Cutler-Hammer IQ Analyzer Скачать руководство пользователя страница 8

Use (F2) or (F3) PBs to

Move to Incoming

Line-Line Voltage

Press and Release

Select (F1) PB

Incoming L-L
Voltage Blinking

L-L Voltage
Rating with
3 Digits 
Displayed

Use F1-F4 PBs to

Establish and Enter 

480 Volts

Incoming
L-L Voltage
Blinking

Use F2-F4 PBs

to Move to 

PT Primary Rating

PT Primary
Rating Blinking

Press and Release

Select (F1) PB

PT Primary
Rating with
6 Digits 
Displayed

Use F1-F4 PBs 

to Establish and

Enter 120 Volts

PT Primary
Rating Blinking

Use F2-F4 PBs

to Move to

CT Primary Rating

CT Primary
Rating Blinking

Press and Release

Select (F1) PB

CT Primary
Rating with
5 Digits
Displayed

Use F1-F4 PBs to

Establish and

Enter 1200 A

CT Primary
Rating Blinking

Use F2-F4 PBs

to move to GND

CT Primary Rating

GND CT
Primary
Rating Blinking

P G M / G E N

SELECT PARAMETER:
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING
GND CT PRIMARY RATING

SEL  UP  DOWN  PGDN

Press and Release

Select (F1) PB

GND CT
Primary Rating 
with 5 Digits
Displayed

Use F1-F4 PBs to

Establish and

Enter 50 A

GND CT
Primary
Rating Blinking

Press Program

PB to exit

Program Mode

P G M / G E N / G C T

GND CURR TRANSFORMER
PRIMARY RATING:

5 TO 10,000 AMPS

(MUST BE 5 AMP

SECONDARY CT)

0 0 0 5 0 : 5

-->   UP  DOWN  ENTER

P G M / G E N

SELECT PARAMETER:
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING
GND CT PRIMARY RATING

SEL  UP  DOWN  PGDN

P G M / G E N / C T

CURRENT TRANSFORMER
PRIMARY RATING:

5 TO 10,OOO AMPS
(MUST BE 5 AMP

SECONDARY CT)

0 1 2 0 0 : 5

-->   UP  DOWN  ENTER

P G M / G E N / P T

PT PRIMARY L-L RATING

120 TO 500,000 V

(SEE USER’S MANUAL IF

NOT USING 120V
SECONDARY PTS)

0 0 0 1 2 0 : 1 2 0

-->   UP  DOWN  ENTER

P G M / G E N / I N V O L T

INCOMING L-L VOLTAGE
APPLIED TO VOLTAGE
INPUT TERMINALS A,B,
C, N OF IQ ANALYZER
(100 TO 600 VAC):

4 8 0

-->   UP  DOWN  ENTER

15

Programming Example

(USER’S MANUAL SECTION 6)

Meter a typical load on a 480 volt, 3 phase 3 wire
(ABC phase rotation), 60Hz system with 1200/5
CTs, 50/5 ground CTs and no PTs. (Assume
Kilowatt-hour energy resolution, and lagging vars
& Power Factor negative at load.)
NOTE: The IQ Analyzer must be programmed to
a PT ratio of 120/120 or unity for the IQ Analyzer
to recognize there are no PTs.

From Main Menu

Press and Release

Program PB

Press Up (F2), then

Enter (F4) to input

default password

10000

Top Level Entry 
Screen Displayed

Incorrect 
Password Exits
Program Mode 
Automatically

Program Mode

Top Level Menu

Displayed

General Setup
Blinking

Press and Release

Select (F1) PB

Type of System
Blinking

Press and Release

Select (F1) PB

Choose Type of
System with
Parameters
Displayed

Use F1-F3 PBs to

Move an Select

3 Phase/3 Wire

Phase Rotation with
Parameters Displayed

Use F2-F4 PBs to

Move and 

Enter ”ABC”

Type of System
Blinking

Use (F2) or (F3) PBs

to Move to 

Frequency

Frequency
Blinking

Press and Release

Select (F1) PB

Frequency
Choices
Displayed

Use F2-F4 PBs to

Move to and Enter

60Hz

Type of System
Blinking

P G M

CHOOSE CATEGORY:

GENERAL SETUP
ANALOG INPUTS
ANALOG OUTPUTS
DISCRETE INPUTS
EVENT TRIGGERS

SEL  UP  DOWN  ENTER

P G M / G E N

SELECT PARAMETER:
TYPE OF SYSTEM
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING

SEL  UP  DOWN  PGDN

P G M / G E N / T Y P E

3 PHASE/4 WIRE

*3 PHASE/3 WIRE

SINGLE PHASE/3 WIRE
SINGLE PHASE/2 WIRE

SEL  UP  DOWN

P G M / G E N / T Y P E / 3 P H 3 W
*ABC - PHASE ROTATION

CBA - PHASE ROTATION

UP  DOWN  ENTER

P G M / G E N

SELECT PARAMETER:
TYPE OF SYSTEM
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING

SEL  UP  DOWN  PGDN

P G M / G E N / F R E Q

25 HZ
40 HZ
50 HZ

*  60 HZ

UP  DOWN  ENTER

P G M / G E N

SELECT PARAMETER:
TYPE OF SYSTEM
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING

SEL  UP  DOWN  PGDN

continued on next page

P G M - M A I N

LAST PROGRAMMED:

6/11/97 11:48:07A

INCOM ADDR:000
SOFTWARE VER. 1.14

ENTER PASSWORD:00000
(00000=VIEW ONLY PW)
-->  UP  DOWN  ENTER

Содержание IQ Analyzer

Страница 1: ...Cutler Hammer IQ Analyzer START QUICKSTART GUIDE...

Страница 2: ...lly understand the wide array of features offered by your IQ Analyzer it is strongly recommended that operators read the User s Manual Following initial power up of the IQ Analyzer the displayed Meter...

Страница 3: ...ol relaying analog inputs outputs and communications capabilities It will replace dozens of existing individual meters recorders and relays The IQ Analyzer displays a comprehensive list of metered par...

Страница 4: ...nager PGM DISPMGR CUST 7 Display Mode USER S MANUAL SECTIONS 5 2 The IQ Analyzer monitors and displays a compre hensive list of metered parameters The Meter Menu provides easy access using Up Down PBs...

Страница 5: ...and information Note on Sign Convention USER S MANUAL SECTIONS 5 22 As a factory default lagging vars and power factor are represented as negative values at the load This is a negative sign convention...

Страница 6: ...ent damage The only exception is when connecting disconnecting ribbon cables at J2 or J3 11 Wiring installation for the IQ Analyzer must follow a suitable Wiring Plan Drawing and conform to applicable...

Страница 7: ...___________ Change Password Enter new 5 digit password if required __ __ __ __ __ General Setup Settings Worksheet 13 Quick Start Procedure USER S MANUAL SECTIONS 4 5 During initial setup of your IQ A...

Страница 8: ...SECTION 6 Meter a typical load on a 480 volt 3 phase 3 wire ABC phase rotation 60Hz system with 1200 5 CTs 50 5 ground CTs and no PTs Assume Kilowatt hour energy resolution and lagging vars Power Fac...

Страница 9: ...Setup Blinking Type of System Blinking Month Blinking Parameter Digit Blinking Parameter Blinking Time Date Programming Example Password Programming Example From Main Menu Press and Release Program P...

Страница 10: ...r Re enter program setpoints using proper password Customer established or factory default 44444 or 10000 1 I O Fuse Littlefuse Plug in Microfuse Catalog 273 250 0 25A 125V or equivalent Troubleshooti...

Страница 11: ...Cutler Hammer For additional information or technical assistance contact ADVANCED PRODUCT SUPPORT CENTER 1 800 809 2772 www cutlerhammer eaton com...