Use (F2) or (F3) PBs to
Move to Incoming
Line-Line Voltage
Press and Release
Select (F1) PB
Incoming L-L
Voltage Blinking
L-L Voltage
Rating with
3 Digits
Displayed
Use F1-F4 PBs to
Establish and Enter
480 Volts
Incoming
L-L Voltage
Blinking
Use F2-F4 PBs
to Move to
PT Primary Rating
PT Primary
Rating Blinking
Press and Release
Select (F1) PB
PT Primary
Rating with
6 Digits
Displayed
Use F1-F4 PBs
to Establish and
Enter 120 Volts
PT Primary
Rating Blinking
Use F2-F4 PBs
to Move to
CT Primary Rating
CT Primary
Rating Blinking
Press and Release
Select (F1) PB
CT Primary
Rating with
5 Digits
Displayed
Use F1-F4 PBs to
Establish and
Enter 1200 A
CT Primary
Rating Blinking
Use F2-F4 PBs
to move to GND
CT Primary Rating
GND CT
Primary
Rating Blinking
P G M / G E N
SELECT PARAMETER:
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING
GND CT PRIMARY RATING
SEL UP DOWN PGDN
Press and Release
Select (F1) PB
GND CT
Primary Rating
with 5 Digits
Displayed
Use F1-F4 PBs to
Establish and
Enter 50 A
GND CT
Primary
Rating Blinking
Press Program
PB to exit
Program Mode
P G M / G E N / G C T
GND CURR TRANSFORMER
PRIMARY RATING:
5 TO 10,000 AMPS
(MUST BE 5 AMP
SECONDARY CT)
0 0 0 5 0 : 5
--> UP DOWN ENTER
P G M / G E N
SELECT PARAMETER:
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING
GND CT PRIMARY RATING
SEL UP DOWN PGDN
P G M / G E N / C T
CURRENT TRANSFORMER
PRIMARY RATING:
5 TO 10,OOO AMPS
(MUST BE 5 AMP
SECONDARY CT)
0 1 2 0 0 : 5
--> UP DOWN ENTER
P G M / G E N / P T
PT PRIMARY L-L RATING
120 TO 500,000 V
(SEE USER’S MANUAL IF
NOT USING 120V
SECONDARY PTS)
0 0 0 1 2 0 : 1 2 0
--> UP DOWN ENTER
P G M / G E N / I N V O L T
INCOMING L-L VOLTAGE
APPLIED TO VOLTAGE
INPUT TERMINALS A,B,
C, N OF IQ ANALYZER
(100 TO 600 VAC):
4 8 0
--> UP DOWN ENTER
15
Programming Example
(USER’S MANUAL SECTION 6)
Meter a typical load on a 480 volt, 3 phase 3 wire
(ABC phase rotation), 60Hz system with 1200/5
CTs, 50/5 ground CTs and no PTs. (Assume
Kilowatt-hour energy resolution, and lagging vars
& Power Factor negative at load.)
NOTE: The IQ Analyzer must be programmed to
a PT ratio of 120/120 or unity for the IQ Analyzer
to recognize there are no PTs.
From Main Menu
Press and Release
Program PB
Press Up (F2), then
Enter (F4) to input
default password
10000
Top Level Entry
Screen Displayed
Incorrect
Password Exits
Program Mode
Automatically
Program Mode
Top Level Menu
Displayed
General Setup
Blinking
Press and Release
Select (F1) PB
Type of System
Blinking
Press and Release
Select (F1) PB
Choose Type of
System with
Parameters
Displayed
Use F1-F3 PBs to
Move an Select
3 Phase/3 Wire
Phase Rotation with
Parameters Displayed
Use F2-F4 PBs to
Move and
Enter ”ABC”
Type of System
Blinking
Use (F2) or (F3) PBs
to Move to
Frequency
Frequency
Blinking
Press and Release
Select (F1) PB
Frequency
Choices
Displayed
Use F2-F4 PBs to
Move to and Enter
60Hz
Type of System
Blinking
P G M
CHOOSE CATEGORY:
GENERAL SETUP
ANALOG INPUTS
ANALOG OUTPUTS
DISCRETE INPUTS
EVENT TRIGGERS
SEL UP DOWN ENTER
P G M / G E N
SELECT PARAMETER:
TYPE OF SYSTEM
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING
SEL UP DOWN PGDN
P G M / G E N / T Y P E
3 PHASE/4 WIRE
*3 PHASE/3 WIRE
SINGLE PHASE/3 WIRE
SINGLE PHASE/2 WIRE
SEL UP DOWN
P G M / G E N / T Y P E / 3 P H 3 W
*ABC - PHASE ROTATION
CBA - PHASE ROTATION
UP DOWN ENTER
P G M / G E N
SELECT PARAMETER:
TYPE OF SYSTEM
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING
SEL UP DOWN PGDN
P G M / G E N / F R E Q
25 HZ
40 HZ
50 HZ
* 60 HZ
UP DOWN ENTER
P G M / G E N
SELECT PARAMETER:
TYPE OF SYSTEM
F R E Q U E N C Y
INCOMING L-L VOLTAGE
PT PRIMARY RATING
CT PRIMARY RATING
SEL UP DOWN PGDN
continued on next page
P G M - M A I N
LAST PROGRAMMED:
6/11/97 11:48:07A
INCOM ADDR:000
SOFTWARE VER. 1.14
ENTER PASSWORD:00000
(00000=VIEW ONLY PW)
--> UP DOWN ENTER