background image

34

14) Place the boiler back in operation using the procedure outlined in “Start-up”. Check the pilot line and any other gas piping
disturbed during the inspection process for leaks.

Heat Exchanger Cleaning Procedure

1)

Turn off electrical power and gas supply to the boiler

2)

Disconnect the damper and vent connector from the boiler.

3)    Remove the upper front and top jacket panels. If possible, remove the rear and left side jacket panels
4)

Remove the burners.

5)

Remove the blocked vent (“spill”) switch

6)

Remove the ¼-20 nuts and washers holding the flue collector onto the heat exchanger.

7)

Carefully remove the flue collector gasket strips and set them aside.

8)

Remove the flue collector from the heat exchanger.

        9)

Clean the flue passageways using a stiff bristle brush. Be certain that all foreign material is removed from the gaps
between the pins

10) Clean the bottom surfaces of the heat exchanger
11) Put a light in the combustion chamber and look through the flue passages from the top to verify that they have been

thoroughly cleaned.

12) Replace the flue collector gasket strips. If desired, RTV silicone sealant with a 500F intermittent duty temperature may be
substituted for this rope gasket. The flue collector must be thoroughly sealed to the heat exchanger.
13) Replace the ¼-20 nuts and washers that hold down the flue collector

14) Reattach all the jacket components.
15) Reinstall burners, being careful to put the pilot main burner in its original location.
16) Replace the blocked vent switch.
17)  Reconnect the damper and vent system.

WARNING

SOOT  DEPOSITS  IN  THE  FLUE  PASSAGES  ARE  A  SIGN  THAT  THE  BOILER  MAY  BE  OPERATING  AT  HIGH
CARBON  MONOXIDE  (CO)  LEVELS.   AFTER  CLEANING  THE  BOILER  OF  SOOT  DEPOSITS,  CHECK  THE  CO
LEVEL  IN  THE  FLUE  GAS  TO  INSURE  THAT  THE  BOILER  IS  OPERATING  PROPERLY.
   If it is necessary to check CO, use a combustion analyzer, or other instrument which is designed to measure CO in flue gas.
A CO “sniffer” designed for testing CO levels in ambient air cannot be used to check boiler combustion. Take a flue gas
sample by inserting a sample probe through the draft diverter opening and into the flue collector so that the sample is taken
in the area directly over the heat exchanger. Do not take a sample until the boiler has been firing for at least five minutes.
   A normal CO reading for a BSI series boiler is less than 50ppm (0.005%). A reading of more than 100ppm (0.01%) is indica-
tive of a combustion problem.
   Some causes of excessive CO include:

Incorrectly sized main burner orifice for the altitude at which boiler is installed

Crooked or out-of-round orifice holes (never attempt to drill orifice for this boiler in the field)

Partially plugged flue passages

Improper manifold pressure

Foreign material in burner venturis or burner ports

Leak in seal between flue collector and heat exchanger

Inadequate supply of combustion air

33

Содержание BERMUDA BSI069

Страница 1: ...ffixed on or adjacent to the boiler WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or loss of life For assistance or additional informa tio...

Страница 2: ...AppendixA Knockdown BoilerAssembly 47 I Product Description The BSI series boilers are low pressure cast iron gas fired steam boilers designed for use in closed steam heating systems These boilers are...

Страница 3: ...URATION Combustion efficiency Volume to normal water line NOTE BSI345 and BSI379 not available for use with LP gas Suffix E Intermittent Ignition Suffix S Standing Pilot Add Suffix N for Natural Gas o...

Страница 4: ...for the correct gas natural or LP The BSI345 and BSI379 may only be used with natural gas 5 Boilers installed at altitudes above 2000 ft require different burners and main burner orifice than those at...

Страница 5: ...Air for Combustion and Ventilation of the National Fuel Gas Code NFPA 54 ANSI Z223 1 To ensure an adequate supply of combustion ventilation and flue gas dilution air supply start by determining wheth...

Страница 6: ...square inch per 1000 BTU hr input of all gas burning appliances in the boiler room The minimum opening dimension is 3 inches Minimum opening free area is 100 square inches per opening If the total vo...

Страница 7: ...7 6 FIGURE4 ALLAIRFROMOUTDOORS VENTILATED CRAWL SPACE AND ATTIC FIGURE5 ALLAIRFROMOUTDOORS VIA VENTILATED ATTIC FIGURE3 BOILERINSTALLEDINCONFINEDSPACE ALL AIR FROM INSIDE...

Страница 8: ...8 FIGURE6 ALLAIRFROMOUTDOORS USING OPENINGSINTOBOILERROOM FIGURE7 ALLAIRFROMOUTDOORS USING HORIZONTAL DUCTS INTO BOILER ROOM 7...

Страница 9: ...n exterior chimneys may be used An exterior masonry chimney may be used if it is lined with B vent or a listed chimney lining system 5 This boiler may be vented using a listed power venter The power v...

Страница 10: ...d with each appliance remaining connected to the common venting system placed in operation while the other appliances remaining connected to the common venting system are not in operation a Seal any u...

Страница 11: ...11 10 FIGURE8 BSI BOILERTYPICALVENTSYSTEM INSTALLATION AND COMPONENTS FIGURE 9 VENTDAMPERINSTALLATIONDETAILS RIGHT SIDE VIEW...

Страница 12: ...ows typical gas piping connection to the BSI boiler A sediment trap must be installed upstream of all gas controls Install a manual shut off valve outside the jacket and ground joint union as shown Th...

Страница 13: ...n Figure 12 and appears to be working If two or more steam mains must be connected to the boiler connect a separate take off for each main into the header between the riser s and equalizer Also note t...

Страница 14: ...area where it is not likely to become plugged by debris or subjected to freezing 4 Install drain valve into tapping on boiler left side using the 2 x 3 4 bushing provided see Figure 1 5 Connect system...

Страница 15: ...ERPIPINGMISTAKES FIGURE11 STEAMBOILERPIPINGFORGRAVITYRETURN A B C D BSI069 2 1 1 2 1 1 4 BSI103 2 1 1 2 1 1 4 BSI138 2 1 1 2 1 1 4 BSI172 2 1 1 2 1 1 4 BSI207 2 3 1 1 2 1 1 4 BSI241 2 3 2 1 1 2 BSI276...

Страница 16: ...on 2 Y Strainer Install a Y strainer to prevent sediment from accumulating inside the indirect water heater 3 Check Valve Prevents gravity circulation through the indirect water heater when the boiler...

Страница 17: ...WIRE feeder Do not alter factory boiler wiring Connect VXT 24 to CG400Aas follows Connect the BLACK lead on the feeder to terminal A on the LWCO Connect the WHITE lead on the feeder to terminal 2 on t...

Страница 18: ...igh limit described in Part IX must also be supplied by the installer Acall for heat from the indirect water heater thermostat will energize the relay making both sets of contacts One set of these con...

Страница 19: ...GURE14b WIRINGMCDONNELL MILLERWF2 U 24FEEDERORTHREE WIREHYDROLEVEL VXT 24FEEDERTOBOILEREQUIPPEDWITH 67L W C O CAUTION DO NOT INSTALL JUMPER BETWEEN 2 3 ON 67 L W C O FIGURE15 WIRINGINDIRECTWATERHEATER...

Страница 20: ...in gas flow through the control and burner operation Sequence of Operation Intermittent Ignition 1 When the boiler is energized 24 volts is immediately applied to terminals 1 blue and 4 yellow on the...

Страница 21: ...WIRINGDIAGRAM STANDINGPILOTANDMcDONNELL MILLERMODEL67LOWWATERCUTOFF L N V8295A BSI310 379 ONLY VENT DAMPER NOTE 2 NOTE 3 LESS VENT DAMPER 2 VENT DAMPER REQUIRED ON BSI069 BSI276 OPTIONAL ON BSI310 BSI...

Страница 22: ...er cut off interrupts burner operation McDonnell Miller 67 Low Water Cut off Interrupts burner operation if the water in the boiler drops below a safe level Burner operation is restored when the water...

Страница 23: ...terrupts burner operation when flames or excessive heat are present in vestibule The flame roll out switch is a single use device which must be replaced by an identical switch in order to restore norm...

Страница 24: ...should produce single steady medium blue flame covering around 3 8 to of thermocouple tip See Figure 21 for intermittent ignition Pilot burner produces three flames The center one should be a steady m...

Страница 25: ...manometer to the manifold outlet pressure tap on the gas valve see Figures 23 and 24 d Read the manifold pressure It should be set at NaturalGas LPGas Manifold Press inches w c 3 5 10 0 e If a manifol...

Страница 26: ...you light pilot burner with a match After about one minute release reset button Pilot should remain lit If it goes out turn gas control knob clockwise to OFF To relight repeat steps 5 9 If button does...

Страница 27: ...old the Knob while you light pilot burner with a match After about one minute release reset button Pilot should remain lit If it goes out turn gas control knob clockwise to OFF To relight repeat steps...

Страница 28: ...all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do try to light the pilot by hand not 5 Remove front access panel 6 Rotat...

Страница 29: ...lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do try to light the pilot by hand not 5 Remove f...

Страница 30: ...ler models should relight 20 After the boiler has operated for approximately 30 minutes check the boiler and heating system piping for leaks Repair any leaks found at once 21 Inspect the vent system f...

Страница 31: ...204ANDVR8304 INTERMITTENT IGNITION FIGURE 23a GASVALVEDETAIL HONEYWELLVR8200ORVR8300 STANDINGPILOT FIGURE 23b GASVALVEDETAIL ROBERTSHAW 7000ERHCANDHONEYWELLV8295 STANDINGPILOT FIGURE 24b GASVALVEDETAI...

Страница 32: ...ck the thermocouple for deterioration some discoloration of the thermocouple is normal If any deterioration is present replace the thermocouple Inspect the pilot assembly for deposits and deterioratio...

Страница 33: ...s present in the steam main takeoff close it Alternatively temporarily replace enough of the vents on the mains and or radiators with plugs so that 2 5 psi can be developed when the boiler is fired d...

Страница 34: ...llector 14 Reattach all the jacket components 15 Reinstall burners being careful to put the pilot main burner in its original location 16 Replace the blocked vent switch 17 Reconnect the damper and ve...

Страница 35: ...s assume that the vent damper is closed at the beginning of the troubleshooting process With the 120 volts applied to the boiler and no call for heat the damper should go to the closed position If it...

Страница 36: ...hermostat Thermostat misw ired or misapplied N N 24 volts between P2 and 2 on CG400 LWCO Jumper missing betw een 1 and P1 on CG400 Poor connection betw een transformer and terminals 1 2 on CG400 24 vo...

Страница 37: ...ational Fuel Gas Code Down draft Inadequate combustion air supply in boiler room Y N Y 24 volts across rollout switch Loose electrical connection in spill switch or rollout switch wiring or gas valve...

Страница 38: ...ve transformer See Note 6 on page 34 N Y Bad connection in thermostat w iring Defective thermostat Thermostat misw ired or misapplied N N 24 volts betw een terminal 1 on 67 LWCO and yellow tranformer...

Страница 39: ...onal Fuel Gas Code Down draft Inadequate combustion air supply in boiler room Y N Y 24 volts across rollout switch Loose electrical connection in spill switch or rollout switch wiring or gas valve com...

Страница 40: ...orifice partially plugged Y N N Y N Turn control on gas valve to ON Y END Defective gas valve Y START 24 VOLTS PRESENT ACROSS TH AND TR ON GAS VALVE BUT MAIN BURNERS DO NOT LIGHT Ensure knob on gas v...

Страница 41: ...rcelain cracked Pilot flame not covering gap between electrode and grounding strap Low gas pressure at gas valve inlet Defective S8600 module Main burner lights N Y 24VAC across terminals 1 2 on S8600...

Страница 42: ...rown distributor consult the area Crown representative or the factory at Crown Boiler Co Customer Service P O Box14818 Philadelphia PA 19134 www crownboiler com For boilers installed at elevations abo...

Страница 43: ...43 42...

Страница 44: ...36 3501136 3501136 3501136 48 PILOT TUBING 1 ea 90 042 90 042 90 042 90 043 90 043 90 043 900041 900041 900041 49 35 1600 392449 50 35 1650 392449 4 51 51 51a 51 51a 61 40mm BURNER LESS PILOT BRACKET...

Страница 45: ...45 44...

Страница 46: ...FLOAT TYPE L W C O 67 CR 2 400676 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 90a PROBE TYPE L W C O CG400 400821 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 91 PRESSURE GUAGE 95 070 1 ea...

Страница 47: ...47 46...

Страница 48: ...2 Once the heat exchanger has been placed on the base inspect the gasket for proper seal Repair or replace gasket if necessary 3 Secure the heat exchanger with 5 16 lock nuts with nylon inserts and wa...

Страница 49: ...49 48 FIGUREA1 BASE HEATEXCHANGER FLUE COLLECTORASSEMBLY...

Страница 50: ...g pilot boilers only E ControlandTrimInstallation Refer to Figure A3 for Tapping Locations 1 Install the pressure limit control into tapping H with the siphon A x bushing has been factory installed Do...

Страница 51: ...51 50 FIGUREA2 JACKETINSTALLATION...

Страница 52: ...8 Hydrolevel CG 400 Probe Low Water Cutoff a Mount the end of the BX cable containing the 3 wire Molex plug and the single red wire to the control box with the BX cable fitting nut supplied b Insert t...

Страница 53: ...53 52 FIGUREA3 TAPPING LOCATIONS SEE TEXT FOR TAPPING USES...

Страница 54: ...54 Manufacturer of Hydronic Heating Products P O Box 14818 3633 I Street Philadelphia PA 19134 7HO D ZZZ FURZQERLOHU FRP P N980423 10 10Rev 3...

Отзывы: