Setup and Operation
16
Setting the Tap Baud Rate
Note:
The “Tap speed” function is accessed from the second DCU setup screen. Press “PgDn” from
the initial DCU setup screen to display the second screen.
1.
Select “Tap speed” from the second DCU setup screen to set the Tap baud rate.
2.
Press the +/– keys to toggle through the available PC port baud rates.
3.
Press “Done” to accept your choice.
Setting the Controller LAN Baud Rate
Note:
All devices on the LAN must be communicating at the same baud rate. The typical LAN
baud rate is 19200. Only use 9600 baud if you experience problems with data throughput.
1.
Select “Network speed” from the second DCU setup screen.
2.
Press the +/– keys to toggle between 9600 baud and 19.2 Kbaud rates.
3.
Press “Done” to accept your choice.
Modem Switch Settings
Integrated Dial (7801 Tap Emulation)
You must configure the modems attached at the call initiating end (host PC) and the call
receiving end (I/SITE LAN) so that they will communicate with each other. For modems
without switch settings, a terminal emulator and software, such as Procomm, or the
communication software received with your modem, must be used to issue command
strings to the modem for proper initialization.
Call Initiating End
Use the following DIP switch settings or software controlled switch settings to initialize
your modem.
A Hayes 1200 baud modem, or compatible, connected to the PC at the call initiating end
must have switches 1, 6, 7, 9, and 10 up.
For a Hayes 2400 baud SmartModem, or compatible, issue the following settings from a
terminal emulator. Use the steps shown below.
1.
AT & F
[Enter]
2.
AT E0 V0 X1 & C1 & D2 S7=60
[Enter]
3.
AT & W0
[Enter]
4.
Cycle power on the modem to store the setup commands of the user’s profile to the
modem’s NOVRAM.
For a Hayes Optima series SmartModem, or compatible, issue the following settings
from a terminal emulator. Use the steps shown below.
1.
AT&F
[Enter]
2.
AT E0 V0 N0 X0 & C1 & D2 & K0 & Q0 S7=60 (and S37=0 only for Optima 9600)
[Enter]