General information
!
To low adjusted values
might imply that the re-
quired indoor tempera-
ture is not being reached.
Then you have to adjust
the heating curve accord-
ing to need.
Suitable standard values
At the time of the installation it is seldom possible to instantly set the heating curve
exactly . The values to the right may then be a good starting-point before the more ac-
curate adjustment is set.
Radiators with small heat emission surfaces require higher primary flow temperatures.
Menu:
Installer/Settings/Setting house paramt ----->Inclination
Floor heating only
Inclination 35
Low temperature system
(well insulated house)
Inclination 40
Standard temperature system
(older house)
Inclination 50
High temperature system
(older house, small radiators, poorly insulated)
Inclination 60
Adjustment (if the outdoor temperature is lower than 0 degrees)
◗
At too
cold
indoors:
Increase
the value at
Inclination
a couple of degrees.
Wait one day before the next adjustment.
◗
At too
warm
indoors:
Decrease
the value at
Inclination
a couple of degrees. Wait one day before the next adjustment.
Adjustment (if the outdoor temperature is higher than 0 degrees)
◗
At too
cold
indoors:
Increase
the value at
Adjustment
a couple of degrees.
Wait one day before the next adjustment.
◗
At too
warm
indoors:
Decrease
the value at
Adjustment
a couple of degrees. Wait one day before the next adjustment.
!
When the standrad
values are fairly correct
adjusted, the curve can
be displaced directly in
the normal display menu
Indoor°C.