Cutler-Hammer IQ Analyzer Скачать руководство пользователя страница 10

Unit displays:
“Hardware Failure”
“Register Failure”
“Multiply Failure”
“Divide Failure”
“Logic Failure”
“ A d d / S u b t r a c t
F a i l u r e ”

Unit displays:
“Internal RAM
E r r o r ”
“External RAM
E r r o r ”
“External ROM
E r r o r ”

Unit displays:
“Reverse Sequence”

Unit fails to capture
Harmonic Data
when Manual
Capture is pressed.

Unit fails to com-
municate over
IMPACC network.

Display goes blank
after several min-
utes.

Unit setpoints
unchanged upon
exiting program
mode.

Possible IQ Analyzer
hardware failure.

IQ Analyzer hardware
error.

IQ Analyzer has detect-
ed phasing difference
between programmed
setpoint and actual sys-
tem parameters.

No manual capture
event trigger has been
programmed.

Wrong or conflicting
address set on IPONI.

Blown fuse on 
IQ Analyzer. 

Communications
wiring error.

IPONI failure.

Display Manager
Screen Saver Option is
set to blank rather than
dim.

Unit was in
View-Only mode using
password (00000).

•Reboot Unit by

mometarily removing
power cable at connector
J2.

•Replace Unit.

•Reboot Unit.
•Replace Unit.

•Verify actual system

phasing. Capture an
event and compare
phase angles of Va, Vb,
Vc, Ia, Ib, Ic to detect
possible wiring error(s).

• Verify that IQ Analyzer

setpoint matches actual
system phasing.

• Verify IQ Analyzer con-

nections.

• Enter Program Mode

and set up an Event
Trigger for Manual
Capture.

• Check that IPONI has a

unique address on the
system and that soft-
ware is addressing 
proper unit.

• Check input/output fuse

adjacent to IQ Analyzer
communication connec-
tor. Replace if
necessary.

1

• Verify wiring is in con-

formance with IMPACC
wiring rules.

• Press any pushbutton to

activate display.

• Program longer timeout

in Meter Menu Return
Time in Display
Manger.

• Re-enter program 

setpoints using proper
password. Customer
established or  factory
default (44444 or 10000).

1

I/O Fuse: Littlefuse Plug-in Microfuse, Catalog #273.250, 0.25A, 125V or

equivalent.

Troubleshooting

(USER’S MANUAL SECTIONS 7)

19

ymptom         Probable Cause    Possible Solutions(s)

 Operator Panel

icator LED’s

 off.

ne or more volt-

ge phases read

ncorrectly.

ower parameters

Watt, var, VA,

ower Factor)

ead incorrectly.

ncorrect readings

n one or more

urrents.

Line voltage level is

d e f i c i e n t .

Separate source con-

trol power is deficient.

ac line connections (or

optional external PTs)

are not properly

w i r e d .

Blown or loose fuse(s).  

Blown or loose

fuse(s).

Incorrect voltage 

settings.

Phasing for voltage

and current is mis-

matched.

CT polarity is

reversed.

Incorrect current

transformer ratio set-

ting.

• Locate cause of defi-

ciency in ac line.

• Locate deficiency in

the ac control power

l i n e .

• Verify that the ac line

(and/or PTs) are wired

p r o p e r l y .

• Verify line voltage

with multimeter.

Check power module

fuse(s) on affected

phase(s). These are

located just above volt-

age inputs (behind the

cover of power mod-

ule). Reseat or replace

fuse(s) as necessary.

1

•Verify line voltage with

multimeter. Check

power module fuse(s)

on affected phase(s)

located just above the

voltage inputs behind

the cover of power

module. Reseat or

replace fuse(s) as 

n e c e s s a r y .

1

• Verify correct settings

programmed in the IQ

Analyzer for system

type,L-L voltage and

PT rating.

• Capture an event and

compare phase angles

of Va, Vb, Vc, Ia, Ib, Ic

to detect possible

wiring error(s).

• Verify connections per

wiring diagrams.

• Reverse CT leads.

Verify proper wiring

and grounding.

• Verify incoming cur-

rent using a separate

a m m e t e r .

• Verify proper CT ratio

s e t t i n g s .

• Check CT wiring and

g r o u n d i n g .

Power Module Fuse: Buss KTK-R-3/4 or equivalent (3/4 amp).

oubleshooting

oubleshooting

(USER’S MANUAL SECTIONS 7)

18

Содержание IQ Analyzer

Страница 1: ...Cutler Hammer IQ Analyzer START QUICKSTART GUIDE...

Страница 2: ...lly understand the wide array of features offered by your IQ Analyzer it is strongly recommended that operators read the User s Manual Following initial power up of the IQ Analyzer the displayed Meter...

Страница 3: ...ol relaying analog inputs outputs and communications capabilities It will replace dozens of existing individual meters recorders and relays The IQ Analyzer displays a comprehensive list of metered par...

Страница 4: ...nager PGM DISPMGR CUST 7 Display Mode USER S MANUAL SECTIONS 5 2 The IQ Analyzer monitors and displays a compre hensive list of metered parameters The Meter Menu provides easy access using Up Down PBs...

Страница 5: ...and information Note on Sign Convention USER S MANUAL SECTIONS 5 22 As a factory default lagging vars and power factor are represented as negative values at the load This is a negative sign convention...

Страница 6: ...ent damage The only exception is when connecting disconnecting ribbon cables at J2 or J3 11 Wiring installation for the IQ Analyzer must follow a suitable Wiring Plan Drawing and conform to applicable...

Страница 7: ...___________ Change Password Enter new 5 digit password if required __ __ __ __ __ General Setup Settings Worksheet 13 Quick Start Procedure USER S MANUAL SECTIONS 4 5 During initial setup of your IQ A...

Страница 8: ...SECTION 6 Meter a typical load on a 480 volt 3 phase 3 wire ABC phase rotation 60Hz system with 1200 5 CTs 50 5 ground CTs and no PTs Assume Kilowatt hour energy resolution and lagging vars Power Fac...

Страница 9: ...Setup Blinking Type of System Blinking Month Blinking Parameter Digit Blinking Parameter Blinking Time Date Programming Example Password Programming Example From Main Menu Press and Release Program P...

Страница 10: ...r Re enter program setpoints using proper password Customer established or factory default 44444 or 10000 1 I O Fuse Littlefuse Plug in Microfuse Catalog 273 250 0 25A 125V or equivalent Troubleshooti...

Страница 11: ...Cutler Hammer For additional information or technical assistance contact ADVANCED PRODUCT SUPPORT CENTER 1 800 809 2772 www cutlerhammer eaton com...

Отзывы: