I.B. 29C892B
Page 9
Effective 8/99
Displayed
Display
Additional Comments
Menu Items
Definition
SA
SELECT ADDRESS
Network use only – permits selection of specific trip unit address within network
FI
FIND BAUD/ADDR
Search to identify address and baud rate of connected trip unit (8 conductor custom phone cord only)
ID
FIND PRODUCT ID
Identification of type and frame rating of connected breaker
BA
CHANGE BAUD/ADDRESS
Permits the initial setup or changing of address and baud rate of connected trip unit –
valid password required to setup or change address
RP
RATING PLUG
Rating plug size installed in connected trip unit
ME
METERED VALUES
Depending on trip unit connected, some or all of the values are displayed:
• Current (A)
- Phases A, B, C, Ground and Neutral
• Energy (kWh)
- Total, Forward and Reverse
• Power (kW)
- Power and Peak Demand
• Power Factor
• THD Currents (%)
- Phases A, B, C and Neutral
• Harmonic Content
- Phases A, B, C and Neutral
TM
TEST MODE
Provides for Phase or Ground, Trip or Non-Trip Test (valid password)
SP
SETPOINTS
Permits viewing, initial setup and changing of setpoints for connected trip unit – valid password
required to setup or change setpoints:
• LD
- Long Delay Setting
• LDTI
- Long Delay Time
• LDA
- Long Delay Action
• LDS
- Long Delay Slope
• SDPU
- Short Delay Setting
• SDTI
- Short Delay Time
• SDA
- Short Delay Action
• SDS
- Short Delay Slope
• IN
- Instantaneous Setting
• INA
- Instantaneous Action
• DSC
- Discriminator
• GFP
- Ground Fault Setting
• GFT
- Ground Fault Time
• GFA
- Ground Fault Action
• GFS
- Ground Fault Slope
• HLA
- High Load Setting
• PTM
- Powered Thermal Memory
• UPM
- Unpowered Thermal Memory
• FRQ
- Line Frequency
• NR
- Neutral Ratio
• AWC
- Auto Waveform Capture
• PI
- Phase A Identification
PA
PASSWORD
Permits authorized personnel to change or enter 4 digit password
TC
TRIP EVENT COUNT
Display of number of circuit breaker automatic trip operations
CT
CAUSE-OF-TRIP
Displays one of four possible modes of trip on most recent automatic trip operation:
• Long Delay
• Short Delay
• Instantaneous
• Ground Fault
FW
FIRMWARE REV/VER
Displays Firmware Revision and Version of OPTIMizer or connected trip unit
CP
COPY COMMAND
Loads trip unit settings into OPTIMizer
DL
DOWNLOAD COMMAND
Sends stored settings in OPTIMizer to trip unit (valid password)
RE
RESET TRIP UNIT
Resets trip unit LEDs, historical current etc.
Table 2.1 Programmable Categories