cGas Detector for Indoor Public Spaces - Installation Manual
Rev. A | 2020.11
choose from:
• 9,600
• 14,400
•
19,200 (default, confi gurable)
• 38,400
• 57,600
• 76,800
• 115,200
Select the preferred baud rate by pressing ENTER to save and Exit.
8.2.3 Modbus® Holding Registers
If you have specifi c requirements, have any questions or require clarifi cation
about the Modbus® holding registers, please contact CETCI for assistance.
8.3 Confi guring BACnet® Settings
The cGas Detector (CGAS-DP) can be confi gured with BACnet® output to
communicate with a BAS, DDC or similar control panel.
8.3.1 Change BACnet® MAC Address
The factory set default BACnet® MAC address is 100. The MAC ID along with
the Instance ID make up the complete ID for the device. Each device requires a
unique ID in order to communicate with the BAS / DDC. A MAC address should
be set for each digital cGas Detector during installation.
From the main display, press ENTER.
Enter passcode 1001 using the UP button and ENTER button.
Enter Password
1001
Press ENTER to access the Basic Menu.
Basic Menu
Press Enter