B. MOUNTING THE OPERATOR

Mount the operator according to the chosen illustration 

on page 2. The operator must be installed level.  With 

the door in the closed position drill the door to receive 

the door bracket (Note: fasteners are supplied by 

others).  Attach the arms from the operator to the door 

bracket.  Manually swing door open and closed ensuring 

both the door and operator function freely.

C. WIRING OPERATOR AND CONTROLS:

(1) No. 1502 Electric Operators are intended for 

applications  with motor branch circuits that have voltage 

and current characteristics to meet the operators’ 

ratings.  Branch circuit, branch circuit disconnecting 

means, and branch circuit over current protection are to 

be properly sized in respect to the operators’ horsepower 

rating.

WARNING: Insure operator branch circuit is 

disconnected from power source when installing, 

adjusting or servicing operator.

(2) 

Be sure all power is off.

  Wire the electric operator 

and controls according to the wiring diagrams provided 

in the installation packet.

D. START-UP:

(1) Confirm all wires are correctly connected to 

terminals.  Reference wiring schematic provided in the 

installation packet.

(2) LIMIT SWITCH ADJUSTMENT:

  (a)  

Disconnect the Electrical Power Supply to the  

  Operator Control Box.

  (b)   Unscrew limit switch cover and expose assembly.

Reference 

Figure 3. Rotary Cam Limit Switch 

Assembly

.

Note: For right hand pull to open or left hand push to 

open operators.
 (

a)  

 LSO = Limit Switch Open 

(Wired Normally Closed)

 

   

This limit shuts off the electric operator when the    

 

 

 door reaches the full open position. (Light on  

 

               PLC turns 

OFF

 when activated)

 (b)   

LSC = Limit Switch Close 

(Wired Normally Closed)

  

  This limit shuts off the operator when the door  

 

 

 

  has reaches the full closed position. (Light on                       

               PLC turns 

OFF

 when activated)

 (c)   

LSCO = Limit Switch Creep Open 

(Wired Normally 

Open)

  

  This limit activates the creep mode during the  

 

 

 

  end of open cycle. When the limit switch is 

 

 

  actuated the door travels in the open direction at 

 

 

  a reduced speed. (Light on PLC turns 

ON

 when 

   

activated)

 (d)   

LSCC = Limit Switch Creep Close 

(Wired Normally 

Open

)

   

This limit activates the creep mode during the 

 

 

  closing cycle. When this limit switch is actuated

              the door travels in the closed direction at a    

              reduced speed. (Light on PLC turns 

ON

 when 

   

activated) 

 

     

U.L. recognized snap-action 

switches.  Supplied as 

SPDT, DPDT optional.

Rotary Cam Limit 

Switch Assembly

SRLS51-(      )-SP4

Plastic planetary gear 

reduction stages.  Sun gear 

is input, ring gear is 

stationary, planet carrier is 

output.  No lubrication.

17.5

29

75

Independent cam 

adjusting screw with 

self-locking adjustment.

Gear switching stages are 

same as gear reduction 

stages except cam is on 

planet carrier.  Sun gears 

connected in parallel.

Primary gear stages yield 

mulitiplier for 

input/cam shaft ratio.

Figure 5. Rotary Cam Limit Switch Assembly

Crown Industrial Operators • 213 Michelle Ct. • So. San Francisco, Ca 94080-6202 

Phone: (650) 952-5150 • Fax: (650) 873-1495

www.crown-industrial.com Email: [email protected]

G-1001

3

Содержание Aut-o-doR 1502-1

Страница 1: ...o San Francisco CA 94080 Phone 650 952 5150 Fax 650 873 1495 website www crown industrial com Copyright Crown Industrial Operators 2011 GENERAL INSTALLATION OPERATION MAINTENANCE and PARTS MANUAL for...

Страница 2: ...cement Parts 6 B Parts List 6 7 WARRANTY 11 Note We reserve the right to modify or change without prior notice any statements or information contained herein If exact dimensions or specifications are...

Страница 3: ...allation packet is a copy of the packing slip for the components supplied with the order Compare the components received with the packing slip to insure that all equipment is complete 2 REVIEW INSTALL...

Страница 4: ...tor Assembly The angle bracket is mounted to the face of the door with fasteners while the other end mounts directly to the operator drive shaft Note For push to open applications the operator is moun...

Страница 5: ...hand push to open operators a LSO Limit Switch Open Wired Normally Closed This limit shuts off the electric operator when the door reaches the full open position Light on PLC turns OFF when activated...

Страница 6: ...extended can engage the limit switch roller Adjust the limit switch by turning the limit switch adjusting screw until half of the extended cam travels past the roller When this limit switch roller is...

Страница 7: ...til the door begins to move For each adjustment be sure to stand clear of the door 7 Reset the run and creep speed pots in the control box to a combined equivalent speed ASP as fied in the table on Sa...

Страница 8: ...son or company to whom the invoices to be sent B PARTS LIST The following pages list the replacement parts which are illustrated in page 7 Part Number Description 1502P27 Electric Magnetic Clutch Asse...

Страница 9: ...Pkg and Pull to Open Accessory Pkg are not shown 1502P37 Limit Switch 4 1 Adjustment Screws for Limit Switch Cams Operator Name Plate Indicates Model 1502 Serial 1502 Operator without Cover 1502 Opera...

Страница 10: ...ORTH ABOVE Operator Serial Number ________________________________ H P _____________________________________ Supplied on Crown Industrial Operators Order Number _______________________________________...

Отзывы: