Safety Warnings Continued
Non-Compliance
Failure to install or maintain this heater properly will void the war
-
ranty.
Check the heater for any damage that may have occurred in shipment!
If damage is found, file a claim with the transport company. Your unit was
inspected and tested at the factory prior to crating and was in perfect
condition at that time. Open the boxes and verify receipt of all parts.
To protect the unit during shipping, the blower model (RAD) has special
supports that must be removed before installation.
• Blower support legs - Remove the four blower support legs and
screws.
• Check Belt Tension - Belt should be able to be depressed 1/2”
- 3/4” (See illustration below.) If the belt does not have proper
tension, adjust by means of the adjusting screw on the motor
base. After proper tension is achieved, tighten the lock nut on the
adjusting screw.
• Replace the belt guard.
WARNING: Care should be exercised to ensure that
an adequate supply of combustion air is available
and free to enter the air openings on all units. Room
openings must equal one square inch per each 1,000
BTU heat input.
Air for Combus-
tion
Fan Models (RA) use plastic cable ties to support the fan motors during
shipment. Cut and remove prior to installation.
Unpacking and
Inspection
Содержание RA 350
Страница 48: ...Form I RA D 350 500 Page 48 Wiring Diagram 147351 for Models RA RAD 350 Appendix...
Страница 49: ...Form I RA D 350 500 P N 131090R12 Page 49...
Страница 51: ...Form I RA D 350 500 P N 131090R12 Page 51...
Страница 53: ...Form I RA D 350 500 P N 131090R12 Page 53...
Страница 55: ...Form I RA D 350 500 P N 131090R12 Page 55...
Страница 57: ...Form I RA D 350 500 P N 131090R12 Page 57...