Vecto
III
User Manual
36
Terminal
Legend
Description
1.
V
1
Phase 1
2.
V
2
Phase 2
3.
V
3
Phase 3
4.
V
com
Reference for V
1-3
5.
V
4+
Phase 4
6.
V
4-
Reference for V
4
Table 2: Voltage connection layout
Input voltages can be up to 600 V
AC-RMS
. The 20 mV resolution results in accurate
recording of all harmonic components up to the 63
rd
harmonic component.
A high impedance input prevents the accidental shorting of VT inputs to system ground
and also eliminates ground loops.
Differential resistive inputs assure a safe and stable analog input stage with minimal
phase error, a high bandwidth and zero temperature drift.
2.4.5
Current Inputs
The Vecto III has 4 galvanically isolated resistive current shunt inputs with input
impedance of 20 m
and a full-scale measurement range of 6 A
AC-RMS
.
Resistive shunts provide excellent AC and DC response; zero offset drift and very low
temperature drift.
The 3-second overcurrent withstand rating of each input is 50 A. The galvanic isolation
voltage between each channel and earth is 1 kV.
The current inputs are by an 8-terminal lockable connector plug with screw terminals.
Each terminal can accommodate conductors with size up to 2.5 mm
2
.
Содержание Vecto III
Страница 35: ...Vecto III User Manual 35 Figure 9 Vecto III 4 wire star connection Figure 10 Vecto III 3 wire delta connection...
Страница 63: ...Vecto III User Manual 63 Figure 33 CT circuit connection layout...
Страница 70: ...Vecto III User Manual 70 Appendices 1 Vecto III dimensions...
Страница 71: ...Vecto III User Manual 71 2 Vecto III wiring diagram...
Страница 72: ...Vecto III User Manual 72 3 Vecto III Top View...
Страница 74: ...Vecto III User Manual 74 2964 2197 2569 3541...
Страница 76: ...Vecto III User Manual 76 2964 2197 2569 3541 1084...
Страница 78: ...Vecto III User Manual 78 2934 1084 3539 2431 2951 2487 2964 2535 2486 2571 2488 2344 2346 2600...