Page S
Notes:
1
This switch has eight (8) positions, and seven (7)
of them show
"DIS"
in the window, while ONLY
ONE position shows "[BLANK]".
2
When the
"OVERRIDE/"
window shows
"[BLANK]", the only fast-acting high short-circuit
protection available is the OVERRIDE [Fixed
Instantaneous]. (See 3.5 below.)
3.5 OVERRIDE (Fixed Instantaneous)
(For Types
LS
And
LSG
Trip Units Only)
When the Digitrip RMS 51 0 Trip Unit is not equipped with
an adjustable instantaneous setting, i.e., types LS or
LSG, the Fixed Instantaneous "Override" analog trip cir
cuit is automatically pre-set to a value no greater than the
short-time withstand current rating of the circuit breaker
in which the trip unit is installed. Since the specific values
vary for different circuit breaker types and ratings, refer to
time-current curves, listed in Section 9, for the values
applicable to your breaker. If breaker trips due to high
instantaneous current, the "OVERRIDE" LED will light
"RED".
3.6 Zone Interlocking
Zone Selective Interlocking (or Zone Interlocking) is avail
able (see Fig. 3) for Digitrip RMS Trip Units having Short
Delay and/or Ground Fault protection. Zone Selective
Interlocking provides the fastest possible tripping for
faults within the breaker's zone of protection, and yet also
provides positive coordination among all breakers in the
system (mains, ties, feeders and downstream breakers)
to limit the outage to the affected part of the system only.
When Zone Interlocking is enabled, a fault within the
breaker's zone of protection will cause the RMS DIG
ITRIP trip unit to:
a)
Trip the affected breaker instantaneously,
and at the same time
b)
Send a signal to upstream RMS DIGITRIP
trip units to restrain from tripping immedi
ately. The restraining signal causes the
upstream breakers to follow their set coor
dination times, so that only the minimum
service is disrupted, while the fault is
cleared in the shortest time possible.
(This signal requires only a single pair of wires from the
output terminals of the downstream breaker's trip unit to
the input terminals of the upstream breaker's trip unit. For
specific instructions see the applicable connection dia
grams for your breaker listed in Section 9.0.)
I.L. 29-8858
Note: If a breaker (M) receives a Zone Interlocking
signal from another breaker (F), but the fault current
level is less than the trip unit setting for breaker (M),
the signal from the other breaker (F) will not cause
breaker (M) to trip.
A
CAUTION
IF ZONE INTERLOCKING IS NOT TO BE USED (I.E.
STANDARD TIME-DELAY COORDINATION ONLY IS
INTENDED), THE ZONE INTERLOCKING TERMINALS
MUST BE CONN ECTED WITH JUMPER WIRES, AS
SPECIFIED ON THE CONNECTION DIAGRAMS FOR
YOUR BREAKER (SEE SECTION 9.0), SO THE TIME
DELAY SETTINGS WILL PROVIDE THE INTENDED
COORDINATION.
For an example of how Zone Selective Interlocking may
be used, See Appendix A.
4.0 PROTECTION SETTINGS
4.1 General
Prior to placing circuit breaker in operation, each trip unit
protection setting must be set to the values specified by
the engineer responsible for the installation. The number
of settings that must be made is determined by the pro
tector model supplied as illustrated in Figs. 2.1 through
2.6. Each setting is made with a rotary switch, using a
small screwdriver. The selected setting for each adjust
ment appears in its respective rectangular viewing win
dow as illustrated in Fig. 1 .
The installed rating plug establishes the maximum con
tinuous current rating of the circuit breaker
(In)·
Instanta
neous and ground current settings are defined in
multiples of (In).
To illustrate the effect of each protection curve setting,
simulated Time-Current curves are pictured on the face
of the trip unit. The rotary switch to make each setting is
located nearest that portion of the simulated Time-Cur
rent curve it controls. Should an automatic "trip" occur (as
a result of the current exceeding the pre-selected value),
the LED in the appropriate segment of the simulated
Time-Current curve will light "RED" indicating the reason
for "trip".
The available settings, along with the illustrated effect of
changing the settings, are given in Figs. 4.1 through 4.7.
Effective May 1 997
www
. ElectricalPartManuals
. com
Содержание Digitrip RMS 510
Страница 17: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Page 1 8 I L 29 8858 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 19: ...I L 29 8858 Page 1 9 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 37: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 38: ...Page 1 8 I L 29 8858 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 39: ...I L 29 8858 Page 19 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 57: ...I L 29 8858 Page 1 7 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 58: ...Page 1 8 I L 29 8858 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 59: ...I L 29 8858 Page 1 9 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 77: ...I L 29 8858 Page 1 7 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 78: ...Page 1 8 I L 29 8858 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 79: ...I L 29 8858 Page 19 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 97: ...I L 29 8858 Page 1 7 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 98: ...Page 1 8 I L 29 8858 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 99: ...I L 29 8858 Page 1 9 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 117: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 118: ...Page 18 I L 29 8858 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 119: ...I L 29 8858 Page 19 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 137: ...I L 29 8858 Page 1 7 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 138: ...Page 1 8 I L 29 8858 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 139: ...I L 29 8858 Page 19 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 157: ...I L 29 8858 Page 17 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 158: ...Page 1 8 I L 29 8858 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 159: ...I L 29 8858 Page 1 9 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 177: ...I L 29 8858 Page 17 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 178: ...Page 1 8 I L 29 8858 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 179: ...I L 29 8858 Page 1 9 NOTES Effective May 1 997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...