2.4  PC Board Settings

2.4.1  On-Card Jumpers
NOTE:  Dot position means jumper goes from center pin to the pin nearest the dot on the PCB. Also the first 
jumper designation is for switch A (J1) and the second is for switch B (J101).

JP1, JP101 - 3-pin jumper that works with JP3, JP103  

In the dot position when channel 1 alarms the 1582-14 will switch to channel 2 until channel 2 alarms. 
At this point, if channel 1 is still in alarm, the switch will stay on channel 2. When the channel 1 alarm 
clears if channel 2 is still in alarm, the switch will switch to channel 1. 
In the non-dot position, operates in conjunction with JP3 as noted below.
JP1, JP101 normal position - non-dot and operates in conjunction with JP3, JP103 as noted below.

JP2, JP102 - Input alarm condition 3-pin jumper

In the dot position open is normal operation, ground is alarm 
In the non-dot position ground is normal operation, open is an alarm.
JP2, JP102 normal position - dot

JP3, JP103 - LATCH to CH2 mode on / off - 3-pin jumper effective when JP1 is in the non-dot position.  

With  JP3 in the dot and JP1 in the non-dot, when channel 1 alarms, the 1582-14 switch switches to 
channel 2 and stays there until the reset button is pushed on the front panel or by an external closure to 
ground on the remote RESET pin on J8, and then it switches to channel 1. (If channel 1 alarms are 
cleared ). If in the ICS mode and originally set to CH2 the 1582-14 will not switch if CH2 alarms. 
Only the RESET functions (front panel pushbutton or J8 closure to ground) will return the switch to 
CH1.With JP3 in the non-dot and JP1 in the non-dot, when channel 1 alarms the 1582-14 switches to 
channel 2 until the alarm on channel 1 clears and then the 1582-14 switches back to channel 1 
automatically. 
JP3, JP103 normal position - dot .

JP4, JP104 - CH2 alarm enable / ignore - 3-pin jumper  dot position - Failure in CH1 will cause 

the 1582-14 to switch to CH2 even if CH2 is in alarm. LEDs will correctly show CH2 alarm status
Non-dot position - Failure in CH1 will cause the 1582-14 to switch to CH2 only if CH2 is not in alarm.
JP4, JP104 normal position - non-dot

1582-725 Manual, Rev. B

 

 

  Page 7

    

          4/10/14

Содержание 1582-725

Страница 1: ...proprietary to Cross Technologies Inc but may be reproduced or duplicated without the prior permission of Cross Technologies Inc for purposes of operating the equipment Printed in USA When ordering parts from Cross Technologies Inc be sure to include the equipment model number equipment serial number and a description of the part CROSS TECHNOLOGIES INC 6170 Shiloh Road Alpharetta Georgia 30005 770...

Страница 2: ...nship for a period of one year after shipment to customer Cross Technologies Inc s obligation under this warranty is limited to repairing or at Cross Technologies Inc s option replacing parts subassemblies or entire assemblies Cross Technologies Inc shall not be liable for any special indirect or consequential damages This warranty does not cover parts or equipment which have been subject to misus...

Страница 3: ...lear Factory set mode is generally 1 CH1 Prime Mode When power is first applied and there are no alarms CH1 is selected On power loss CH2 is the selected channel The Manual Select switch and contact closures to Remote Select pins when in Auto select CH1 or CH2 independent of alarms LEDs indicate alarm and switch conditions for CH1 and CH2 REMOTE or MANUAL operation and power on RF connectors are B...

Страница 4: ...ls are in alarm SWITCH RESET Resets switch to CH1 if it is good and switch is in the latch mode Also Resets REMOTE by returning operation to Auto Indicators LEDs CH1 ON LINE Turns green when Channel 1 is selected CH2 ON LINE Turns green when Channel 2 is selected MANUAL Turns red when the Manual Select switch manually selects channel 1 or 2 ALARM CH1 Turns red when an external alarm input closure ...

Страница 5: ...s J7A J7B Monitors and Controls Connectors J7A TOP J7B BOTTOM Function Pin Description ALARM 1 IN 13 Ground or Open selectable by JP2 JP102 gives CH1 alarm ALARM 2 IN 14 Ground or Open selectable by JP2 JP102 gives CH2 alarm REMOTE 1 IN 1 When in AUTO momentary ground on this pin selects CH1 REMOTE 2 IN 2 When in AUTO momentary ground on this pin selects CH2 REMOTE RESET IN 4 When in LATCH mode gr...

Страница 6: ...sition switch as follows LEFT manually select Channel 1 CENTER AUTO switch position determined by alarm and remote closures RIGHT manually select Channel 2 Switch RESET Resets switch to Channel 1 if it is good and switch is in the latch mode Also resets REMOTE selection to normal AUTO operation Common for the Chassis Common for the Chassis Item Description POWER 1 LED Turns green when power is app...

Страница 7: ...de on off 3 pin jumper effective when JP1 is in the non dot position With JP3 in the dot and JP1 in the non dot when channel 1 alarms the 1582 14 switch switches to channel 2 and stays there until the reset button is pushed on the front panel or by an external closure to ground on the remote RESET pin on J8 and then it switches to channel 1 If channel 1 alarms are cleared If in the ICS mode and or...

Страница 8: ...ote 1 or Remote 2 pins on J8 and then grounding the Remote reset pin on J8 causing the 1582 14 to go back to Auto in the channel last selected remotely if both channel alarms are clear or both channels are in alarm The initial channel can also be selected if both channel alarms are clear or both channels are in alarm S3 S103 positions 1 2 3 4 to OFF ICS is disabled Minimum Auto switching Return to...

Страница 9: ...ALL SWITCH POSITIONS IN THE ON SIDE POWER SUPPLY 2 POWER SUPPLY 1 SHOWN IN THE ICS MODE S4 S5 JP2 JP3 JP15 JP16 JP17 JP18 JP1 JP104 JP102 JP103 JP101 S3 S103 JP10 S104 S105 JP109 JP110 FIGURE 2 3 1582 725 PCB Settings Parts Locations 1582 725 Manual Rev B Page 9 4 10 14 ...

Страница 10: ...te selection after return to Auto if both channel alarms are clear or both channels are in alarm Auto switching occurs only if current channel alarms and the other channel is clear Non dot SWITCH A JP4 SWITCH B JP104 Dot SWITCH A JP1 JP2 JP3 SWITCH B JP101 JP102 JP103 S3 SWITCH A S103 SWITCH B ALL TO ON Factory set mode is generally 1 CH1 Prime Mode 2 7 Operation a Set the on board controls as des...

Страница 11: ... equipment is not compromised Additional space between units may be required E Circuit Overloading Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of circuits could have on over current protection and supply wiring Appropriate consideration of equipment name plate rating should be used when addressing this concern F Reliable Ea...

Страница 12: ...ES INC 6170 Shiloh Road Alpharetta Georgia 30005 770 886 8005 FAX 770 886 7964 Toll Free 888 900 5588 WEB www crosstechnologies com E MAIL info crosstechnologies com Printed in USA 1582 725 Manual Rev B Page 12 4 10 14 ...

Отзывы: