Drill two holes sized for #8 screws to mount the mullion plate.
4.
Run the shielded, dual twisted-pair cable from the controlling DPU to the mullion
plate cutout. The cable may extend for up to 200 feet (60 m).
5.
Connect the shielded, dual twisted-pair cable as shown in
6.
Insert the mullion plate into the cutout and secure to the wall using security
mounting screws provided with the reader or with separately purchased #8 screws.
Note:
If using the security screws to mount the mullion plate, you must purchase a separate tool
(CSI TRDRTOOL) to secure the screws. Otherwise, use any hardware to install the I/DISC
reader.
I/DISC Field Output Installation
The LED and sensor pigtails connect to a 24 AWG (0.206 mm
2
), shielded, dual twisted-
pair cable that goes to the DPU. The cable connects to the DPU in one of the following
ways:
✦
When connecting the I/DISC reader to a DPU-7910A series controller, the cable
from the reader connects to a CSI breakout box (BRKBOX2). The breakout box
then connects to the DPU reader ports (1A, 2A, 1B, or 2B) using an RJ45 CSI
modular reader cable (CBL063).
✦
When connecting the I/DISC reader to a DPU-7920 series controller, the cable
from the reader can be connected directly to TB3 or TB4 on the DPU.
With I/NET versions 4.3x and later, the DPU-7920 series controllers also support the
combination of an I/DISC reader along with an ESSEX PIN pad. Installation instructions
for this configuration are described following the basic I/DISC installation instructions.
Figure 14. I/DISC Cable Connection
LED
Probe
RED
GRN
BLK
BLK
GRY
A1
A2
B1
B2
Shielded,
200 Feet (60 m) maximum
Dual Twisted-pair Cable
24 AWG (0.206 mm
2
)