Содержание E2 L

Страница 1: ...cent of the solenoid coil rating The UVR consists of a continuous rated solenoid with a plunger and reset lever assembled to a plug in module The plug in module is mounted in slots in the top of the t...

Страница 2: ...NTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT BEFORE REMOVING A CIRCUIT BREAKER INSTALLED INA N ELECTRICAL SYSTEM MAKE SURE THE CIRCUIT BREAKER IS SWITCHED TO THE O...

Страница 3: ...it falling out of recessed hole in trip unit and into molded case switch mechanism 2 6 Remove interphase barrier between accessory mounting cavity and operating mechanism see Figure 2 3 2 7 Install re...

Страница 4: ...ing of leads of opposite side through rear wiring trough FAILURE TO KEEP FINGERS AWAY FROM MOVING PARTS CAN CAUSE PERSONAL INJURY WHEN CHECKING ACCESSORY DO NOT PUT FINGERS NEAR MOVING PARTS INSIDE CI...

Страница 5: ...ter taking all necessary safety precautions apply rated voltage to UVR Reset and close circuit breaker Confirm that cir cuit breaker trips when voltage is removed 2 15 Install circuit breaker Accessor...

Страница 6: ...and V Min Min Max Response Breaker Breaker Voltage V Contact Contact Separation Opening 120 120 44 5 77 93 5 2 1 5 15 25 1500 Table 1 1 AC 50 60 Hz Undervoltage Release Mechanism Handle Reset Ratings...

Страница 7: ...I L 29C171 Page 7 Effective 3 98...