FIGURE 7
Set Screws
45° MAX
2c. Square Pole Architectural Arm
This luminaire has been configured the same as 4 and
no adapter plate is needed to mount to a square pole.
Hole pattern on square pole shall be in accordance with
Figure 6.
• Place fixture against pole. Adjust nut plate
(See Figure 3.) to desired hole spacing and tighten set
screw on plate.
• For legacy diagonal bolt pattern (Figure 5.) set nut
plate to 4.58” (116 mm). For all other mounting
patterns reference Figure 2.
• Install 3/8 bolt, lock washer and washer in top hole as
shown and tighten into nut plate. (See Figure 4).
• Install 3/8 bolt, lock washer and washer below arm as
shown and tighten into nut plate.
• Torque top and bottom bolts to 25-32 ft-lbs
(34-43 N-m).
• Inspect installation to ensure fixture is secure.
•
NOTE: Make all electrical connections in accordance
with the National Electrical Code and any applicable
local code requirements.
• Strain relief for incoming power must be provided in
the pole top by the customer.
Terminal Block (Optional)
• Supply Wire Type and Size, for Customer Connection
to (if option present) Terminal Block: 16 AWG (1.5mm
2
)
to 6 AWG (10mm
2
) Solid or Stranded.
WIRING
3
CAUTION
Risk of Damage or Injury: Door should be closed with
screw until fixture in final location.
DRILLING TEMPLATE SQUARE POLE MOUNTING
FIGURE 6
2.1960 in.
(56 mm)
.438 in. DIA.
(11 mm DIA.)
(2 PLACES)
5.2500 in.
(133 mm)
(MIN.)
1.250 in. DIA.
(32 mm DIA.)
(HOLE)
.656 in. (17 mm)
1.312 in. (33 mm)
4.3920 in.
(112 mm)
2d. Knuckle Slipfitter for 2-3/8 in. (60mm) to 3.0 in.
(76mm) OD Vertical Tenon
This luminaire has been configured to provide 0 to 45°
vertical aiming in 5° increments and mount on 2-3/8-inch
O.D. (73mm) through 3-inch O.D. (76mm) vertical pipe.
• Place slipfitter on the tenon.
• Clamp the fixture to the pipe with three set screws
(See Figure 6) Tighten set screws to 18-22 foot pounds
(24-30 N-m).
• To aim the luminaire, loosen the knuckle bolt, adjust
the aim 0 to 45°, and tighten to 45-50 ft-lbs (61-68 N-m).
• Inspect installation to ensure fixture is secure.
• Open wiring compartment cover loacted on the
mounting bracket. Make electrical connections and
close wiring compartment cover. Seal wall mounting
flange to the mounting surface with silicone, caulk,
or equivalent.
• To aim the luminaire loosen the knuckle bolt, adjust
the aim 0° to 45° (see Figure 7), and tighten to
45-50 ft-lbs (61-68 N-m).
Terminal Block Connections:
Terminal Board Position
Supply Type
L1
High Line
G
Ground
N/L2
Low Line/Neutral
•
NOTE: Verify that supply voltage is correct by
comparing it to nameplate inside door or on carton.
• See table below for screw torques (Table 1).
WARNING
Under no conditions should architectural arm mounting
bolts be torqued to greater than 32 foot pounds (43 N-m).
Terminal Block Torque Table UL Units:
Wire Range Copper
Aluminum
Torque (in lbs)
10-16 SOL,STR
30
8-6 SOL,STR
STR6, SOL, STR
45
2e. Wall Mounted Units:
The wall mounting plate has four .438 inch clearance
holes spaced 4.375 (H) x 2.875 (V) inches for mounting.
Do not mount the unit such that the hinge side of door
is higher than the latch side of door