TABLE 13.0 - ERROR CODES
Error
Code Meaning
Possible Cause
4
Low Flame Signal
•
Low gas pressure at gas valve inlet
•
Partially plugged pilot tubing or pilot orifice
•
Loose connection in ignition cable or ground wiring
•
Dirty pilot electrode/ground strap
•
Pilot electrode porcelain cracked
•
Damaged pilot hood/ assembly
•
Defective control
6
Pilot Flame detected when no
flame should be present
•
Defective gas valve
•
High gas pressure
•
Defective control
18
Internal electronics failure
•
Possible internal problem with boiler control. Cycle power to the boiler and replace
control if problem persists.
23
Flame sensed during 1.7s pre-
purge (before pilot valve opened)
•
Defective gas valve
•
High gas pressure
•
Defective control
32
Boiler water temperature sensor
failure
•
Loose sensor connection at control
•
Defective Sensor
•
Defective control
35
Duplicate Zone
Error code reserved for future use
55
Damper failed to open after 60s
•
Loose or defective damper harness
•
Obstruction in path of damper blade
•
Defective damper
•
Defective control
56
Power at end of limit string when
it shouldn’t be.
•
Control, vent damper, or damper harness is defective. With Error 56 present, and
no call for heat, unplug damper harness from control and check for 24VAC between
termminal P6-5 on control (see Figure 9.2 for location) and ground. If voltage is
present, replace control. If not, inspect the damper harness for shorts or miswired con-
nections. If no harness defect is found, replace vent damper.
57
Grounded pilot electrode
•
Condensate or foreign material is shorting pilot electrode to ground.
•
Ignition cable insulation is damaged and touching ground.
•
Pilot is damaged
58
AC Power Frequency Error
•
120VAC power supply frequency is incorrect (Should be 60Hz)
•
120VAC power supply is dirty (consult electrician and/or Utility)
•
Boiler water temperature sensor common (center wire) is damaged and shorted to
ground
59
Line voltage error
(Supply voltage too high or low)
•
Power supply voltage is incorrect (should be 120VAC nominal)
•
Defective or incorrect 24VAC transformer
•
Loose 120VAC connection or 24VAC connection between transformer and control
60
Thermostat input higher than
threshold
•
External voltage is applied to thermostat connections (most common cause is external
transformer in old thermostat wiring.
61
Line Voltage Unstable
•
120VAC power supply is dirty (consult electrician and/or Utility)
•
Loose 120VAC connection or 24VAC connection between transformer and control
•
Large electrical loads elsewhere on the installation are switching on and off, causing
incoming voltage to swing excessively at boiler.
63
Maximum recycles exceeded
•
See Error Code 4 above (boiler lost proof of pilot 6 times in a row)
64
Internal failure
•
Loose or defective damper harness
•
Obstruction in path of damper blade
•
Defective damper
•
Improper pilot operation
•
If problem persists, replace control
89
EnviraCom communication lost
Communication lost between boiler control and certain Crown control options. Consult
Crown control option manual.
Содержание AWR038
Страница 2: ......
Страница 19: ...17 FIGURE 8 5 BOILER BYPASS PIPING FIGURE 8 6 ISOLATION OF BOILER FROM SYSTEM WITH A HEAT EXCHANGER...
Страница 23: ...21 FIGURE 9 0 LINE VOLTAGE FIELD CONNECTIONS FIGURE 9 1 LOW VOLTAGE FIELD CONNECTIONS...
Страница 24: ...22 FIGURE 9 2 INTERNAL CONNECTIONS DIAGRAM...
Страница 25: ...23 FIGURE 9 3 LADDER DIAGRAM...
Страница 43: ...41 Notes...
Страница 45: ...43...
Страница 47: ...45...