Effective 2/2/2001
Page 28
I.L. 70C1037H03
3. The Short Delay Current Setting is a multiple of (
I
r):
Short Delay Current Setting = SD x (
I
r) = SD x [LD x
(
I
n)] (see Section 4.4).
CAUTION
BEFORE YOU FIT THE RATING PLUG INTO THE TRIP
UNIT, BE SURE TO CHECK THAT EACH BREAKER
POLE SENSOR RATING MATCHES THAT PRINTED ON
THE RATING PLUG DOOR. INSTALLING A RATING
PLUG THAT DOES NOT MATCH THE SENSOR RATING
CAN PRODUCE SERIOUS MISCOORDINATION AND/OR
FAILURE OF THE PROTECTION SYSTEM.
NOTE:
Rating plugs from Digitrip models 210, 500, or 510
CANNOT
be used with 520 family model Trip Units.
8.0 RECORD KEEPING
Use the forms shown in Figures 8.1 and 8.2 for record
keeping. Fill in these forms, giving the indicated reference
information and initial time-current trip function settings. If
desired, make a copy of the form and attach it to the
interior of the breaker cell door or another visible location.
Figure 8.3 provides a place for recording test data and
actual trip values.
Ideally, sheets of this type should be used and maintained
by those personnel in the user’s organization that have the
responsibility for protection equipment.
9.0 REFERENCES
9.1 Magnum and Magnum DS Circuit Breakers
I.B. 2C12060
Magnum DS Breaker Instructions
I.B. 2C13060
Magnum I. Breaker Instructions
4A36346
Zone Interlocking Application with Non-
Magnum Breakers
9.2 Time-Current Curves
The Time-Current Curves are listed below for particular trip
unit models. All protection function time-current settings
should be made following the recommendations of the
specifying engineer in charge of the installation.
70C1009
Digitrip 220 (LI) Curve
70C1006
Digitrip 520 (LS) Curve
70C1007
Digitrip 520 (I) Curve
70C1008
Digitrip 520 (G) Curve