Sequence of Operation, Intermittent Ignition, Less Tankless Heater
1) When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the vent damper. As-
suming that there is no call for heat, and that the damper switch is in the “automatic” position, the damper will close.
2) A call for heat from the thermostat energizes relay coil 1R (the relay on the L8148E), causing contacts 1R1 and 1R2 to make.
Contact 1R1 starts the circulator. Contact 1R2 sends power to the high limit.
3) Assuming that the high limit is made, current will flow to pin terminal #2 (orange) at the vent damper and the damper will
open.
4) Once the vent damper is fully open, an end switch inside the damper will make, energizing pin #3 (red) at the damper. This
pin is connected through the damper harness to terminal “B1” on the L8148E. At this point in the operating sequence, 24
volts is present across “B1” and “B2”.
5) Under normal conditions, the flame roll-out switch and blocked vent switch are made. Voltage will therefore immediately ap-
pear across the “24V” and “24V (GND)” terminals on the ignition module.
6) Upon application of voltage across the “24V” and “24V (GND)” terminals, the ignition module will start an ignition spark at
the pilot and apply 24 volts across the pilot valve (terminals “PV” and “MV/PV”).
7) Once the pilot is established, the pilot flame will act as a diode, converting the AC current at the electrode to a half wave DC
current at the pilot’s ground strap. This DC current flows through the boiler to the “GND (BURNER)” connection on the igni-
tion module. For the ignition module to recognize that a pilot flame is present, the DC current flowing into this terminal must
be in excess of approximately 1.0 uA.
8) Once the ignition module detects the presence of a pilot flame, voltage is applied across the main valve (terminals “MV” and
“MV/PV”), opening the valve and establishing main flame.
9) The way in which the ignition module handles failure to establish pilot or the loss of an already established pilot depends
upon the exact ignition module supplied with the boiler. For more information on module operation, consult the ignition mod-
ule instructions supplied with the boiler or the local Crown representative.
Sequence of Operation, Intermittent Ignition, With Tankless Heater
1) When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the vent damper. As-
suming that there is no call for heat, and that the damper switch is in the “automatic” position, the damper will close.
2) If the boiler water temperature is less than the low limit setting minus the differential setting, terminals “R” and “B” in
the L8124E are made through the low limit switch. The low limit switching action is SPDT with “R” being common. “R”
and “W” are therefore open whenever “R” and “B” are made. This means that while “R” and “B” are made relay coil R1 is
deenergized, regardless of whether or not there is a call for heat. The circulator will therefore not operate if the boiler water
temperature is too low to generate domestic hot water.
3) Assuming that the high limit is made, current will flow to terminal “B1” on the L8124E and then to terminal “2” (orange) at
the vent damper and the damper will open.
4) Once the vent damper is fully open, an end switch inside the damper will make, energizing pin #3 (red) at the damper. The
red wire from this pin runs to the flame rollout switch.
5) Under normal conditions, the flame roll-out switch and blocked vent switch are made. Voltage will therefore immediately ap-
pear across the “24V” and “24V (GND)” terminals on the ignition module.
6) Upon application of voltage across the “24V” and “24V (GND)” terminals, the ignition module will start an ignition spark at
the pilot and apply 24 volts across the pilot valve (terminals “PV” and “MV/PV”).
7) Once the pilot is established, the pilot flame will act as a diode, converting the AC current at the electrode to a half wave DC
current at the pilot’s ground strap. This DC current flows through the boiler to the “GND (BURNER)” connection on the igni-
tion module. For the ignition module to recognize that a pilot flame is present, the DC current flowing into this terminal must
be in excess of approximately 1.0 uA.
8) Once the ignition module detects the presence of a pilot flame, voltage is applied across the main valve (terminals “MV” and
“MV/PV”), opening the valve and establishing main flame.
9) The way in which the ignition module handles failure to establish pilot or the loss of an already established pilot depends
upon the exact ignition module supplied with the boiler. For more information on module operation, consult the ignition mod-
ule instructions supplied with the boiler or the local Crown representative.
10) The boiler will fire until the boiler water temperature is approximately equal to the low limit setting. Once the water tem-
perature reaches this point, “R” and “B” open and “R” and “W” make. At this point, a call for heat from the thermostat will
energize 1R, making contacts 1R1 and 1R2. Contacts 1R1 energize the circulator. Contacts 1R2 switch current from the “hot”
side of the transformer secondary to the high limit switch. If the high limit is made, current flows to terminal “B1” and the
ignition sequence is then the same as it is for a call for burner operation from the low limit (see (3) above).
Содержание CWI103
Страница 2: ......
Страница 17: ...15 15 FIGURE 12 INDIRECT WATER HEATER BOILER SIDE PIPING FIGURE 11 STANDARD BOILER PIPING ...
Страница 19: ...17 17 FIGURE 15 BOILER PIPING WITH CHILLER FIGURE 14 ISOLATION OF BOILER FROM SYSTEM WITH A HEAT EXCHANGER ...
Страница 29: ...27 27 FIGURE 24a GAS VALVE DETAIL HONEYWELL VR8204 AND VR8304 FIGURE 24b GAS VALVE DETAIL ROBERTSHAW 7000DERHC ...
Страница 34: ...32 32 Notes ...
Страница 41: ...39 39 Notes ...
Страница 43: ...41 41 ...
Страница 45: ...43 43 ...
Страница 47: ...45 45 ...
Страница 49: ...47 47 FIGURE A1 BASE HEAT EXCHANGER FLUE COLLECTOR ASSEMBLY ...
Страница 51: ...49 49 FIGURE A2 JACKET INSTALLATION ...
Страница 53: ...51 51 FIGURE A3 TAPPING LOCATIONS SEE TEXT FOR TAPPING USES ...
Страница 54: ...52 52 Notes ...
Страница 55: ...53 53 Notes ...