background image

All installations and services must be performed by qualified service personnel.

 

APPENDIX-A Replacement Parts List 

11 

 

Содержание CSHB60-90XE

Страница 1: ...alteration service or maintenance can cause a fire or explosion resulting in property damage personal injury or loss of life For assistance or additional information consult a qualified installer or...

Страница 2: ...ry substantial property damage or death See Page 5 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 8 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 9 cWAR...

Страница 3: ...R CONDITIONING 4 D FILTERS MOUNTED EXTERNAL TO FURNACE 4 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 6 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANING INSTRUCTIONS 8 III...

Страница 4: ...rotected to avoid physical damage by vehicles cWARNING This furnace is not to be used as a construction heater 5 Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MATERIAL COMBU...

Страница 5: ...oil furnaces If a power venter must be used it is the responsibility of the installer and power venter manufacturer to design and assemble a satisfactory power vent system A VENTING NOTE On the CSHB6...

Страница 6: ...n air inlet pipe diameter is also 4 inch diameter For Riello the combustion air inlet pipe will be reduced to 3 inch diameter with the included Riello side wall vent kit For Beckett the combustion air...

Страница 7: ...t dampers or other means used to control flow of air should be provided to prevent chilled air from entering the furnace If such a damper is manually operated it must be equipped with a means to preve...

Страница 8: ...k can be anchored to the furnace with screws or pop rivets through the securing flange of the filter rack Connect the return air plenum to the filter rack and slide the filter into place Dimensions fo...

Страница 9: ...he chamber during shipping and helps to maintain insertion depth DO NOT remove this retainer when installing burner Fig 4 Typical location of the overfire air tap and components in burner mounting pla...

Страница 10: ...RATED AT 0 65 GPH 100 PSIG THAT PROVIDES AN 80 SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 A For more specific burner information contact Crown Boiler Co P O...

Страница 11: ...th access to the inside of the heat exchanger through the burner area clean out openings and vent pipe connection it is possible to use a long flexible wire brush and an industrial type vacuum cleaner...

Страница 12: ...oloration of materials and damage from rust or corrosion FLUE PIPE VENT PIPE OR CONNECTOR The furnace vent pipe should be inspected for signs of rust corrosion pitting or holes in pipe and leakage aro...

Страница 13: ...em and home cWARNING To avoid injury from moving parts hot surfaces or electrical shock shut off the power to the furnace before removing any furnace access doors to service the air filters The filter...

Страница 14: ...All installations and services must be performed by qualified service personnel APPENDIX A Replacement Parts List 11...

Страница 15: ...All installations and services must be performed by qualified service personnel APPENDIX B Wiring Diagrams BLOWER SPEED TAPS COOL A C Tap HEAT Heating Tap LOW Constant air or Dehumifier 12...

Страница 16: ...All installations and services must be performed by qualified service personnel All installations and services must be performed by qualified service personnel 13 13...

Отзывы: