26: ...d in Table 2 1 Step 10 Use the Up Arrow pushbutton to return to the main menu Figure 2 9 3 9 TEST TRIP UNIT Digitrip OPTIM 550 750 and 1050 Trip Units contain a test capability One of the means for pe...

Страница 27: ...r in the OPTIM family within a system The set tings are permanently retained in the memory of the OPTIMizer until another copy sequence replaces them 3 10 1 USING THE COPY COMMAND CP Plug the OPTIMize...

Страница 28: ...battery information The OPTIMizer Hand Held Programmer should be stored in an environment that does not exceed the stor age temperature range of 30 C to 85 C The environ ment should also be free of ex...

Страница 29: ...pond Incorrect key press Let OPTIMizer time out for 30 seconds Paragraph 3 3 to pressing on off Unit will shut off or go to main menu OPTIMizer turns off after Energy saver powered unit off several mi...

Страница 30: ...Digitrip OPTIM Trip Unit System OPTIM Trip Unit System Overview IB 29C890 OPTIM Trip Units IB 29C891 OPTIMizer Hand Held Programmer IB 29C892 Breaker Interface Module IB 29C893 Digitrip RMS Trip Units...

Страница 31: ...6 2500A I2t Long Flat Short Delay Phase SC 6340 96 2500A I4t Long Flat Short Delay Phase SC 6341 96 1600A Instantaneous Override Phase SC 6342 96 2000A Instantaneous Override Phase SC 6343 96 2500A In...

Страница 32: ...act between the purchaser and Cutler Hammer NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PAR TICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEAL IN...

Отзывы: