background image

17

Note: 

When collecting waveform data from the BNC jack on the signal 

conditioner using a portable data collector that supplies constant current power, 

it is recommended that the data collector is configured so that power to the 

sensor is turned off . Although the BNC connector circuitry offers short circuit 

protection and can safely sink the current, long-term degradation may occur due 

to increased power dissipation depending on the magnitude of the IEPE current . 

There is no need for the data collector sensor power to be turned on for the data 

collection to be made, and it is the safest way to make measurements if possible .

Troubleshooting

Signal Conditioner Configuration 

Refer to the 

SC310

 and 

SC320

 Series Signal Conditioner Product Manuals 

for configuration specifications and procedure for SC310 and SC320 signal 

conditioners . 
Once all wires are connected, apply power to begin operating the signal 

conditioner(s) . Make sure the status light is indicating normal mode on each 

SC300 . 

Operating Procedure

To operate the signal conditioners inside the enclosure, make sure that all wires 

are properly connected, and then apply power . 

Caution:

 Make sure that power input does not exceed specified limits or damage 

to the system may result . See Table 1 .

Calibration

The signal conditioner is calibrated internally during startup . The digital calibration 

eliminates the need for any adjustments to the Analog Output .

Indicators

The LED on the front of the signal conditioner will indicate the status of the signal 

conditioner .

State 1

 - Normal Operation

• 

LED is solid green

State 2

 - Input Short Detected

• 

LED is rapidly flashing red

Содержание SCE400 Series

Страница 1: ...SCE400 Series Signal Conditioner Enclosure SCE400 Series Signal Conditioner Enclosure 8 Sensor Inputs 8 Sensor Inputs Product Manual Product Manual...

Страница 2: ...tion 3 Product Description 3 Product Dimensions and Diagram 4 Mounting Instructions 5 Conduit Entry 6 Grounding 7 Electrical Connections 9 Troubleshooting 12 Warranty and Return Information 15 Table o...

Страница 3: ...terminal blocks for integration into PLC DCS systems Each signal conditioner utilizes screw terminals for the various input output options such as 20 to 32 Vdc power input signal output 1 2 configurab...

Страница 4: ...4 14 25 in 362 0 mm 12 00 in 304 8 mm 17 50 in 444 5 mm 16 53 in 420 0 mm 9 23 in 234 3 mm Product Dimensions Figure 1 Dimensions Figure 2 Diagram Side View Front View...

Страница 5: ...ncluded Note If you have purchased a SCE400 Series enclosure without cable entries provided you should add your own entry prior to mounting the enclosure CTC does not recommend putting holes in the to...

Страница 6: ...is located at the bottom of the enclosure when mounted Note To ensure moisture will not flow into the enclosure a hole should be drilled at the lowest point in the conduit to provide drainage for any...

Страница 7: ...ies enclosure is grounded to earth ground A Mounting to Earth Ground When mounting SCE400 Series enclosures to earth ground such as an I Beam no additional steps are necessary as the enclosure is grou...

Страница 8: ...Grounded Structure When mounting the SCE400 Series enclosure to a non grounded structure ensure the shield ground wire or customer supplied ground wire is tied to a source of earth ground Figure 6 Gr...

Страница 9: ...d grips one per channel output wiring is routed through a conduit fitting 110 Vac is needed to power the unit through the terminal on the right side of the enclosure A in conduit fitting is provided f...

Страница 10: ...res to be equipped with a power supply and circuit breaker Below is the wiring configuration to bring live power into the enclosure Cable Cable Color Destination Ground Green Ground lug beneath the po...

Страница 11: ...nected to terminal blocks within the enclosure Sensor inputs for the SCE400 series are located on the right side of the enclosure as indicated by the interior labeling Sensor Input Input for Vibration...

Страница 12: ...corresponding transmitter for that channel will not power on Be sure to power the system on AFTER the sensor has been connected Signal Conditioner Terminal Block Position Four Pole Terminal Block Posi...

Страница 13: ...eft side of the enclosure as indicated by the interior labeling Output SCE411 Signal Conditioners with Single Vibration Band Output Signal Conditioner Terminal Block Position Four Pole Terminal Block...

Страница 14: ...rs with Single Vibration Band and Temperature Outputs Signal Conditioner Terminal Block Position Four Pole Terminal Block Position Cable Color Destination 11 1 Red Channel 1 Output 12 2 Black Common 1...

Страница 15: ...Conditioners with Dual Vibration Band Output Signal Conditioner Terminal Block Position Four Pole Terminal Block Position Cable Color Destination 11 1 Red Channel 1 Output 12 2 Black Common 7 3 Blue...

Страница 16: ...Vibration Band and Temperature Outputs Signal Conditioner Terminal Block Position Four Pole Terminal Block Position Cable Color Destination 11 1 Red Channel 1 Output 12 2 Black Common 7 3 Blue Channe...

Страница 17: ...Series Signal Conditioner Product Manuals for configuration specifications and procedure for SC310 and SC320 signal conditioners Once all wires are connected apply power to begin operating the signal...

Страница 18: ...correct output wiring e g an open circuit detected on a current output or a short circuit detected on a voltage output or corrupted configuration memory The device will still be processing input data...

Страница 19: ...ause the device to enter this state Regular operation will not occur while the USB cable is plugged in State 7 Bootloader LED is flashing between red and green This state occurs during device startup...

Страница 20: ...products qualify for free cancellation if your order is cancelled within 24 hours of purchase Built to order products qualify for a 50 refund if returned in new condition within 90 days of shipment C...

Отзывы: