background image

20

EXPERT WW   rev.12

EXPERT WW

6.2.  Fan Stages

6.2.1.  Principle of Operation

6.2.1.1.  Operation of Fan Stages

The controller has 12 fan stages which op-
erate in a sequence to increase the level of 
ventilation as the room temperature increases. 
Each stage can activate on/off outputs and a 
combination of timer relays for cooling pur-
poses. A fan stage is activated when the room 
temperature  reaches  its  start  temperature 
and is disabled when the room temperature 
decreases to its stop temperature.

Operating Diagram 

of Fan Stages

Room 

Set Point

Stage x Stop T°

Stg x

Stg y

Stage y Stop T°

Stage x Start T°

Stage y  Start T°

Ventilation 

Level

Start temperatures of fan stages are defined 
with respect to the set point and with respect 
to each other. This means that when one of 
these values is adjusted, all the consecutive 
values are adjusted by the same amount.  For 
example, if the set point is increased by 1°F,  
the start temperature of all fan stages will be 
increased by the same amount. 

Timer-based relays in fan stages

Fan stages can activate relays that operate 
following a timer (On and Off Times). This is 
useful to  activate misting units in timer mode 
while a specific fan stage is active. Refer to 
section 4.8 to enable timer-based relays. 

6.2.2.  Stage 1 Ramping

The controller can gradually increase (or de-
crease) the running time of the fans to smooth 
out the transition from the minimum ventila-
tion cycle to full operation of stage 1 fans.

Room

Temp.

Run

Time

OnTime 

=

Cycle 

Time

On 

Time 

Min. Vent.

Stage 1 Diff.

Stage 1 Ramping

 

At  room  temperatures  at  or  below  the  set 
point,  the  controller  operates  the  fans  of 
stage  1  according  to  the  minimum  ventila-
tion cycle.

If the room temperature rises above the set 
point, a new

 “On Time” 

is calculated periodi-

cally as the temperature increases to allow 
a smooth progression (from point A to point 
B) up to full operation of the fans when the 
set point + differential is reached (when the 

“Off Time”

 becomes less than 15 seconds, it 

is fixed at 15 seconds until the temperature 
has reached the set point + differential. At 
that point, the fans of stage 1 operate con-
tinuously).

If  the  room  temperature  decreases  0.3°F 
below  the  set  point  +  differential,  the

 “On 

Time” 

value of the minimum ventilation cycle 

decreases  gradually  from  a  value  equal  to 
the  total

 “Cycle Time” 

(point  C)  towards  the 

regular 

“On Time”

.

Ramping Settings: 

To use the ramping func-

tion, enable the 

“Ramping on stage 1” 

function in 

the Installation Setup (section 4.5) and adjust 
the differential of stage 1 in section 6.2.3.

6.2.3.  Fan Stage Settings

1.  

Select:

  Main menu 

  Start/Stop*
  Fan Stages

*  A password may be required to access this menu.

Fan Stage  Start / Stop

 

Use   to navigate

Stage 1 Start 

  70.0 

°F

        Stop 

  69.0 

°F

 

  Differential   2.0  °F

Stage 2 Start 

  72.0 

°F

        Stop 

  71.0 

°F

Stage 3 Start 

  74.0 

°F

        Stop 

  73.0 

°F

 

        On Time 

  0:15 

m:s

 

        Off Time 

  5:15 

m:s

Stage 4 Start 

  76.0 

°F

        Stop 

  75.0 

°F

Stage 5 Start 

  78.0 

°F

        Stop 

  77.0 

°F

2. Set the following parameters:

(Refer to the previous section to get further informa-

tion on these parameters)

Start & Stop temperatures —

 Set the start 

and stop  temperatures of each fan stage. 

The minimum difference between two 
consecutive  start  temperatures  is  of 
0.5 °F (0.3 °C). 

The  start  temperature  of  a  fan  stage 
must  be  greater  value  than  its  stop 
temperature.

Differential  —

  The  differential  is  the  tem-

perature difference between the moment the 
Stage 1 start running in timer mode (stage 1 
ramping) and the moment they run continu-
ously. Refer to the diagram in section 6.2.2. 
The  differential  can  be  adjusted  between 
1.0°F and 10.0°F (0.6°C and 5.6°C). *

This 

parameter  is  accessible  if  the  ramping  option  is 

enabled in the Installation Setup (section 4.5).

Timer —

 If timer-based relays are assigned to 

some fan stages (sec. 4.8), set the

 “On Time” 

and the

 “Off Time” 

of each timer-based relay. 

These 

“On & Off Times”

 can be adjusted from 

0 to 15 minutes in  increments of 15 seconds.

Содержание EXPERT WW

Страница 1: ...EXPERT WW Temperature controller User s Manual...

Страница 2: ...f this product is used in a manner not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is howev...

Страница 3: ...Operation 18 5 3 2 Settings 18 5 3 3 Modifying Curve Points 18 6 VENTILATION COOLING 19 6 1 Minimum Ventilation 19 6 1 1 Minimum Ventilation Cycles 19 6 1 2 Minimum Vent Settings 19 6 1 3 Minimum Ven...

Страница 4: ...l Age Count 41 12 5 Automatic Reminder 41 13 TECHNICAL SPECIFICATIONS 42 14 MEMORY CARD 43 14 1 Principle of Operation 43 14 2 Accessing the Transfer Menu 43 14 3 Configuration Transfer 43 14 3 1 Inst...

Страница 5: ...ontroller is located must always remain between 32 F and 104 F 0 C to 40 C Indoor use only To avoid exposing the controller to harmful gases or excessive humidity it is preferable to install it in a c...

Страница 6: ...y Menus History menus allow monitoring the sensor readings and verify the run time of some out puts The controller comes with the following histories menus Minimum maximum sensor readings Ambient temp...

Страница 7: ...ect the devices to the 0 10V outputs This type of output can be used to connect various devices such as heat mats or fans 3 USER INTERFACE 3 1 Location of the Controls Menu selectors Use these buttons...

Страница 8: ...natural ventilation curtain 2 is opening Close Solid LED natural ventilation curtain 2 is closing CURTAIN 1 Open Solid LED natural ventilation curtain 1 is opening Close Solid LED natural ventilation...

Страница 9: ...user 2 pass word is posted the prompt Change Password appears on screen Use the adjustment buttons to set the new password code 4 Use the adjustment buttons to confirm the new installer password then...

Страница 10: ...at are enabled in the Installation Setup are available see sec 4 5 The day number refers to the animal age 4 3 2 Copying Pasting Programs Use the copy paste function to duplicate all parameter setting...

Страница 11: ...of temperature 2 Potentiometer Pot The vent door inlet reaches predefined positions with the help of a potentiometer as a function of temperature Only the first vent door inlet output can use a potent...

Страница 12: ...able the proper type of panel RP 16 or RP 32 This parameter is common to all programs Use age based functions Some functions of the controller are based on the age of the ani mals temperature curve co...

Страница 13: ...probe Select the number of inside temperature probes that are connected to the controller 1 to 8 probes Inside relative humidity RH probe Select Yes if an indoor humidity probe is connected to the con...

Страница 14: ...ly outputs that are enabled in the Setup menu are available sec 4 5 1 2 3 4 5 6 7 8 9 10 TMR Fan Stage 6 Relay Assignment 2 Select a relay then set its status as fol lows The relay is assigned to the...

Страница 15: ...ers op erate according to the clean mode set point heaters turn on when the room temperature is lower than the clean mode set point Refer to section 5 1 to adjust the clean mode set point Low temperat...

Страница 16: ...te tempera ture changes and to verify the controller s performances When the test is enabled all outputs of the controller operate according to the simulated temperature 1 Select Main menu Setup Test...

Страница 17: ...oup starts being used Note that the 1st group automatically starts in minimum ventilation or at stage 1 if minimum ventilation is not used Also note that the controller automatically limits the stage...

Страница 18: ...sec 5 3 3 Status Select Yes to activate the curve Once the curve is on the controller auto matically adjusts the set point automatically between consecutive points of the curve for this reason curve...

Страница 19: ...ilation curve is composed of 10 steps and each step associates an On Time with an animal age Once the curve is enabled the controller changes On Time portion of the minimum ventilation cycles every ho...

Страница 20: ...oint A to point B up to full operation of the fans when the set point differential is reached when the Off Time becomes less than 15 seconds it is fixed at 15 seconds until the temperature has reached...

Страница 21: ...is enabled in the Installation Setup section 4 5 0 10V Output Ventilation Use to navigate Mode Automatic Current output 100 Start temp 70 0 F Min 40 Max 100 Max Output at 72 0 F Stop at 69 5 F 2 Set...

Страница 22: ...al ventilation is disabled when the aver age temperature decreases of 5 F 2 8 C below the curtain s closing temperature or when tunnel ventilation starts see graph below Transition from tunnel to natu...

Страница 23: ...he tunnel door operates according to the room temperature the door reaches the posi tion associated with the 1st tunnel stage when the controller enters in tunnel ventilation The controller then start...

Страница 24: ...by 4 for every 1 F 0 6 C in the compensation interval i e an interval of 3 F means a 12 increase The curtain s Off Time is decreased by the same amount Compensation interval Outside T Set Point Curre...

Страница 25: ...s linked with the activation of a user defined fan stage when the start temperature of that fan stage is reached the controller starts controlling tunnel doors according to the static pressure level I...

Страница 26: ...re is optional and can only be used if age based functions are enabled in the Installation Setup section 4 5 Minimum outside temperature A minimum outside temperature can be specified to avoid enterin...

Страница 27: ...ventilation see Installation Setup in section 4 5 Minimum outdoor temperature Select the outside temperature below which both tunnel doors remain closed Available if an outside temperature probe is en...

Страница 28: ...e points of ventilation stages are defined the user can specify the temperature at which vent doors inlets reach their over opening position Start T of the last stage over opening bandwidth Closing Ve...

Страница 29: ...u see section 4 11 Closed This is the position of the vent door inlet during the Off Time portion of minimum ventilation cycles Set this position to the desired value Stage x Assign a vent door inlet...

Страница 30: ...he vent door inlet closes according to the same cycle 6 5 2 2 Vent Door Settings 1 Select Main menu Vent Inlet Vent door Inlet 1 is already displayed This menu is accessible if at least one vent door...

Страница 31: ...sure level exceeds the high or low static pressure set point vent doors inlets wait for the end of the Wind Effect Delay before moving They will only move if the high or low pressure condition is stil...

Страница 32: ...Automatic Manual You can manually control the opening of a 0 10V output by using the manual control mode While this mode is used the control ler stops controlling the output and lets you choose the i...

Страница 33: ...ollowing parameters Temperature Select inside if the opera tion of cool cells is based on the inside tem perature select outside if it is based on the outside temperature On temperature Select the tem...

Страница 34: ...the set point changes 1 Select Main menu Start Stop Heaters Heaters Start Stop Use to navigate Heater 2 Lo fire On 71 0 F Off 73 0 F Hi fire On 70 0 F Off 73 0 F Heater 1 Lo fire On 73 0 F Off 75 0 F...

Страница 35: ...to stay lit all day long select No to use light cycles Maximum Intensity If the lights on 24 hours option is enabled above set the maxi mum light intensity to the desired value This parameter is acces...

Страница 36: ...PUTS The controller has 2 outputs to control various devices using the real time clock These clock output can use up to 12 timer cycles A clock output starts when the On Time of a timer is reached it...

Страница 37: ...dition a password may be required to access this menu section 4 2 RH Compensation Use to navigate RH Set Point 65 Heater Compensation Min On Time 15 sec Max On Time 45 sec Cycle Time 300 sec Mist on L...

Страница 38: ...ds an alarm when the temperature falls below low alarm limit that is associated to the clean mode The low alarm limit used in clean mode is re lated to the clean mode set point this means the alarm li...

Страница 39: ...mit Specify the maximum amount of water that can be consumed by each water meter per 15 minutes 1 10 000 gal or liters 15 min This parameter is accessible if a water meter is enabled sec 4 7 1 Static...

Страница 40: ...tside temperature probes for the past 75 days This parameter is accessible if an outside temperature sensor is enabled section 4 7 1 Inside relative humidity RH This menu contains the daily minimum an...

Страница 41: ...culled marketed At the beginning of a group the user must specify the initial number of animals Afterwards the user can specify the number of mortalities culled and marketed animals as it occurs ALL h...

Страница 42: ...input 4 20 mA Outside RH input 0 2 5Vdc Temperature inputs 1K 77 F 25 C NTC Relays 1 20 Dry contact 15 A RES 50 60 Hz 16 FLA 120 VAC 1HP 746 W 12 FLA 240 VAC 2HP 1490 W Max tungsten light bulb 8 3A 1...

Страница 43: ...component of the configuration without affecting the two other components For instance you can upload new controller software without affecting your calibration parameter settings 14 3 1 Installing a...

Страница 44: ...NEXT 3 Read the warning message carefully then press Next 4 Select the proper firmware file fir on the main screen The icon indicates which files can be used for the transfer FIRMWARE UPDATE Select Ex...

Страница 45: ...19 Settings 19 Set point curve Curve offset 18 Enable the curve function 12 Principle of operation 18 Settings 18 D Date 9 Day Night Activation 15 Day night times 15 Night set point Principle of oper...

Страница 46: ...s Current probe set in use 40 Principle of operation 26 Probe assignment 14 Settings 27 Programs Automatic program switch Activation 12 Settings 9 12 Copy paste program settings 10 Current program in...

Страница 47: ...ion 25 26 27 Probe set 2 27 Settings 27 Tunnel doors following natural curtains 11 Tunnel Natural vent transition 23 U Units 10 User password See Password V Vent door inlet potentiometer Activation 11...

Отзывы: