15
TABLE 13.0: ERROR CODES
Error
Code Meaning
Possible Cause
2
Pressure Switch failed to open
Jumped air pressure switch
•
Condensate in air pressure switch or switch tubing
•
Defective air pressure switch
•
4
Low Flame Signal
Low gas pressure at gas valve inlet
•
Partially plugged pilot tubing or pilot orifice
•
Loose connection in ignition cable or ground wiring
•
Dirty pilot electrode/ground strap
•
Pilot electrode porcelain cracked
•
Damaged pilot hood/ assembly
•
Defective control
•
6
Pilot Flame detected when no
flame should be present
Defective gas valve
•
High gas pressure
•
Defective control
•
18
Internal electronics failure
Possible internal problem with boiler control. Cycle power to the boiler and
•
replace control if problem persists.
23
Flame sensed during 30s pre-
purge (before pilot valve opened)
Defective gas valve
•
High gas pressure
•
Defective control
•
29
Air pressure switch failed to
close
Vent system blockage
•
Vent system not constructed in accordance with installation manual (exces-
•
sive length, undersized pipe, wrong terminal, etc)
Condensate or leakage in air pressure switch tubing
•
Winds in excess of 40mph
•
32
Boiler water temperature sensor
failure
Loose sensor connection at control
•
Defective Sensor
•
Defective control
•
35
Duplicate Zone
Error code reserved for future use
57
Grounded pilot electrode
Condensate or foreign material is shorting pilot electrode to ground.
•
Ignition cable insulation is damaged and touching ground.
•
Pilot is damaged
•
58
AC Power Frequency Error
120VAC power supply frequency is incorrect (Should be 60Hz)
•
120VAC power supply is dirty (consult electrician and/or Utility)
•
Boiler water temperature sensor common (center wire) is damaged and
•
shorted to ground
59
Line voltage error
(Supply voltage too high or low)
Power supply voltage is incorrect (should be 120VAC nominal)
•
Defective or incorrect 24VAC transformer
•
Loose 120VAC connection or 24VAC connection between transformer and
•
control
60
Thermostat input higher than
threshold
External voltage is applied to thermostat connections (most common cause is
•
external transformer in old thermostat wiring.
61
Line Voltage Unstable
120VAC power supply is dirty (consult electrician and/or Utility)
•
Loose 120VAC connection or 24VAC connection between transformer and
•
control
Large electrical loads elsewhere on the installation are switching on and off,
•
causing incoming voltage to swing excessively at boiler.
63
Maximum recycles exceeded
See Error Code 4 above (boiler lost proof of pilot 6 times in a row)
•
64
Internal failure
Improper pilot operation
•
If problem persists, replace control
•
89
EnviraCom communication lost
Should not be observed on BWF or CWD Series Boilers.