Crundfos BMQ 1 Скачать руководство пользователя страница 7

7

The required voltage for GRUNDFOS submersible 
motors, measured at the motor terminals, is 
–10%/+6% of the nominal voltage during continuous 
operation (including variation in the supply voltage 
and losses in cables).

If the booster module is connected to an electric 
installation where an earth-leakage circuit breaker 
(ELCB) is used as an additional protection, this cir-
cuit breaker must trip out when earth fault currents 
with DC content (pulsating DC) occur.
The earth leakage circuit breaker must be marked 
with the following symbol: 

.

Supply voltage: 

1 x 200-240 V –10%/+6%, 50/60 Hz, PE.
1 x 110-115 V –10%/+6%, 50/60 Hz, PE.

The current consumption can only be measured by 
means of a true RMS instrument. If other instruments 
are used, the value measured will differ from the 
actual value.

The BMQE-NE booster modules can be connected 
to a control box, type CU 300. 

Note: The booster module must never be connected 
to a capacitor or to another type of control box than 
CU 300. 
The booster module must never be connected to an 
external frequency converter.

6.1 Motor protection 

The motor incorporates thermal overload protection 
and requires no additional motor protection. 

6.2 Connection of motor

The motor incorporates a starter device and can 
therefore be connected directly to the mains. 

7. Liquid filling and module venting

The booster module(s) is/are filled with water/liquid 
through the suction port of module 1, see fig. 3. 

1. Slacken the air vent screw in the booster module. 

2. Inject water/liquid until it starts running out of the 

vent hole.

3. Tighten the air vent screw.

8. Operation

The booster modules must be started in the order 
1-2-3-4 at intervals of 1 or 2 seconds. 

The modules must be stopped in reverse order, i.e. 
4-3-2-1, at the same intervals. 

Module 1 is always the first module on the suction 
side. 

The start/stop intervals stated will reduce water ham-
mering in the system. 

If water hammering is a problem in the modules dur-
ing stopping, it is recommended to install a dia-
phragm tank. 

During operation, it must be checked that the inlet 
pressure is as estimated.

When not being used, all modules should be filled 
with water as all internal bearings are water lubri-
cated.

If the booster unit is taken out of operation for a long 
period, the modules should be flushed through with 
clean water. The modules are then left with clean 
water until they are to be used again.

The total pressure and flow of modules connected in 
series should never be changed by stopping one or 
more of the modules. If different pressures or flows 
are required, it is recommended to proceed as fol-
lows:

a)  In the case of GRUNDFOS BMQ or BMQE-NE 

booster modules installed in accordance with fig. 
6, fit a bypass between two modules.
Stop the module(s) which is/are not required and 
close the isolating valves on either side of the 
module. 
If the module(s) taken out of operation will not be 
used for long periods, it is recommended to flush 
this/these module(s) through with clean water. 
If a module is taken out of operation as de-
scribed, it should always be the last one in the 
series. 

b)  When a pressure reducing valve or a pressure 

relief valve is fitted to the discharge pipe, the fol-
lowing minimum flows must be ensured at all 
times:
• at 40°C: 0.8 m³/h (104°F: 3.5 US GPM).
• at 25°C: 0.5 m³/h (77°F: 2.2 US GPM).
Please note that the minimum flows stated do not 
ensure optimum conditions and should be avoid-
ed, see section 8.1 Limitations to operation
Furthermore, the operating pressure and the 
maximum inlet pressure in sleeves must not ex-
ceed the values stated in section 8.1 Limitations 
to operation

If there is any danger of the modules running 
against a closed discharge valve, a minimum liq-
uid flow through the pump should be ensured 
(see above). 
Furthermore, the liquid temperature must not ex-
ceed the values stated in section 8.1 Limitations 
to operation.
 

If a module of a booster unit in series in a system 
with two or more series connected in parallel without 
bypass fails, the whole booster unit in question must 
be switched off, because all modules connected in 
series must develop the same pressure. Otherwise, 
the module that develops a too low pressure will stop 
and the next motors in the series will burn because 
of insufficient cooling.

The booster module is not allowed to run 
against a closed discharge valve as this 
will cause an increase in temperature/for-
mation of steam in the pump which may 
cause damage to the pump and the motor. 

If there is any danger of the module run-
ning against a closed discharge valve, a 
minimum liquid flow through the pump 
should be ensured by connecting a by-
pass/a drain to the discharge pipe. The 
drain can for instance be connected to a 
tank.

Содержание BMQ 1

Страница 1: ...BMQ BMQE NE Installation and operating instructions Montage und Betriebsanleitung Monterings og driftsinstruktion TM01 7415 4599 ...

Страница 2: ...htsvorschriften der EG Mitgliedstaaten übereinstim men Maschinen 98 37 EWG Norm die verwendet wurde EN 292 Elektromagnetische Verträglichkeit 89 336 EWG Normen die verwendet wurden EN 55 014 und EN 55 014 2 Elektrische Betriebsmittel zur Verwendung innerhalb bestimmter Spannungs grenzen 73 23 EWG Normen die verwendet wurden EN 60 335 1 und EN 60 335 2 41 Overensstemmelseserklæring Vi GRUNDFOS erkl...

Страница 3: ...3 BMQ BMQE NE Installation and operating instructions Page 4 Montage und Betriebsanleitung Seite 11 Monterings og driftsinstruktion Side 20 ...

Страница 4: ...designed for pumping thin clean non aggressive non explosive liquids not containing solid particles or fibres The liquid must not attack the pump materials chem ically or mechanically BMQE NE The booster module is designed for pumping thin clean non explosive liquids not containing solid par ticles or fibres These booster modules are suitable for pumping contaminated or hydrogen carbonate containi...

Страница 5: ...requency details given on the nameplate should be compared with the ac tual electricity supply available Versions BMQ BMQE NE Fig 1 5 Installation The GRUNDFOS booster modules BMQ and BMQE NE are supplied without built in non return valve An arrow on the module sleeve shows the direction of flow of liquid through the module fig 1 The booster modules are suitable for both vertical and horizontal in...

Страница 6: ...booster unit Fig 6 Booster unit with four modules connected in series with bypass mounted above each other Note In the case of constant pressure control of BMQE NE modules connected in series it is recom mended to control the last controllable module in the booster unit All modules are supplied without non return valve Booster modules connected in parallel may also be installed vertically Note As ...

Страница 7: ...riod the modules should be flushed through with clean water The modules are then left with clean water until they are to be used again The total pressure and flow of modules connected in series should never be changed by stopping one or more of the modules If different pressures or flows are required it is recommended to proceed as fol lows a In the case of GRUNDFOS BMQ or BMQE NE booster modules ...

Страница 8: ...on If any of the above checks reveal any abnormal operating details inspection should be carried out in accordance with the fault finding chart in section 11 10 Service For the replacement and repair of parts of the booster unit please refer to 1 Service manual for SQ SQE describing replace ment of motor cable and motor 2 Parts list for SQ SQE with instructions for dis mantling and assembly of pum...

Страница 9: ... circuit breaker c No electricity supply Contact the electricity supply authorities d The motor protection has cut off the electricity supply due to over load Check whether the motor pump is blocked e The pump cable is defective Repair replace the pump cable f Overvoltage has occurred Check the electricity supply 2 The booster module runs but gives no water a The discharge valve is closed Open the...

Страница 10: ...test Resistance test Hight voltage test 1 Supply voltage TM00 1371 5092 Measure the voltage RMS between phase and neutral Connect the voltmeter to the terminals at the connection The voltage should when the motor is loaded be within the range specified in sec tion 6 Electrical connection Large variations in supply voltage indicate poor electricity supply and the booster module should be stopped un...

Страница 11: ...nweise aufgeführten allgemeinen Sicher heitshinweise zu beachten sondern auch die unter den anderen Abschnitten eingefügten speziellen Sicherheitshinweise 1 2 Kennzeichnung von Hinweisen Direkt an der Anlage angebrachte Hinweise wie z B Drehrichtungspfeil Kennzeichnung für Fluidanschlüsse müssen unbedingt beachtet und in vollständig lesba rem Zustand gehalten werden 1 3 Personalqualifikation und s...

Страница 12: ...ung ent sprechend Abschnitt 3 Verwendungszweck der Montage und Betriebsanleitung gewährleistet Die in den technischen Daten angegebenen Grenzwerte dürfen auf keinen Fall überschritten werden 2 Lieferung und Transport GRUNDFOS 3 Druckmodule BMQ und BMQE NE werden installationsfertig in Kartons geliefert in de nen sie bis zur Montage verbleiben sollten 3 Verwendungszweck Die GRUNDFOS Druckmodule sin...

Страница 13: ... den Grenzwerten die in der EG Richtlinie 89 392 EWG für Maschinen angeführt sind 5 Montagevorbereitung Vor der Montage sind die folgenden Punkte zu prü fen 1 Pumpentyp Auf dem Druckmantel befindet sich ein Lei stungsschild auf dem die Daten der Pumpe ein gestempelt sind Prüfen ob sie mit denen des Auftrages übereinstimmen 2 Stromversorgung Prüfen ob die auf dem Leistungsschild angege benen elektr...

Страница 14: ...ach Abb 6 empfohlen Abb 3 Reihen Einheit mit vier in Reihe geschalte ten Modulen übereinander angeordnet Abb 4 Parallel Einheit mit vier parallelgeschalteten Modulen übereinander angeordnet Abb 5 Reihen Parallel Einheit mit jeweils zwei in Reihe und parallel geschalteten Modulen übereinander angeordnet Abb 6 Reihen Einheit mit vier hintereinander in Reihe geschalteten Modulen mit Bypass übereinand...

Страница 15: ...duls lösen 2 Wasser Flüssigkeit einfüllen bis es sie aus der Entlüftungsöffnung austritt 3 Entlüftungsschraube anziehen 9 Betrieb Beim Einschalten sind die Druckmodule in der Rei henfolge 1 2 3 4 im Abstand von 3 oder 5 Sek ein zuschalten Das Ausschalten ist in umgekehrter Reihenfolge 4 3 2 1 mit denselben Zeitabständen durchzufüh ren Modul 1 ist immer das erste Modul auf der Saugsei te Durch dies...

Страница 16: ...n Förderdruck haben müssen Anderen falls bringen die Pumpengruppen die einen zu gerin gen Druck erzeugen zu wenig Pumpenleistung und die Statoren der Antriebsmotoren verbrennen auf Grund mangelhafter Kühlung 9 1 Betriebsgrenzen Der Förderstrom und der Förderdruck der Druckmo dule sollten stets in den empfohlenen Bereichen des jeweiligen Druckmoduls liegen Achtung Falls der maximal zulässige Zulauf...

Страница 17: ...wird das Druckmodul als kontaminiert klas sifiziert Bei eventueller Serviceanforderung muß unbedingt vor dem Versand des Druckmoduls mit GRUNDFOS Kontakt aufgenommen werden Informationen über Fördermedium usw müssen vorliegen da sonst GRUNDFOS die Annahme des Druckmoduls verwei gern kann BMQE NE Druckmodule die nicht kontaminierte Flüssigkeiten gefördert haben können zur Wartung an GRUNDFOS zurück...

Страница 18: ...ie hen und reinigen auswechseln 3 Das Druckmodul läuft mit verringer ter Leistung a Die Ventile in der Druckleitung sind teilweise geschlossen blockiert Ventile überholen und evtl reinigen auswechseln b Die Druckleitung ist durch Verun reinigungen teilweise zugesetzt Druckleitung reinigen auswechseln c Die Pumpe ist durch Verunreini gungen teilweise zugesetzt Pumpe aus dem Druckmantel herauszie he...

Страница 19: ...ng Widerstands prüfung Hochspan nungsprüfung Achtung 1 Netzspannung TM00 1371 5092 Spannung zwischen Phase und Nulleiter Effektiv Meßge rät messen Voltmeter mit den Klemmen an der Anschlußstel le verbinden Die anliegende Spannung während des Be triebes darf nicht von dem im Abschnitt 7 Elektrischer Anschluß angegebenen Spannungsbereich abweichen Große Spannungsschwankungen deuten auf eine schlecht...

Страница 20: ...ve ikke eksplosive medier uden indhold af faste bestanddele eller fibre Mediet må ikke kemisk eller mekanisk angribe de materialer der indgår i pumpen BMQE NE Boostermodulet anvendes til pumpning af rene tyndt flydende ikke eksplosive medier uden indhold af faste bestanddele eller fibre Disse boostermoduler må anvendes til pumpning af forurenet vand med indhold af hydrogenkarbonat fra f eks lossep...

Страница 21: ...get kontraventil En pil på modulets kappe angiver strømningsretnin gen gennem modulet fig 1 Boostermodulet er egnet til såvel vertikal som hori sontal installation dog må trykstudsen ikke komme under det horisontale plan se fig 2 Fig 2 5 1 Moduler forbundet i serie og parallelt 1 For moduler som er forbundet i serie monteret oven over hinanden anbefales det at tilslutte rø rene som vist i fig 3 2 ...

Страница 22: ... i boosterenheden Alle moduler leveres uden kontraventil Boostermoduler der er forbundet parallelt kan også installeres vertikalt Bemærk Da der kan opstå udluftningsproblemer i sådanne anlæg anbefales det at installere egnede udluftningsanordninger 6 El tilslutning El tilslutning skal foretages af en autoriseret el installatør i overensstemmelse med de lokalt gæl dende regler Forsyningsspænding på...

Страница 23: ...ære fyldt med vand indtil de igen tages i brug Samlet afgangstryk og flow for moduler der er for bundet i serie må ikke ændres ved at stoppe et eller flere moduler Hvis der ønskes et andet afgangstryk eller et andet flow anbefales følgende fremgangs måde a Når GRUNDFOS BMQ eller BMQE NE booster moduler er installeret som vist i fig 6 monteres et bypass mellem to moduler Stop det de modul er der ik...

Страница 24: ...under drift Konstateres der afvigelser fra normale driftsdata foretages eftersyn i henhold til fejlfindingsskemaet i afsnit 11 10 Service Vedrørende udskiftning og reparation af dele i boosterenheden henvises til følgende 1 Servicemanual for SQ SQE vedrørende udskift ning af motorkabel og motor 2 Delliste for SQ SQE med vejledning i demonte ring og montering af pumpe og motor 3 Anvendes en SQ stan...

Страница 25: ...relæ eller fejl spændingsafbryder er udkoblet Indkobl relæet eller afbryderen c Ingen elektricitetsforsyning Kontakt el selskabet d Motorbeskyttelsen er udløst på grund af overbelastning Kontrollér om motor pumpe er blokeret e Pumpe kabel er defekt Reparér udskift pumpe kabel f Der forekommer overspænding Kontrollér forsyningsspændingen 2 Boostermodulet kører men giver ikke vand a Afgangsventilen ...

Страница 26: ...rensstem melse med bekendtgørelse 1067 af 22 12 98 TM01 2072 1098 M V Isolations test Modstands test Højspændings test 1 Netspænding TM00 1371 5092 Mål spændingen RMS mel lem fase og nul Tilslut voltme teret til klemmerne ved tilslut ningsstedet Spændingen skal ved belastning ligge inden for intervallet som er angivet i afsnit 6 El tilslutning Stor variation i netspændingen er tegn på dårlig elekt...

Страница 27: ...M01 7297 4299 0 5 10 15 20 25 30 35 40 45 50 C 0 1 2 3 4 5 6 7 8 9 p bar 0 5 dH 5 10 dH 10 15 dH 15 20 dH 20 25 dH 25 30 dH 30 35 dH 35 40 dH 32 40 48 56 64 72 80 88 96 104 112 120 F 0 20 40 60 80 100 120 p p s i ...

Страница 28: ...no Tel 39 02 95838112 95838212 Telefax 39 02 95309290 95838461 Japan GRUNDFOS Pumps K K 1 2 3 Shin Miyakoda Hamamatsu City Shizuoka pref 431 21 Phone 81 53 428 4760 Telefax 81 53 484 1014 Korea GRUNDFOS Pumps Korea Ltd 2nd Fl Dong Shin Building 994 3 Daechi dong Kangnam Ku Seoul 135 280 Phone 82 2 5317 600 Telefax 82 2 5633 725 Malaysia GRUNDFOS Pumps Sdn Bhd 7 Jalan Peguam U1 25 Glenmarie Industr...

Отзывы: