 OVERVIEW

F300 Megablocks are DIN-rail mounted, device couplers for 

F

oundation

™ fieldbus 

or Profibus PA networks. They allow connection of field devices to the segment 
trunk cable and provide short-circuit protection to the segment.

Megablocks minimize hand wiring and allow individual devices to be added to 
and removed from the segment without disrupting network communication.

Megablocks are available in four, eight, and twelve port versions. Multiple 
Megablocks are easily wired together to allow larger segments to be constructed.

Each F300 Megablock includes an F97 Terminator for installation in the trunk 
terminals, which is clearly marked with a large ‘T’ for easy identification by field 
personnel.

Individual surge-protector modules (FS32) can also be fitted to any of the 
Megablock fieldbus terminals to provide protection against induced surges and 
transients that can potentially destroy or degrade certain components inside the 
F300 Megablocks.

DESCRIPTION

Simple and reliable interconnection

Each Megablock has dedicated connections for the fieldbus “home run” or trunk 
cable. Trunk connections are identified by their black connectors. Numbered 
(grey) connectors are provided for each spur.

Wiring connections to the Megablock are made using pluggable connectors 
(screw terminal type are standard, but other connection styles are available). 
These allow wire terminations to be made to the individual connectors, which are 
then plugged into the Megablock.  Devices can be connected and disconnected 
easily during commissioning. On completion, the connector retaining screws are 
tightened to secure each connector to the Megablock.

F300 megablock range 
MTL Fieldbus device couplers

Figure 1 .1

 -  Megablock models F312, F308 and F304

Содержание MTL F300

Страница 1: ...F300 megablock range MTL fieldbus device couplers July 2019 INM F300 rev 6 Instruction manual MTL fieldbus networks DRAFT 09 July 2019...

Страница 2: ...19 Declaration of Conformity A printed version of the Declaration of Conformity has been provided separately within the original shipment of goods However you can find a copy of the latest version at...

Страница 3: ...5 ELECTRICAL CONNECTIONS 3 5 1 DC Power Requirements 4 5 2 Terminator 4 5 3 Trunk connections 4 5 4 Spur port connections 5 5 5 Cable screen connections 5 5 6 Surge protection 5 6 TESTING 6 6 1 Power...

Страница 4: ...ontents of this manual and the product datasheet Ensure installation and operating personnel have received adequate training for this task Ensure that any operating instructions are fully understood b...

Страница 5: ...n also be fitted to any of the Megablock fieldbus terminals to provide protection against induced surges and transients that can potentially destroy or degrade certain components inside the F300 Megab...

Страница 6: ...ing bars for F312 pack of 10 The standard connector for the Megablock is a pluggable screw terminal elevator type Pluggable spring clamp connectors rely on constant spring pressure to maintain contact...

Страница 7: ...r the ledge of the DIN rail Push the Megablock against the edge of the rail then rotate the Megablock until it sits flat onto the DIN rail then release the pressure to allow the clips on the other sid...

Страница 8: ...minator so that the T F97 molded logo is facing inwards towards the body of the Megablock otherwise difficulty will be experienced in accessing the spring clamp buttons to remove it For screw terminal...

Страница 9: ...onnector provides and cable screen S connections See section 5 5 for information on cable screen grounding Cable screen connections The S screen terminals for the trunk and the spurs are interconnecte...

Страница 10: ...e FS32 and tighten its securing screws 7 Repeat 5 and 6 for all the other FS32 modules A separate grounding bar F300 BAR is used for the trunk connector which must be similarly connected to ground see...

Страница 11: ...is also applicable b This apparatus may be installed in a safe area and also in a Zone 2 location providing that the relevant installation conditions are met When mounted in a Zone 2 location the app...

Страница 12: ...epair This product cannot be repaired by the user and must be replaced with an equivalent certified product NOTE All MTL fieldbus power supplies are designed to protect the fieldbus trunk from transie...

Страница 13: ...t used if the F3xx contains an internal Terminator T part number suffix FM CONTROL DRAWING FOR F3XX MEGABLOCK SERIES FIELDBUS CONNECTION BLOCKS CID2 Zone 2 INSTALLATIONS Doc No 502 484 Rev C 0 Sheet 1...

Страница 14: ...nator Installation DIN Rail Mounting F3xx Megablocks are designed to be mounted on 35 mm DIN rail using the clip mechanism on the back of each unit Mounting can be vertical or horizontal Use of DIN ra...

Страница 15: ...o the apparatus to prevent the rated input being exceeded by transient disturbances of more than 140 of the rated voltage See footnote FISCO Ex ic IIC T4 Gc 1 The apparatus is to be installed in an en...

Страница 16: ...vided by Power Source or Power Supply Sheet 1 of 4 If the Fieldbus Power Supply is protected by a type of protection listed in IEC 60079 0 it may be installed in the Hazardous Area Megablock Part Numb...

Страница 17: ...EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT except gray spurs Gas Groups IIC IIB IIA C o 80nF 80nF 80nF L o 0 15mH 0 26mH 0 26mH CONTROL DRAWING...

Страница 18: ...ved by Cyrus Kelly Date 10 FEB 2017 Doc No 502 485 Rev E 0 Device Inductance 0 10 H Device Capacitance 0 5nF FISCO ic FNICO Installation Requirements Sheet 3 of 4 Installation to comply with IEC 60079...

Страница 19: ...ide in the two channels on each side of the F3xx until they latch in place at the bottom of the case The channels are sized differently so the Partition cannot be installed backwards If needed the F97...

Страница 20: ...u Street Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio 3 20090 Se...

Отзывы: