M510-2

, page 2 

Dehumidifier model NADER YARD PRO 

References (A, B) 

1.

 

Humidistat (optional) 

2.

 

Relay 

3.

 

Compressor 

4.

 

Fan 

5.

 

Defrost pilot light 

6.

 

Defrost solenoid valve 

7.

 

Temperature probe 

8.

 

General switch 

9.

 

Electronic card 

10.

 

Air flow 

11.

 

Evaporator 

12.

 

Condenser 

13.

 

Capillary 

14.

 

Hour counter (optional)  

Symbols used in the manual 

SYMBOL MEANING  DESCRIPTION 

 

Note 

Carefully follow the instructions and suggestions given. 

 

Attention ! 

Generic danger. Not keeping to the instructions could cause damage 
to the machine, people or things. 

Introduction 

The machines of the 

N

ADER 

Y

ARD PRO

 series are air dehumidifiers aimed at absorbing the humidity from the 

environment. They are equipped with a refrigeration circuit, loaded with ecological gas, 

R407c

, equipped 

with an electronic controlled defrost system. 

Operating principle (B) 

The machine uses a fan (4) to suck in the air (10) to be dehumidified and which is passed through the 
evaporator (11) of the refrigerator circuit. In this way, the air temperature is lowered below its dew point and 
the water vapour condenses into drops of water that are conveyed to the drain by means of the special tray. 
The degree of pollution of the water collected is proportional to the degree of environmental pollution. The 
air that is so dehumidified is passed through a condenser (12) that raises its temperature to a value that is 
slightly higher the initial temperature. In this way the amount of humidity contained in the environmental air 
is gradually reduced to the desired value. This also entails lowering the humidity in the walls and floor of 
the room, as well as in the materials contained in it. 

Hot gas defrosting (A,B) 

When the environmental temperature drops below 16°C ice may form on the evaporator coil (11). In the 
dehumidifiers of the 

N

ADER 

Y

ARD PRO

 series the defrosting cycle is automatic, and is controlled by a 

temperature probe (7) that detects the presence of ice on the evaporator coil (11). The defrosting phase is 
signalled by a yellow pilot light (5) lighting up on the control panel. During this phase the fan (4) is stopped 
and the solenoid valve (6) is opened: in this way the compressor sends the hot gas directly into the 
evaporation coil battery (11). The duration of the defrosting cycle depends on the environmental conditions 
and the amount of ice formed on the evaporator (11). 

Содержание Nader Yard Pro Series

Страница 1: ......

Страница 2: ...A A A A B B B B ...

Страница 3: ......

Страница 4: ......

Страница 5: ...nciple B 2 Hot gas defrosting A B 2 Installation rules 3 Condensate drain pipe 3 Positioning 3 Start up B 3 Humidistat optional 4 Maintenance 4 Cleaning the heat exchange coil battery 4 Storage 5 Check up to carry out before and after a long period of inactivity 5 Before 5 After 5 Disposal of the product 5 Technical Data 6 Dimensions and weight 6 ...

Страница 6: ...ps of water that are conveyed to the drain by means of the special tray The degree of pollution of the water collected is proportional to the degree of environmental pollution The air that is so dehumidified is passed through a condenser 12 that raises its temperature to a value that is slightly higher the initial temperature In this way the amount of humidity contained in the environmental air is...

Страница 7: ...f the machine Table 1 the room the dehumidifier is to be placed in must be closed the machine must always operate in a vertical position with the wheels facing downwards the dehumidifier must be placed in such a way as to leave the air inlet and outlet grids free at least 10 cm of air space make sure that the power supply voltage corresponds to that indicated in Table 1 and that the electric insta...

Страница 8: ...inal one Before carrying out any kind of work or repair on the machine set the general switch to position O and disconnect the power supply plug Cleaning the heat exchange coil battery To guarantee optimal operation of the dehumidifier it is important to always keep the evaporator 11 condenser 12 coil battery clean how often this is done depends on the environment in which the dehumidifier operate...

Страница 9: ...in a room with a temperature between 25 C and 55 C When the appliance is still packed keep to the instructions on the box Do not place other heavy material on the box Check up to carry out before and after a long period of inactivity Before Switch off the machine and disconnect the plug and empty the condensate collection tank cover the machine to protect it from dust After The fan must turn freel...

Страница 10: ...s 2 C 32 C Working limit relative humidity 35 100 Air Flow rate 236 L s 850 m ora Power supply voltage 230V 50Hz Current absorption 4 1A 4 8A Power absorption 885W 1050W R407c refrigerating gas charge 1050g Refrigerating circuit maximum pressure 2300kPa Noise level at 1 m distance 60dBA 25 C 65 U R 30 C 80 U R Table 1 Dimensions and weight 61 1 ...