All installations and services must be performed by qualified service personnel.

 

G. BURNER SPECIFICATIONS AND APPLICATIONS 

 

FURNACE MODEL 
CSHB60-90  
 
BURNER 

BURNER 
SPEC 
NO.  


INS 

BURNER 
MODEL & TUBE 
LENGTH 

HEAD STATIC 

PLATE 

MAXIMUM
NOZZLE 
SIZE** 

SHIPPED 
NOZZLE 
SIZE   

OIL 
PUMP 
PRESSURE 
(PSIG) 

BECKETT (AFG) 

130200S 

AFG-4.5” 

F4 

3-3/8 

0.75X80

°

 A 

0.60X80

°

 A 

120 

BECKETT (NX) 

130201S 

NX-4.5” 

N/A 

N/A 

0.60X70

°

 A 

0.50X70

°

 A 

150 

CARLIN 130210S 

EZ-1 HP/ 4.5”

 

77958 N/A  0.75X70

°

 A 

0.60X70

°

 A 

150 

RIELLO 130220S 

BF3-4.5” 

N/A 

N/A 

0.70X80

°

 A 

0.60X80

°

 A 

145 

 
* INSULATOR   S = SLEEVE    OR    N = NONE

 

THE NOZZLE SIZE GIVES THE NOMINAL FLOWRATE, IN GPH, FOLLOWED BY THE SPRAY 
ANGLE, IN DEGREE’S, AND THE SPRAY PATTERN, EITHER “A” FOR HOLLOW CONE OR “B” 
FOR SOLID CONE. FOR EXAMPLE, A NOZZLE RATED AT 0.65 GPH @ 100 PSIG THAT PROVIDES 
AN 80° SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE 
TABLE AS “0.65 X 80

°

A

”. 

 
For more specific burner information, contact Crown Boiler Co, P.O. Box 14818 3633 I St.. Philadelphia, PA 19134 
 
 

Beckett AFG

Beckett NX

Carlin

Riello

CSHB60-90

70,000

60,000

0.50 x 80° A

0.40 x 70° A

0.50 x 70° A

0.50 x 80° A

CSHB60-90

85,000

73,000

0.60 x 80° A

0.50 x 70° A

0.60 x 70° A

0.60 x 80° A

CSHB60-90

106,250

90,000

0.75 x 80° A

0.60 x 70° A

0.75 x 70° A

0.70 x 80° A

INPUT CAPACITY SELECTION CHART

NOZZLE SIZE (GPH x TYPE)

EFFECTIVE  
HEATING 
CAPACITY** 
(BTU/HR)

EQUIVALENT 
HEAT INPUT 
RATE* 
(BTU/HR)

UNITS

 
All rates shown achieved with 120 PSIG pump pressure for Beckett AFG,  150 PSIG pump pressure for Beckett 
NX, 150 PSIG pump pressure for Carlin, and 145 PSIG pump pressure for Riello.  
* Based on #2 domestic heating fuel oil having heating value of 140,000 BTU per gallon. 
** Based on thermal efficiency of 84%-85%. 

 
 

Содержание CSHB60-90XE

Страница 1: ...alteration service or maintenance can cause a fire or explosion resulting in property damage personal injury or loss of life For assistance or additional information consult a qualified installer or...

Страница 2: ...ry substantial property damage or death See Page 5 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 8 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 9 cWAR...

Страница 3: ...R CONDITIONING 4 D FILTERS MOUNTED EXTERNAL TO FURNACE 4 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 6 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANING INSTRUCTIONS 8 III...

Страница 4: ...rotected to avoid physical damage by vehicles cWARNING This furnace is not to be used as a construction heater 5 Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MATERIAL COMBU...

Страница 5: ...oil furnaces If a power venter must be used it is the responsibility of the installer and power venter manufacturer to design and assemble a satisfactory power vent system A VENTING NOTE On the CSHB6...

Страница 6: ...n air inlet pipe diameter is also 4 inch diameter For Riello the combustion air inlet pipe will be reduced to 3 inch diameter with the included Riello side wall vent kit For Beckett the combustion air...

Страница 7: ...t dampers or other means used to control flow of air should be provided to prevent chilled air from entering the furnace If such a damper is manually operated it must be equipped with a means to preve...

Страница 8: ...k can be anchored to the furnace with screws or pop rivets through the securing flange of the filter rack Connect the return air plenum to the filter rack and slide the filter into place Dimensions fo...

Страница 9: ...he chamber during shipping and helps to maintain insertion depth DO NOT remove this retainer when installing burner Fig 4 Typical location of the overfire air tap and components in burner mounting pla...

Страница 10: ...RATED AT 0 65 GPH 100 PSIG THAT PROVIDES AN 80 SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 A For more specific burner information contact Crown Boiler Co P O...

Страница 11: ...th access to the inside of the heat exchanger through the burner area clean out openings and vent pipe connection it is possible to use a long flexible wire brush and an industrial type vacuum cleaner...

Страница 12: ...oloration of materials and damage from rust or corrosion FLUE PIPE VENT PIPE OR CONNECTOR The furnace vent pipe should be inspected for signs of rust corrosion pitting or holes in pipe and leakage aro...

Страница 13: ...em and home cWARNING To avoid injury from moving parts hot surfaces or electrical shock shut off the power to the furnace before removing any furnace access doors to service the air filters The filter...

Страница 14: ...All installations and services must be performed by qualified service personnel APPENDIX A Replacement Parts List 11...

Страница 15: ...All installations and services must be performed by qualified service personnel APPENDIX B Wiring Diagrams BLOWER SPEED TAPS COOL A C Tap HEAT Heating Tap LOW Constant air or Dehumifier 12...

Страница 16: ...All installations and services must be performed by qualified service personnel All installations and services must be performed by qualified service personnel 13 13...

Отзывы: