5. SPARE PARTS AND ACCESSORIES

Please refer to the Sensor Replacement Label mounted on the outside of

the 96HD housing for the correct replacement part number.

Description

Part no.

Complete 96HD sensor

Sensor

housing with sensor

only

Hydrogen sulphide

(96HD/HS)   S01750

E01229

Carbon monoxide

(96HD/CO)   S01751

E01344

Ammonia

(96HD/AM)   S01752

E01618

Oxygen

(96HD/OX)   S01753

E01488

Sulphur dioxide

(96HDSO)   S01901

E01232

M20 to 1/2” NPT adaptor

M02125

M20 to 3/4” NPT adaptor

M02281

Ceiling mounting bracket

M01401

Collector cone

C01051

Weatherproof cap

C01442

Sinter removal tool

M01614

Sinter assembly

S01781

Gasket 1

M04452

Gasket 2

M04128

Amplifier - toxic version

S01866

Amplifier - oxygen version

S01867

Terminal board

S01846

Relay board

S01847

Calibration gas

Contact Crowcon

Loctite no. 243

Contact Crowcon

89/336/EEC

This product has been tested and found to comply with the European Directive on EMC 89/336/EEC

Crowcon Detection Instruments Ltd, 2 Blacklands Way, Abingdon Business Park, Abingdon, Oxfordshire OX14 1DY, UK

Tel: +44 (0)1235 553057, Fax: +44 (0)1235 553062, email: [email protected], internet: http://www.crowcon.com

Installation, operating and maintenance instructions, M07194-A4

6. SPECIFICATION

Dimensions

200 x 115 x 115 mm (8” x 4

1

/

2

” 

x 4

1

/

2

”)

Weight

2.2 kg (4.8 lbs)

Material

96HD sensor housing: 316 Stainless steel

Junction box: Marine grade alloy

Temperature range

-10–55°C (14–131°F)

Humidity range

0–99% RH, non condensing

Ingress protection

IP66 with weatherproof cap

Explosion protection

Flameproof

Approval codes

CENELEC EEx d IIC T6
UL Class 1, Zones 1 & 2, AEx d IIC T6

Standards

EN50014, EN50018, UL2279

Zones

1 and 2

Gas groups

IIA, IIB and IIC

Operating voltage

10–30 Vdc

Operating current

Relay version:

100 mA (maximum)

Non-relay version:

50 mA (maximum)

Detector output

4–20 mA source or sink selectable

0 mA 

= Fault

2 mA

= Inhibit (4 mA option)

4–20 mA

= 0–100% LEL

24 mA

= Over range

Relay outputs

2 x Alarm relays SPNO (SPNC option)
1 x Fault relay SPNC (SPNO option)

Contact rating

1 A @ 30 Vdc

i.

Using a long instrument screwdriver, turn the relevant ALARM SET pot

mounted on the terminal board (see Diagrams 1 & 2) to adjust the alarm

level. Tripping of the ALARM 1 level relay is confirmed by the status LED

turning a steady red. Tripping of the ALARM 2 level relay is confirmed by

the Status LED flashing red.

j.

Once the alarm level has been set, place end of ‘CRO-Mag’ over the ‘UP’

or ‘DOWN’ arrow pads and reset the display to read zero.

k.

Place the end of the ‘CRO-Mag’ over the ‘MENU’ pad to return the

detector to normal operation, ie. No decimal points displayed, backlight

off and the Status LED indicating steady green.

l.

Check that the detector operates correctly by applying test gas as

necessary.

m.

Switch off and isolate power to the detector.

n.

Reset jumpers which may have been changed in step ‘d’ above.

o.

Replace the amplifier and close the junction box, ensuring that all screws

have been re-fitted correctly.

p.

Apply power to the detector and allow to stabilise before checking correct

operation.

q.

Re-calibrate if necessary as per section 4.1.

NOTES