cGas Detector for Indoor Public Spaces - Installation Manual
7 MODBUS AND BACNET CONFIGURATION
NOTE: This entire chapter applies to CGAS-DP (digital) models only.
The cGas Detector can be changed from Modbus® to BACnet® or vice versa
in the fi eld.
7.1 Changing Digital Communication Type in the Field
When the communication type is changed, the device will reset, which will
briefl y interrupt communications on the network it is connected to.
From the main display, press ENTER.
Enter passcode 1001 using the UP button and ENTER button.
From the main display, press ENTER.
Enter passcode 1001 using the UP button and ENTER button.
Enter Password
1001
Press ENTER to access the Basic Menu.
Basic Menu
Press Enter
Comm Type
MODBUS
Press ENTER. Use the UP or DOWN buttons to choose MODBUS or BACNET or
Cancel. Press ENTER. If you have changed the communication type, the device
will display Reset Device.
Comm Type
>BACNET
Reset Device
Press ENTER and the cGas Detector will power off and on. This will cause a
brief interruption in communications if the cGas Detector is on a network.
NOTE: If you change the Comm Type, make sure you make the necessary
changes to the corresponding MAC, Baud and Instance ID as appropriate.
Refer to the following Sections 8.2 Confi guring Modbus® Settings or 8.3
Confi guring BACnet® Settings.