Maintenance

The GG-H2 was designed for long life and minimal 

maintenance. For proper operation it is essential 

that the test and calibration schedule be adhered to. 

Calibration Technologies recommends the following 

maintenance schedule.

Maintenance Guidelines:

•  The sensor is shipped with a factory calibration.  

Sensor should be calibrated 6 months from 

purchase date.

•  Calibrate the detector at least once every 6 months. 
• 

Calibration should be performed with certified 

calibration gas.  Calibration kits and replacement 

cylinders are available from Calibration 

Technologies.

•  In highly critical areas, a response test should be 

performed between calibrations to verify proper 

sensor response and alarm functions.  This can be 

done with calibration gas. The response test is not 

required if multiple electrochemical sensors are 

installed in the same room.

•  All tests and calibrations must be logged.
•  Always disconnect power at the controller before 

performing any wiring at the sensor.

Sensor Life: 

These electrochemical cells are extremely 

reliable, but several things can cause the cell chemicals 

to become depleted including:
•  a period of time
•  exposure to high temperatures
•  continuous, long term exposure to hydrogen

When the cell becomes depleted, the unit will give no 

indication of failure other than that the sensor will not 

respond.  For this reason it is 

absolutely essential 

that these sensors be calibrated on a regular basis .

 

When the cell becomes depleted, a replacement cell 

can be obtained from Calibration Technologies. Simply 

unplug the cell’s ribbon cable from the transmitter, 

pull the old cell from the spring clip, discard the old 

cell and replace it with a new one.  The sensor can 

be span calibrated after a 5 minute warm-up period, 

but best to wait 12 hours before zeroing due to 

acclimation.

Replacement cell order#: 

GG-H2-EC-RC

Содержание GG-H2-EC

Страница 1: ...Installation and Operation Manual GG H2 EC HYDROGEN GAS SENSOR...

Страница 2: ...nly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Страница 3: ...ies 920 N Trade Winds Pkwy Columbia MO 65201 866 394 5861 Sales ctiengineering com www ctiengineering com General description 4 Installation 4 Locating the sensor 4 Installation guidelines 5 Wiring 6...

Страница 4: ...atmospheric variations The transmitter circuit board is sealed in potting compound protecting sensitive electronic components and copper tracing from corrosion The specially vented chemical resistant...

Страница 5: ...p sensor and wire runs away from mercury vapor lights variable speed drives and radio repeaters Protect sensor from physical damage forklifts etc If mounting on a wall with studs the mounting screws s...

Страница 6: ...or insulated stranded shielded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot be made without a splice all splice connections s...

Страница 7: ...A Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 12 hours the unit can be zero calibrated by the following Be sure the...

Страница 8: ...Red Fault red LED On steady if supply voltage is less than 10VDC Status amber LED Blinks once per second if RFI is detected Power green LED On steady to Indicate Power Blinks once per second for 60 se...

Страница 9: ...nsors are installed in the same room All tests and calibrations must be logged Always disconnect power at the controller before performing any wiring at the sensor Sensor Life These electrochemical ce...

Страница 10: ...26 12 AWG torque 4 5 lbs in Power green LED Blinks once per second for 60 seconds during power up If supply voltage is too low 10VDC or improperly grounded will blink once per second continuously Sta...

Страница 11: ...ir of the product by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a pro...

Страница 12: ...ctiengineering com 866 394 5861 GG H2 EC DOC1 0 20171207...

Отзывы: